Datasheet summary
FlowFit CYA21
Engineering summary from PDF text extraction for FlowFit CYA21. Verify every value with the OEM datasheet.
Summary
Product identification
Flowfit CYA21 Universal assembly for analysis systems in industrial utilities.
Application
The Flowfit CYA21 is designed for integration on analytical panels and analysis systems, or to implement bypasses in industries including:
- Power stations
- Utilities in the (petro-)chemical and pharmaceutical industry
- Water treatment
It allows for the implementation of analytical measuring points for quality monitoring and control of process media such as boiler feedwater or condensate.
Operating limits
- Process temperature: -15 to 100 °C (5 to 212 °F), non-freezing
- Maximum process pressure: PN 16 (232 psi)
- Ambient temperature: –15 to 70 °C (5 to 158 °F)
Mechanical / hydraulic
- Materials: Stainless steel 1.4404 (AISI 316 L)
- Sensor connection: NPT 1/2" or Pg 13.5
- Pipe connection: 6 x 1 mm (open pipe outlet)
- Weight: 255 g (8.99 oz)
- Dimensions: See the official PDF for exact dimensions.
The inlet and outlet connection of the flow assembly are identical (Ø 6 x 1 mm). The assembly is designed for gaugeable tube fittings systems.
To achieve flow through the assembly with a bypass, pressure p1 must be higher than pressure p2. This can be achieved by installing an orifice plate in the main pipe.
Required at point of installation:
- 2 shut-off valves (for branch pipes)
- 1 shut-off valve (for bypass solution)
- Dirt filter (500 μm or finer) if the medium contains coarse particles.
- Pressure-reducing valve if the medium pressure exceeds the permitted value.
- Wall holder unit to secure the assembly.
Measuring system
A complete measuring system comprises:
- Flowfit CYA21 assembly
- Electrode (e.g., Orbisint CPS11D, length 120 mm / 4.72")
- Transmitter (e.g., Liquiline CM44x or Liquiline CM42)
- Measuring cable (e.g., CYK10)
Optional components include junction boxes and extension cables.
Scope of delivery
- Assembly in the version ordered
- Mounting kit
- Operating Instructions