Datasheet summary
Liquiphant Failsafe FTL80
Engineering summary from PDF text extraction for Liquiphant Failsafe FTL80. Verify every value with the OEM datasheet.
Summary
Product identification
- Product: Liquiphant FailSafe FTL80, FTL81, FTL85
- Type: Vibronic Point level switch for liquids
Application
The Liquiphant FailSafe is a point level switch for minimum and maximum detection (MIN/MAX) in liquids.
- Process temperatures: –60 to 280 °C (–76 to 536 °F)
- Ambient temperatures: –60 to 70 °C (–76 to 158 °F)
- Pressure: Up to 100 bar (1450 psi)
- Viscosity: Up to 10000 mPa·s
- Density: From 0.4 g/cm³ (0.4 SGU)
- Media: Suitable for highly corrosive media.
The device is designed for MIN and MAX safety applications up to SIL3 with a focus on fail-safe design and high availability. It features a permanent LIVE signal for function monitoring.
Operating limits
- Process temperature:
- FTL80, FTL81: –50 to +150 °C (–58 to +300 °F); –60 to +280 °C (–76 to +540 °F) (high-temperature version: 300 °C (572 °F) for a maximum of 50 cumulative hours)
- FTL85:
- ECTFE: –50 to +120 °C (–58 to +248 °F)
- PFA: –50 to +150 °C (–58 to +300 °F)
- Enamel: –50 to +150 °C (–58 to +300 °F)
- Ambient temperature range:
- Standard: –40 °C (–40 °F)
- Optional: –50 °C (–58 °F) or –60 °C (–76 °F)
- Pressure: Up to 100 bar (1450 psi)
Feed water
- Density setting:
- MAX mode: 0.4 to 2.0 g/cm³ (0.4 to 2.0 SGU)
- MIN mode: 0.4 g/cm³ (0.4 SGU)
- Viscosity:
- MAX mode: 10000 mPa·s
- MIN mode: 350 mPa·s
- MIN mode with coating, high temperature (230/280 °C): 100 mPa·s
- Solids content: Maximum ø5 mm (0.2 in)
Product water
- Output signal: 4-20 mA interface (acc. to NAMUR NE 06/NE 43)
- Status signals: LEDs indicate: Operation, Function check, Outside specification, Maintenance required, Failure, Power supply issues.
- Error current: < 3.6 mA (as per NAMUR NE 43)
Electrical
- Supply Voltage: DC 24 V nominal (DC 12 to 30 V range)
- Power consumption: < 660 mW
- Reverse polarity protection: Yes
- Connectable load (R): R = (U - 12 V) / 22 mA (where U is supply voltage)
- Galvanic isolation: Between sensor and power supply
Mechanical / hydraulic
- Sensor Types:
- FTL80: Compact
- FTL81: With pipe extension
- FTL85: With coated pipe extension (flanged version only)
- Housing types: Polyester, Stainless steel, Aluminum. Various degrees of protection (IP66, IP67, IP68) and NEMA ratings (4X, 6P) are available depending on the housing material.
- Process connections:
- Threads: G, R, NPT
- Flanges: EN, ANSI, JIS standards
- Weights:
- Basic weight (Sensor, G ¾ thread, Electronic insert, Polyester housing F16, Cover): 0.7 kg (1.5 lbs)
- Additional weights for various housings, temperature spacers, pressure-tight feedthroughs, threaded connections, and flanges are detailed in the document.
- Materials: Various materials are available for parts in contact with the process and non-process parts, including 316L, AlloyC22, ECTFE, PFA, and Enamel.
Performance characteristics
- Maximum measured error: ±1 mm (± 0.04 in)
- Non-repeatability: 0.1 mm (0.004 in)
- Hysteresis:
- FTL80, FTL81, FTL85 (ECTFE and PFA): approx. 2 mm (0.08 in)
- FTL85 (enamel): approx. 2.5 mm (0.1 in)
- Switching time:
- Fork covered: approx. 0.5 s ±0.2 s
- Fork exposed: approx. 1.0 s ±0.2 s
- Dwell time: at least 0.3 s
System components
- Nivotester FailSafe FTL825: A separate switching unit.
- Power Supply:
- Mains voltage version: AC/DC 230/115 V (AC 85 to 253 V, 50/60 Hz; DC 85 to 253 V)
- Extra-low voltage version: AC/DC 24 V (AC 20 to 30 V, 50/60 Hz; DC 20 to 60 V)
- Outputs: Two floating NO contacts (supervised safety contacts), one floating NC contact (signaling contact), fault-signaling relay.
- Switching capacity: Up to 253 V / 2 A / 500 VA (AC); Up to 40 V / 2 A / 80 W (DC).
- Installation: Vertically on DIN top-hat rail.
- Dimensions: 45 mm (W) x 108 mm (H) x 112 mm (D)
- Power Supply:
Certificates and approvals
The device has CE marking and complies with applicable EC Directives. Various other approvals are listed, including:
- ATEX (Zone 0, 1, 2, 20, 21, 22)
- CSA C/US (Div 1, Div 2)
- FM C/US (Div 1, Div 2)
- IECEx
- NEPSI
- TIIS
- WHG (overfill and leak detection)
- Marine approval (GL, ABS)
- CRN approval
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.