Back to Endress + Hauser Level measurement
Endress+Hauser logo

Datasheet summary

Prosonic S FMU90

Engineering summary from PDF text extraction for Prosonic S FMU90. Verify every value with the OEM datasheet.

Summary

Product Identification

  • Product Name: Prosonic S FMU90
  • Product Type: Transmitter for 1 or 2 ultrasonic sensors
  • Technology: Ultrasonic measuring technology
  • Document ID: TI00397F/00/EN/19.21
  • Document Date: 2021-05-31

Application

The Prosonic S FMU90 is designed for:

  • Level measurement and point level measurement of liquids or bulk solids.
  • Flow measurement in open channels or weirs.
  • Pump and rake control.
  • Advanced pump control functions (e.g., pump function test).
  • Calculation of average, difference, or total values.
  • Backwater or dirt detection.
  • Totalization of flow volume with up to 3 totalizers and 3 daily counters.
  • Counting and time pulses for controlling external units.

Operating Limits

  • Measuring Range: Up to 45 m (148 ft).

Input

Sensor Inputs

  • Number of Sensor Inputs: 1 or 2 (defined by order code 060).
  • Connectable Sensors: FDU90, FDU91, FDU91F, FDU92, FDU93, FDU95.
  • Old Connectable Sensors: FDU80, FDU80F, FDU81, FDU81F, FDU82, FDU83, FDU84, FDU85, FDU86, FDU96 (support for existing installations; manual type specification required for FDU8x; certain FDU8x sensors with Ex approval are not certified for Prosonic S).

External Point Level Switch Inputs

  • Number of Inputs: 4 (order code 090).
  • Switching Possibilities: External passive point level switch (NC or NO contact).
  • Voltage Levels: 0: < 8 V, 1: > 16 V.
  • Possible Applications: Pump feedback, pump tariff control, start/stop/reset daily counters for flow measurements, min/max level detection.

External Temperature Sensor Input

  • Number of Inputs: 1 (order code 090).
  • Use: Sound time-of-flight correction for FDU90 and FDU91 with sensor heating.
  • Connectable Sensors: Pt100 (3-wire or 4-wire connection). A 2-wire Pt100 is not recommended due to accuracy.

Output

Analog Outputs

  • Number of Outputs: 1 or 2 (order code 080).
  • Type: Active current output.
  • Output Damping: User-definable (0 to 1000 s).
  • Load: Max. 600 Ω.
  • Output Signal: Configurable as 4 to 20 mA with HART or 0 to 20 mA without HART. HART signal is on the first analog output only.
  • Response to Errors: Configurable (MIN, MAX, HOLD, User-specific value).

Relays

  • Number of Relays: 1, 3, or 6 (order code 070).
  • Type: Potential-free changeover contact (SPDT), can be inverted.
  • Switching Capacity (DC): 35 VDC, 100 W.
  • Switching Capacity (AC): 4 A, 250 V, 1000 VA (cosφ = 0.7).
  • Assignable Functions: Limit value, inband, out of band, counting pulse (max. 2 Hz), time pulse (max. 2 Hz), alarm/diagnostics (backwater, dirt, echo loss), pump control (individual, alternating, fixed limit, pump rate), advanced pump control, rake control, fieldbus relay.
  • Response to Errors: Configurable (HOLD, Energized, De-energized, Current value).
  • Switch-on Delay: Configurable after power failure.

PROFIBUS DP Interface

  • Device Version: Order code 080, option 3.
  • Profile: 3.0.
  • ID Number: 1540 (hex) / 5440 (dec).
  • GSD File: EH3x1540.gsd.
  • Addressing: DIP switches or software (default address: 126).
  • Bus Termination: Activatable/deactivatable switch.
  • Locking: Hardware or software lockable.
  • Transmittable Values: Primary values (level/flow), distances, counters, temperatures, averages/differences/totals, relay status, rake control, pump control.
  • Function Blocks: 10 AI, 10 DI, 10 DO.
  • Supported Baud Rates: 9.6 kbaud to 12 Mbaud.

Power Supply

Alternating Voltage (AC)

  • Device Version: Order code 050, option A.
  • Supply Voltage: 90 to 253 VAC (50/60 Hz).
  • Power Consumption: ≤ 23 VA.
  • Current Consumption: ≤ 100 mA at 230 VAC.

Direct Voltage (DC)

  • Device Version: Order code 050, option B.
  • Supply Voltage: 10.5 to 32 VDC.
  • Power Consumption: ≤ 14 W (typically 8 W).
  • Current Consumption: ≤ 580 mA at 24 VDC.

