Back to Endress + Hauser Pressure measurement
Endress+Hauser logo

Datasheet summary

Cerabar M PMP51

Engineering summary from PDF text extraction for Cerabar M PMP51. Verify every value with the OEM datasheet.

Summary

Product Identification

  • Product Line: Endress + Hauser Pressure measurement
  • Product Name: Cerabar M
  • Models: PMC51, PMP51, PMP55
  • Communication Protocols: 4 to 20 mA, HART, IO-Link, PROFIBUS PA, FOUNDATION Fieldbus

Application

The Cerabar M is used for:

  • Absolute and gauge pressure measurement in gases, steams, and liquids across various process engineering applications.
  • Level, volume, or mass measurement in liquids.
  • High process temperature applications.

Process Temperature Limits

  • Without diaphragm seals: up to 130 °C (266 °F) for a maximum of 60 minutes; also listed as 150 °C (302 °F).
  • With diaphragm seals: up to 400 °C (752 °F).

Pressure Limits

  • High pressure applications up to 400 bar (6,000 psi).

Features and Benefits

  • Excellent reproducibility and long-term stability.
  • High reference accuracy up to ±0.10%.
  • PLATINUM version: ±0.075% accuracy.
  • Turn down ratio up to 100:1.
  • Integrated platform for differential pressure, hydrostatics, and pressure (Deltabar M, Deltapilot M, Cerabar M).
  • User-friendly navigation for easy commissioning.
  • Suitable for process pressure monitoring up to SIL 2, certified to IEC 61508 Edition 2.0 and IEC 61511 by TÜV NORD.
  • Patented TempC process membrane for diaphragm seals minimizes temperature-induced measurement errors.
  • Available in ASME BPE-compliant versions.

Measuring Principles

  • Ceramic Process Membrane (PMC51 - Ceraphire®): Oil-free, direct pressure application to the membrane. Pressure changes capacitance between the ceramic substrate and the membrane. Guaranteed overload resistance up to 40 times nominal pressure. High chemical and mechanical stability.
  • Metallic Process Membrane (PMP51, PMP55): Pressure deflects the membrane, and a fill fluid transfers pressure to a resistance bridge (semiconductor technology).
    • PMP51: Suitable for process pressures up to 400 bar (6,000 psi). High long-term stability. Guaranteed overload resistance up to 4 times nominal pressure. Reduced thermal effect compared to diaphragm seal systems.
    • PMP55: Utilizes a diaphragm seal to transfer pressure to the measuring cell membrane. Suitable for pressures up to 400 bar (6,000 psi) and extreme process temperatures, depending on the version. High long-term stability. Guaranteed overload resistance up to 4 times nominal pressure.

Measuring Range

See the official PDF for exact tabulated values for PMC51 (gauge and absolute pressure) and PMP51/PMP55 (gauge and absolute pressure) regarding measuring cell types, maximum measuring ranges, lowest calibratable spans, MWP, OPL, and vacuum resistance.

  • Note: Highest factory-configurable turn down is 20:1; higher ratios are available on request or can be set in the device.

Output Signal

  • 4 to 20 mA analog (2-wire)
  • 4 to 20 mA with HART communication protocol (6.0) (2-wire)
  • IO-Link communication (3-wire)
  • PROFIBUS PA (Profile 3.02)
  • FOUNDATION Fieldbus

Signal Range (4 to 20 mA)

  • Analog, HART, and IO-Link: 3.8 to 20.5 mA.

Signal on Alarm

  • As per NAMUR NE 43.
  • Analog: Signal over-range (> 20.5 mA), Signal under-range (< 3.8 mA), Min. alarm (3.6 mA).
  • HART: Options include Max. alarm (21-23 mA), Hold measured value, Min. alarm (3.6 mA).
  • IO-Link: Max. alarm (22 mA), Min. alarm (3.6 mA), Hold measured value.
  • PROFIBUS PA: Configurable in Analog Input block (Last Valid Out Value, Fail-safe Value, Status Bad).
  • FOUNDATION Fieldbus: Configurable in Analog Input block (Last Good Value, Fail-safe Value, Wrong Value).

