HYDRAcap-60+

Engineering summary from PDF text extraction for HYDRAcap-60+. Verify every value with the OEM datasheet.

Summary

Product identification

  • Product Type: Capillary Ultrafiltration Module
  • Model: HYDRAcap60+
  • Configuration: Capillary Ultrafiltration Module
  • Membrane Polymer: Hydrophilic Polyethersulfone
  • Nominal MWCO: 150,000 Daltons
  • Nominal Membrane Area: 605 ft² (56 m²)
  • Fiber Dimensions:
    • ID 0.031” (0.8 mm)
    • OD 0.055” (1.4 mm)
  • Certifications: NSF61, CA-DHS Verification

Performance†

  • Filtrate Flow: 14.7 – 35.7 gpm (3.3 – 8.1 m³/h)
  • Filtrate Turbidity: ≤ 0.07 NTU
  • Virus removal: ≥ 4 log
  • Bacteria removal: ≥ 4 log
  • Typical Filtrate Flux Range: 35 – 85 gfd (59 – 145 l/m²/h)

Operating limits‡

  • Maximum Applied Feed Pressure: 73 psig (5 bar)
  • Maximum Transmembrane Pressure: 20 psig (1.4 bar)
  • Maximum Backwash Transmembrane Pressure: 20 psig (1.4 bar)
  • Instantaneous Chlorine Tolerance: 100 ppm** (for 15 minutes or less)
  • Instantaneous Hydrogen Peroxide Tolerance: 200 ppm** (for 15 minutes or less)
  • Maximum Chlorine Exposure: 200,000 ppm-hrs
  • Maximum Instantaneous Feed Turbidity: 100 NTU
  • Maximum Operating Temperature: 104 °F (40 °C)
  • pH Operating Range: 4.0 - 10.0
  • Cleaning pH Range: 1.5 – 13.0
  • Operating Mode: Inside to Outside Filtration, Direct flow or Crossflow

Typical Process Conditions

  • Backwash Flux: 100 – 150 gfd (170 – 255 l/m²/h)
  • Backwash Duration: 30 – 60 seconds
  • Backwash Frequency: 20 – 60 minutes
  • Chemical Enhanced Backwash Frequency: 0 – 4 times per day
  • Chemical Enhanced Backwash Duration: 1 – 30 minutes
  • Disinfection Chemicals: NaOCl, H₂O₂, ClO₂, or NH₂Cl
  • Cleaning Chemicals: HCl, H₂SO₄, NaOH, or Citric Acid

Mechanical / hydraulic

  • Dimensions:
    • A: 63 inches (1600 mm)
    • B: 66 1/8 inches (1680 mm)
    • C: 67 1/4 inches (1708 mm)
  • Pipe connections: 2” Victaulic
  • Weight, average: 97 lbs. (44 kg)

Disclaimer: This summary is based on extracted text and may not include all figures, footnotes, or the latest revisions. For contractual data, please refer to the specific OEM PDF revision used for your project.