Datasheet summary
TLCX 40
Engineering summary from PDF text extraction for TLCX 40. Verify every value with the OEM datasheet.
Summary
Product identification
- Product Name: TUBULAR LIQUID COOLER
- Product Type: TLCX
- Pressure Rating: MEDIUM PRESSURE - 40 BAR
- Manufacturer: Wila A/S
General Description
The TLCX Tubular Liquid Cooler is designed for fluid-to-fluid heat transfer (cooling or heating). It is constructed from EN.1.4404 (AISI 316L) stainless steel with a sanitary surface finish. The product side is suitable for foodstuff fluids.
Operating Limits
- Maximum Product Side Pressure: 40 barg
- Maximum Product Side Temperature: 85°C
- Maximum Service Side Pressure: 16 barg
- Maximum Service Side Temperature: 95°C
Material and Surface Finish
- Material: EN.1.4404 (AISI 316L) stainless steel
- Tube side surface roughness: ≤ 0.8 µm
- Shell side surface roughness: ≤ 1.6 µm
- All fluid media must be compatible with EN.1.4404 (AISI 316L) Stainless Steel.
Design and Construction
The heat exchanger features two pressure chambers:
- Tube side (Product side): Inner chamber consisting of tubes.
- Shell side (Service side): Outer chamber consisting of the shell and the outside of the tube bundle.
- Designs are based on Ø129x2mm or Ø209x3mm shells. Other sizes and pressure ratings are available.
Regulations and Directives
The heat exchanger is designed and manufactured in accordance with:
- European Commission regulation No. 2023/2006 (Good Manufacturing Practices)
- European Parliament directive No. EN 1935/2004 (Food Contact Materials)
- European Parliament directive No. EN 1907/2006 (Chemical Restrictions (REACH))
- PED - Article 4.3 (SEP) in European Parliament directive No. 2014/68/EU (Pressure Equipment Directive).
- Designed for fluid group 2 (non-dangerous fluids).
Connections
- Tube side (P1 and P2) connections:
- Ø129mm shell: DN125, DN100, DN80, DN65 (DIN 32676-A); 4” (Ø101.6), 3” (Ø76.1), 2.5” (Ø63.5) (ISO 2852-2)
- Ø209mm shell: DN150, DN125, DN100 (DIN 32676-A); 4” (Ø101.6) (ISO 2852-2)
- Shell side (S1 and S2) connections:
- For both Ø129 and Ø209 shells: DN20, DN25, DN40, DN50, DN65 (DIN 32676-A); 3/4” (Ø20), 1” (Ø25), 1.5” (Ø38), 2” (Ø51), 2.5” (Ø63.5) (ISO 2852-2)
- Other connection types and sizes are available.
- Recommendations: Follow fitting supplier guidelines and local legislations. Use SH or SSH clamping rings (or similar). For liquids, the outlet should be at the highest point.
Shell Side Workflow Limits
- 0.5 m²: 3 m³/h
- 1 m²: 3 m³/h
- 2 m²: 7 m³/h
- 3 m²: 12 m³/h
- 4 m²: 14 m³/h
- 6 m²: 21 m³/h
- 8 m²: 28 m³/h
Dimensions and Specifications
Detailed dimensions and specifications for various models (TLCX-.5 to TLCX-08) with Ø129mm and Ø209mm shells are provided in tables within the original document. These tables include:
- Stock number
- Drawing number
- Tube side connection (P1/P2)
- Shell diameter
- Service side connection (S1/S2)
- Dimensions (A, B, C, D)
- Tube bank details (e.g., 61 pc Ø12x1mm or 163 pc Ø12x1mm)
- Dry weight
See the official PDF for exact tabulated values for specific models.