Power Supply

  • 4 to 20 mA Analog: 11.5 to 45 V DC (versions with 35 V DC plug-in connection).
  • 4 to 20 mA HART:
    • Intrinsically safe: 11.5 to 30 V DC.
    • Other types of protection/uncertified: 11.5 to 45 V DC (versions with 35 V DC plug-in connection).
  • IO-Link: 11.5 to 30 V DC (analog output only); 18 to 30 V DC (with IO-Link).
  • PROFIBUS PA: 9 to 32 V DC (non-hazardous areas).
  • FOUNDATION Fieldbus: 9 to 32 V DC (non-hazardous areas).

Current Consumption

  • IO-Link: < 60 mA.
  • PROFIBUS PA: 11 mA ±1 mA.
  • FOUNDATION Fieldbus: 16 mA ±1 mA.

Electrical Connection

Cable Entry Options

See the official PDF for a table detailing connection options (M20 gland, G ½" thread, NPT ½" thread, M12 plug, 7/8" plug, HAN7D plug, PE cable, M16 valve connector) and their corresponding degree of protection (IP ratings).

Terminals

  • Supply voltage and internal ground: 0.5 to 2.5 mm² (20 to 14 AWG).
  • External ground terminal: 0.5 to 4 mm² (20 to 12 AWG).

Performance Characteristics

Ceramic Process Membrane (PMC51)

  • Response Time: See the official PDF for detailed specifications (T63 and T90).
  • Total Performance: See the official PDF for tabulated values.
  • Resolution: See the official PDF for tabulated values.
  • Total Error: See the official PDF for tabulated values.
  • Long-term Stability: See the official PDF for tabulated values.

Metallic Process Membrane (PMP51, PMP55)

  • Response Time: See the official PDF for detailed specifications (T63 and T90).
  • Total Performance: See the official PDF for tabulated values.
  • Resolution: See the official PDF for tabulated values.
  • Total Error: See the official PDF for tabulated values.
  • Long-term Stability: See the official PDF for tabulated values.

Environment

  • Ambient Temperature Range: See the official PDF for details.
  • Storage Temperature Range: See the official PDF for details.
  • Climate Class: See the official PDF for details.
  • Degree of Protection: See the official PDF for details (e.g., IP66/68, NEMA 4X/6P).
  • Vibration Resistance: See the official PDF for details.
  • Electromagnetic Compatibility: See the official PDF for details.

Mechanical Construction

  • Various housing options are available, including F31 (aluminum) and F15 (stainless steel, hygienic).
  • Process Connections: Numerous options exist for PMC51, PMP51, and PMP55, including internal and flush process membranes, hygienic connections, and ANSI threads. See the official PDF for detailed diagrams and specifications.

Materials

  • Materials in contact with the process and materials not in contact with the process are detailed in the official PDF.
  • Seal materials and fill fluids are also specified.

Operability

  • Operating Concept: Local and remote operation supported.
  • Local Operation: Via local display, handheld terminal, or PC with operating program.
  • Operating Languages: See the official PDF for a list.

Certificates and Approvals

  • CE mark
  • RoHS
  • RCM marking
  • Various Ex approvals (ATEX, IEC Ex, FM, CSA)
  • Corrosion test reports
  • EAC conformity
  • Suitable for hygiene applications
  • cGMP certification
  • ASME BPE 2012 certification
  • Functional safety SIL
  • CRN approval
  • AD2000
  • Pressure Equipment Directive 2014/68/EU (PED)
  • ANSI/ISA 12.27.01 compliance
  • Inspection certificates available.

Disclaimer: This extraction may have missed figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.

Official datasheet (PDF)