Datasheet summary
Micropilot FMR20B
Engineering summary from PDF text extraction for Micropilot FMR20B. Verify every value with the OEM datasheet.
Summary
Product identification
- Product: Micropilot FMR20B HART
- Type: Free-space radar
- Document: TI01796F/00/EN/03.24-00, 71687478, 2024-12-09
Application
- Continuous, non-contact level measurement of liquids and bulk solids
- Maximum measuring range up to 30 m (98 ft)
- Flow measurement in open channels or weirs with totalizer
Operating limits
- Process temperature: –40 to 80 °C (–40 to 176 °F)
- Process pressure: –1 to 3 bar (–14 to 43 psi)
- Operating height: Up to 5,000 m (16,404 ft) above sea level
Feed water
- Relative permittivity for liquids: εr ≥ 1.8
- Relative permittivity for bulk solids: εr ≥ 1.6
Product water
- Accuracy: Up to ± 2 mm (0.08 in)
Electrical
- Output signal: 4 to 20 mA with superimposed digital communication protocol HART, 2-wire
- Supply voltage: 12 to 30 VDC
- Power consumption:
- Non-hazardous area: Max. 500 mA
- Hazardous area: Max. 100 mA (in intrinsically safe circuit)
- HART specification: 7.6
- HART load: Min. 250 Ω
Mechanical / hydraulic
- Degree of protection: IP66/68 / NEMA Type 4X/6P
- IP68: 24 h at 1.83 m (6.00 ft) under water
- Weight:
- 40 mm (1.5 in) antenna: approx. 0.5 kg (1.1 lb) (including 5 m cable)
- 80 mm (3 in) antenna: approx. 0.7 kg (1.5 lb) (including 5 m cable)
- Materials:
- Antenna end process connection: PVDF
- Sensor housing/Cable entry process connection: PBT/PC (PC for dust ignition-proof)
- Counter nut: PA6.6
- Connecting cable:
- Available length: 5 to 300 m (16 to 980 ft)
- Material: PVC (or Halogen-free XLPE for marine approval)
Performance characteristics
- Reference conditions: As per IEC 62828-2
- Response time (damping off):
- Measuring rate ≤ 250 ms at 24 V
- Step response time < 1 s
- Warm-up time: ≤ 30 s
- Maximum measurement error (Accuracy):
- Liquids: Up to 0.25 m: max. ±10 mm (±0.39 in); > 0.25 m: ±2 mm (±0.08 in)
- Solids: Up to 0.8 m: max. ±20 mm (±0.79 in); > 0.8 m: ±4 mm (±0.16 in)
- Influence of ambient temperature:
- Digital output (HART): Average TC = ±2 mm (±0.08 in)/10 K
- Analog (current output): Zero point TC = 0.02 %/10 K; Span TC = 0.05 %/10 K
- Vibration resistance: 1.25 (m/s²)²/Hz, ~5 g (5 to 2,000 Hz)
- Electromagnetic compatibility (EMC): Max. measured error < 0.5 % of span
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.