Back to Wila Heat Exchangers
Wila logo

Datasheet summary

THE 40

Engineering summary from PDF text extraction for THE 40. Verify every value with the OEM datasheet.

Summary

Product Identification

  • Product Type: Tubular Heat Exchanger
  • Series: THE
  • Pressure Rating: Medium Pressure - 40 BAR
  • Manufacturer: Wila A/S

Description

The THE series Tubular Heat Exchanger is designed for fluid-to-fluid heat transfer, offering both heating and cooling capabilities. It features two pressure chambers within a combined housing: the "Tube side" or "Product side" encompassing the tubes, and the "Shell side" or "Service side" within the outer shell. The heat exchanger is constructed from EN 1.4404 (AISI 316L) stainless steel with a sanitary surface finish.

Operating Limits

  • Maximum Product Side Pressure: 40 bar[g]
  • Maximum Product Side Temperature: 85°C
  • Shell Side Maximum Pressure and Temperature Limits: These vary by heat exchanger size. For steam:
    • 0.5 m² and 1 m²: 10 bar[g] / 185°C
    • 2 m²: 8 bar[g] / 176°C
    • 3 m²: 6 bar[g] / 165°C
    • 4 m² and 6 m²: 3 bar[g] / 144°C
    • 8 m²: 2.3 bar[g] / 136°C

Materials and Surface Finish

  • Material: EN 1.4404 (AISI 316L) stainless steel
  • Outside Surface Roughness: ≤ 1.6µm
  • Internal Tube Side Surface Roughness: ≤ 0.8µm
  • Compatibility: All fluid media must be compatible with EN 1.4404 (AISI 316L) Stainless Steel.

Connections

  • Tube Side (P1 and P2) Connection Sizes:
    • Ø129mm shell: DN125, DN100, DN80, DN65 (DIN 32676-A); 4” (Ø101.6), 3” (Ø76.1), 2.5” (Ø63.5) (ISO 2852-2)
    • Ø209mm shell: DN150, DN125, DN100 (DIN 32676-A); 4” (Ø101.6) (ISO 2852-2)
  • Shell Side (S1 and S2) Connection Sizes:
    • For both Ø129mm and Ø209mm shells: DN50, DN40 (DIN 32676-A); 2” (Ø51), 1.5” (Ø38) (ISO 2852-2)
  • Other connection types and sizes are available upon request.

Regulations and Directives

The heat exchanger is designed and manufactured in accordance with:

  • European Commission regulation No. 2023/2006 (Good Manufacturing Practices)
  • European Parliament directive No. EN 1935/2004 (Food Contact Materials)
  • European Parliament directive No. EN 1907/2006 (Chemical Restrictions (REACH))
  • PED - Article 4.3 (SEP) in European Parliament directive No. 2014/68/EU (Pressure Equipment Directive) for fluid group 2 (non-dangerous fluids).

Documentation

The following documentation is typically provided:

  1. Customer drawing with description and design data table
  2. Declaration of conformity
  3. Pressure test certificate
  4. User Manual

Optional documentation can include: 5. 3.1 material certificates according to EN 10204 6. Weld-logs with associated welding certificates according to DS/EN ISO 9601-1

Model Naming Convention

  • THE-xx-xxx-40
    • THE: Tubular Heat Exchanger
    • xx: Heat transfer surface area (e.g., .5, 01, 02, 03, 04, 06, 08) in m²
    • xxx: Heat exchanger shell diameter in mm (e.g., 129 or 209)
    • 40: Design pressure in bar
  • THE-xx-xxx-yyy-zz (additional suffixes for connection types)

Dimensions

Detailed dimensions for specific models are provided in tables throughout the document. These tables include:

  • Stock number
  • Drawing number
  • Tube side connection (P1/P2)
  • Shell diameter (Ø)
  • Shell side connection (S1/S2)
  • Overall dimensions (A, B, C, D)
  • Tube bank configuration (e.g., 61 pc Ø12x1mm or 163 pc Ø12x1mm)
  • Dry weight

Disclaimer

This summary is based on extracted text and may not capture all figures, footnotes, or revisions. Contractual data must be verified against the specific OEM PDF revision used for the project.

Official datasheet (PDF)

Lenntech datasheet mirror

Curated from selected public technical reference material for discovery and preliminary comparison. This summary is not a substitute for a current certified manufacturer datasheet. Verify revisions and design limits before use.