Datasheet summary
Proline Prowirl F 200
PDF datasheet mirror for Proline Prowirl F 200 (Endress + Hauser Flow measurement). Verify with OEM before design.
Summary
Product identification
Proline Prowirl F 200 vortex flowmeter.
Benefits
- Easy energy management with integrated temperature and pressure measurement for steam and gases.
- Reliable and secure measurement technology compliant with ISO 12764.
- Consistent accuracy down to Re 10,000 due to a linear Vortex meter body.
- Long-term stability with a robust, drift-free capacitive sensor.
- Convenient device wiring with a separate connection compartment and Ethernet options.
- Safe operation without needing to open the device.
- Integrated verification with Heartbeat Technology.
Field of application
The Prowirl F is a multivariable flowmeter capable of inline wet steam measurement. It features PremiumCal for excellent measuring accuracy and high plant availability at low flow rates of gas, steam, and liquids. With loop-powered technology, it offers cost-effective integration and operational safety in hazardous areas, supported by Heartbeat Technology for process safety.
Features and specifications
General
- Measuring principle: Vortex
- Product headline: Versatile flowmeter with detection of wet steam conditions and best-in-class accuracy.
- Nominal diameter range: DN 15 to 300 (½ to 12")
- Measured variables: Volume flow, mass flow, corrected volume flow, energy flow, heat flow difference, temperature.
Wetted materials
- Measuring tube: 1.4408 (CF3M); CX2MW similar to Alloy C22, 2.4602
- DSC sensor: 1.4404 (316/316L); UNS N06022 similar to Alloy C22, 2.4602
- Process connection: 1.4404/F316/F316L); 2.4602
Performance
- Max. measurement error:
- Volume flow (liquid): ±0.75 %
- Volume flow (optional): ±0.65 %
- Volume flow (steam, gas): ±1.00 %
- Mass flow (saturated steam): ±1.7% (temperature compensated); ±1.5% (temperature/pressure compensated)
- Mass flow (superheated steam, gas): ±1.5 (temperature/pressure compensated); ±1.7% (temperature compensated + external pressure compensation)
- Mass flow (liquid): ±0.85%
- Measuring range (Liquid): 0.2 to 2100 m³/h (0.15 to 1520 ft³/min)
- Example condition: water with 1 bar a, 20 °C (14.5 psi a, 68° F)
- Measuring range (Steam, gas): 1.5 to 28000 m³/h (0.9 to 16600 ft³/min)
- Example condition: steam with 180 °C, 10 bar a (356 °F, 145 psi a); air with 25 °C, 4.4 bar a (77 °F, 63.8 psi a)
Operating limits
- Max. process pressure: PN 100, Class 600, 20K
- Medium temperature range:
- Standard: –40 to +260 °C (–40 to +500 °F)
- High/low temperature (option): –200 to +400 °C (–328 to +752 °F)
- Ambient temperature range:
- Compact version (standard): –40 to +80 °C (–40 to +176 °F)
- Compact version (option): –50 to +80 °C (–58 to +176 °F)
- Remote version (standard): –40 to +85 °C (–40 to +185 °F)
- Remote version (option): –50 to +85 °C (–58 to +185 °F)
Mechanical / hydraulic
- Sensor housing material: Sensor connection housing: AlSi10Mg, coated; 1.4408 (CF3M)
- Transmitter housing material: AlSi10Mg, coated; 1.4404 (316L)
- Degree of protection:
- Compact version: IP66/67, type 4X enclosure
- Sensor remote version: IP66/67, type 4X enclosure
- Transmitter remote version: IP66/67, type 4X enclosure
Electrical
- Outputs:
- 4–20 mA HART (passive)
- 4–20 mA (passive)
- Pulse/frequency/switch output (passive)
- Inputs: Current Input 4–20 mA (passive)
- Digital communication: HART, PROFIBUS PA, FOUNDATION Fieldbus
- Power supply:
- DC 12 to 35 V (4–20 mA HART with/without pulse/frequency/switch output)
- DC 12 to 30 V (4–20 mA HART, 4–20 mA)
- DC 12 to 35 V (4–20 mA HART, pulse/frequency/switch output, 4–20 mA input)
- DC 9 to 32 V (PROFIBUS PA, pulse/frequency/switch output)
Approvals and certifications
- Hazardous area approvals: ATEX, IECEx, cCSAus, JPN, EAC, UK Ex
- Product safety: CE, C-TICK, EAC, UK Ex
- Functional safety: Functional safety according to IEC 61508, applicable in safety-relevant applications in accordance with IEC 61511
- Metrological approvals: Calibration performed on accredited calibration facilities (acc. to ISO/IEC 17025); Heartbeat Technology complies with ISO 9001:2015 requirements.
- Marine approvals: ABS, LR, BV, DNV
- Pressure approvals: PED, CRN, AD 2000
- Material certificates: 3.1 material; NACE MR0175/MR0103, PMI (on request); welding test acc. to ISO 15614‐1, similar to ASME IX (on request)
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.
Official datasheet (PDF)
Curated from selected public technical reference material for discovery and preliminary comparison. This summary is not a substitute for a current certified manufacturer datasheet. Verify revisions and design limits before use.