Back to Endress + Hauser Level measurement
Endress+Hauser logo

Datasheet summary

Levelflex FMP56

PDF datasheet mirror for Levelflex FMP56 (Endress + Hauser Level measurement). Verify with OEM before design.

Summary

Product Identification

The Levelflex FMP56 and FMP57 are guided-wave radar level measurement devices.

Application

Designed for level measurement in bulk solids.

  • Probe Types: Rod or rope probe.
  • Process Connection: Thread (as of ¾") or flange.

Operating Limits

  • Process Temperature: –40 to +185 °C (–40 to +365 °F).
  • Process Pressure: –1 to +16 bar (–14.5 to +232 psi).

Measuring Range

  • Rod Probe: Maximum measuring range of 4 m (13 ft).
  • Rope Probe: Maximum measuring range of 45 m (148 ft).

The specific measuring range depends on the media group and probe type (bare metallic or PA-coated rope). See the official PDF for exact tabulated values.

  • FMP56 (Rope Probes): Maximum 12 m (39 ft).
  • FMP57 (Rod Probes): Maximum 4 m (13 ft).
  • FMP57 (Rope Probes): Maximum 45 m (148 ft).

Note: Measuring range may be reduced for media with strong signal damping.

Blocking Distance

  • Factory Setting (up to 8 m probes): 200 mm (8 in)
  • Factory Setting (over 8 m probes): 0.025 × probe length
  • Can generally be reduced to 100 mm (4 in) for media with εr > 7.0.
  • No blocking distance applies in bypass/stilling wells.

Performance Characteristics

  • Accuracy (Digital Output):
    • Measuring distance ≤ 15 m (49 ft): ±2 mm (±0.08 in)
    • Measuring distance > 15 m (49 ft): ±10 mm (±0.39 in)
  • Accuracy (Analog Output): ±0.02 % of span.
  • Non-repeatability: ≤ 1 mm (0.04 in).

Measurement error at the probe end is detailed in the document, varying with distance from the probe end and dielectric constant.

Output Signals

  • HART: FSK ±0.5 mA over current signal, 1200 Bit/s data transmission rate.
  • Bluetooth® Wireless Technology: Requires order code 610, option NF. Operates via SmartBlue app, range > 10 m (33 ft).
  • PROFIBUS PA: Manchester Bus Powered (MBP), 31.25 kBit/s, voltage mode.
  • FOUNDATION Fieldbus: Manchester Bus Powered (MBP), 31.25 kBit/s, voltage mode.
  • Switch Output: Open collector switch output, available for HART devices. Electrical connection data: U = 16 to 35 VDC, I = 0 to 40 mA.

Power Supply

  • 2-wire, 4-20 mA HART (passive): Terminal voltage 11.5 to 35 V. Maximum load R depends on supply voltage U₀.
  • 2-wire, 4-20 mA HART, switch output: Terminal voltage 13.5 to 35 V. Maximum load R depends on supply voltage U₀.
  • 2-wire, 4-20 mA HART, 4-20 mA: Channel 1: 13.5 to 30 V. Channel 2: 12 to 30 V.
  • 4-wire, 4-20 mA HART (active):
    • 10.4 to 48 VDC
    • 90 to 253 VAC (50 to 60 Hz)
  • PROFIBUS PA, FOUNDATION Fieldbus: 9 to 32 V.

Power consumption varies by configuration, from < 0.9 W to 6 VA.

Mechanical Construction

  • Materials: See official PDF for detailed material specifications.
  • Dimensions: See official PDF for detailed dimension drawings.
  • Weight: See official PDF for weight information.

Certificates and Approvals

Includes CE mark, RoHS, RCM marking, various Ex-approvals, Functional safety (SIL2/SIL3), ASME B31.1 and B31.3, Pressure Equipment Directive, Marine approval, Radio approval, and CRN approval.