Galvanic Isolation

  • Isolated between: Power supply, sensor inputs, analog outputs (1 & 2), relay outputs, bus connection (PROFIBUS-DP).

Fuse

  • AC: 400 mA T /AC.
  • DC: 2 A T /DC.

Mechanical Construction

Dimensions

  • Polycarbonate Field Housing: See diagram (overall height approx. 216 mm).
  • Aluminum Field Housing: See diagram (overall height approx. 232 mm).
  • DIN Rail Housing: Dimensions depend on the number of additional terminal areas (max. width approx. 208 mm for 4 areas).
  • Remote Display and Operating Module: See diagram (height 96 mm, width 92 mm).

Weight

  • Polycarbonate Field Housing: Approx. 1.6 to 1.8 kg.
  • Aluminum Field Housing: Approx. 6 kg.
  • DIN Rail Housing: Approx. 0.7 kg.
  • Remote Display and Operating Module: Approx. 0.5 kg.

Materials

  • Polycarbonate Field Housing: Housing bracket: PC-FR; Field housing: PC-FR; DIN rail housing: PBT-GF; Display/operating module: PC; Seal: PUR soft foam; Nameplate: polyester; Screws: A4.
  • Aluminum Field Housing: Seal: silicone; Aluminum field housing: EN AC-AlSi12 (Fe); DIN rail housing: PBT-GF; Nameplate: polyester; Ground connection: A2; Display/operating module: PC; Dummy plug: nickel-plated brass; O-ring: EPDM 70 + PTFE; Screws: A2.

Performance Characteristics

  • Reference Operating Conditions: Temperature (+24 °C ±5 °C), Pressure (960 mbar ±100 mbar), Humidity (60 % r.F. ±15 % r.F.), surface conditions.
  • Maximum Measured Error: ±0.2 % of maximum sensor span.
  • Measured Error: ±2 mm + 0.17 % of measured distance.
  • Measured Value Resolution: 1 mm (for FDU90/FDU91).
  • Measuring Frequency: Max. 3 Hz.
  • Influence of Vapor Pressure: Negligible if pv ≤ 50 mbar at 20 °C for media like water, aqueous solutions, oils, etc. Accuracy may be compromised for media like ethanol, acetone, ammonia.

Environment

  • Ambient Temperature: –40 to 60 °C (LCD limited below –20 °C).
  • Storage Temperature: –40 to 60 °C.
  • Climate Class: Varies by housing type (Polycarbonate/Aluminum: 4K2/4K5/4K6/4Z2/4Z5/4C3/4S4/4M2; DIN rail: 3K3/3Z2/3Z5/3B1/3C2/3S3/3M1).
  • Vibration Resistance: Varies by housing type (Polycarbonate/Aluminum: 1.0 (m/s²)²/Hz; DIN rail: 0.5 (m/s²)²/Hz, 20 to 2000 Hz).
  • Degree of Protection:
    • Polycarbonate/Aluminum Field Housing: IP66 / NEMA 4x.
    • DIN Rail Housing: IP20.
    • Remote Display: IP65 / NEMA 4 (front), IP20 (rear).
  • Electromagnetic Compatibility (EMC): Meets EN 61326 series and NAMUR NE 21. Designed for industrial environments (Class A emission).

Certificates and Approvals

  • CE Mark: Confirms compliance with EU Directives.
  • RoHS: Not compliant with RoHS 2 substance restrictions.
  • RCM-Tick Marking: Meets ACMA requirements.
  • EAC Conformity: Meets EAC guidelines.
  • Ex Approval: Available; refer to Product Configurator. FDU9x sensors with Ex approval can connect to FMU90 without Ex approval.

Accessories

  • Communication: Commubox FXA195, Commubox FXA291.
  • Device Specific: Weather protection cover, mounting plate, frames (700 mm, 1400 mm), adapter plate for remote display.
  • Cables: Extension cables for sensors (various types and temperature ratings).
  • Temperature Sensor: Omnigrad S TR61.

Supplementary Documentation

  • Technical Information for specific sensors (FDU90, FDU91, etc.).
  • Operating Instructions (BA00288F, BA00289F, BA00292F, BA00293F).
  • Description of Device Parameters (GP01151F).
  • Slot/Index lists (PROFIBUS DP) (BA00333F).
  • Safety Instructions (XA00326F).

Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.

Official datasheet (PDF)

Lenntech datasheet mirror

Curated from selected public technical reference material for discovery and preliminary comparison. This summary is not a substitute for a current certified manufacturer datasheet. Verify revisions and design limits before use.