Back to Kurita
Kurita logo

Datasheet summary

RoQuest-6000

Engineering summary from PDF text extraction for RoQuest-6000. Verify every value with the OEM datasheet.

Summary

Product identification

RoQuest® 6000 is a liquid blend of organic coagulants and ferric sulfate.

Product Information

  • Appearance: Clear, dark brown liquid
  • pH (1% solution): 2.0-3.0
  • Specific Gravity (@25°C): 1.40-1.60
  • Soluble ferric ion: > 9.5%
  • Ferrous ion: < 0.2%

Performance Benefits

  • Contains more than 9.5% soluble ferric ion and less than 0.2% ferrous ion.
  • Filter-aid properties resist solids breakthrough in direct filter applications.
  • Low dosage requirements and effective over a wide pH range.
  • Capable of producing RO quality feedwater in multimedia and sand filters.
  • Compatible with polyamide and cellulose acetate RO membranes and Avista antiscalants, including Vitec® 3000, 3025, 5000, 5100 and 7000.

Instructions for Use

Injecting

Inject RoQuest 6000 at least 5 m upstream of multimedia filters. Do not use static mixers ahead of the filters.

Dosing

  • Typical dose: 5-35 mg/l
  • Alkalinity requirement: Approximately 0.25 mg/l of alkalinity expressed as calcium carbonate is required per mg/l of RoQuest 6000.
  • Residual alkalinity: A minimum of 25 mg/l of residual alkalinity is required.
  • Significant overdosing may cause degradation in filtered water quality.

Dilution

  • Feed neat if possible.
  • When dilution is necessary, dilute no more than 4:1 with RO permeate or deionized water.

Packaging and Storage

  • Standard Pack Sizes:
    • Pail: 45 lb (23 kg)
    • Drum: 500 lb (300 kg)
    • IBC tote: 2500 lb (1500 kg)
  • Protect from freezing.

Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.