Levelflex FMP50

PDF datasheet mirror for Levelflex FMP50 (Endress + Hauser Level measurement). Verify with OEM before design.

Summary

Product identification

  • Product: Levelflex FMP50
  • Type: Guided-wave radar level sensor

Application

  • Level measurement in liquids
  • Rod or rope probe options
  • Process connection: thread ¾" or adapter flange
  • International explosion protection certificates; WHG (German Water Resources Act); EN10204-3.1
  • Linearity protocol (3-point, 5-point)

Operating limits

  • Process temperature: –20 to +80 °C (–4 to +176 °F)
  • Process pressure: –1 to +6 bar (–14.5 to +87 psi)
  • Maximum measuring range:
    • Rod probe: 4 m (13 ft)
    • Rope probe: 12 m (39 ft)
  • Accuracy: ±2 mm (±0.08 in)

Feed water

  • Relative permittivity (εr): Affects pulse reflection. High εr (e.g., water) causes strong reflection; low εr (e.g., hydrocarbons) causes weak reflection.
  • Blocking distance (factory setting):
    • Up to 8 m probe length: 200 mm (8 in)
    • Over 8 m probe length: 0.025 × probe length
    • Can be reduced to 100 mm (4 in) for media with εr > 7.0.
    • No blocking distance in bypass/stilling wells.
  • Tensioning weight area: For rope probes with εr < 7, measurement is not possible from 0 to 250 mm (0 to 9.84 in) from the probe end.

Product water

  • Measured variable: Distance between reference point and product surface.
  • Level calculation: Based on empty distance entered.
  • Linearization: Optional, up to 32 points, for converting level to volume or mass. Preprogrammed tables for cylindrical vessels.

Electrical

  • Output signal:
    • HART: FSK ±0.5 mA over current signal, 1200 Bit/s, galvanically isolated.
    • Bluetooth® wireless technology: Requires order code 610 and option NF. Operates via SmartBlue app. Range > 10 m (33 ft). Encrypted.
    • PROFIBUS PA: Manchester Bus Powered (MBP), 31.25 kBit/s, voltage mode, galvanically isolated.
    • FOUNDATION Fieldbus: Manchester Bus Powered (MBP), 31.25 kBit/s, voltage mode, galvanically isolated.
    • Switch output (for HART devices): Open collector, programmable switch-on/off point, 0 to 100 s delay. Electrical data: U = 16 to 35 VDC, I = 0 to 40 mA.
  • Power supply: External power supply required. Specific terminal voltages and maximum loads depend on the configuration (2-wire, 4-wire) and approvals.
    • 2-wire, 4-20mA HART (passive): 11.5 to 35 VDC.
    • 4-wire, 4-20mA HART (active): 90 to 253 VAC or 10.4 to 48 VDC.
    • PROFIBUS PA, FOUNDATION Fieldbus: 9 to 32 V (non-hazardous), 9 to 30 V (hazardous).
  • Power consumption: Varies by configuration, e.g., < 0.9 W for 2-wire HART, 6 VA for 4-wire 90-253 VAC HART.
  • Current consumption:
    • HART: 3.6 to 22 mA nominal.
    • PROFIBUS PA: 14 mA nominal.
    • FOUNDATION Fieldbus: 15 mA nominal.

Mechanical / hydraulic

  • Probe types: Rod or rope.
  • Rod probe: Maximum length 4 m (13 ft), Material 316 L.
  • Rope probe: Maximum length 12 m (40 ft), Material 316 L.
  • Process connection: Thread ¾" or adapter flange.
  • Terminals: Plug-in spring terminals (without overvoltage protection) or screw terminals (with overvoltage protection).
  • Cable entries: M20x1.5, ½" NPT, G ½", M12 plug / 7/8" plug (non-Ex, Ex ic, Ex ia).
  • Weight: Not specified in extract.
  • Materials: Not specified in extract beyond probe materials.

Other features

  • Integrated data memory (HistoROM).
  • Multi-echo tracking for reliable measurement.
  • SIL2 as per IEC 61508, SIL3 for homogeneous redundancy.
  • Intuitive user interface with local language support.
  • Bluetooth® wireless technology for commissioning, operation, and maintenance.
  • Heartbeat Technology™.
  • Overvoltage protection options available.