Cerabar PMP50
Engineering summary from PDF text extraction for Cerabar PMP50. Verify every value with the OEM datasheet.
Summary
Product identification
- Product Name: Cerabar PMP50 HART
- Manufacturer: Endress+Hauser
- Type: Pressure transmitter with metal process membrane
- Communication Protocol: HART
Applications
- Pressure measuring ranges: up to 400 bar (6,000 psi)
- Process temperatures: up to 400 °C (752 °F) with diaphragm seal
- Accuracy: up to ±0.055%
Key Features & Advantages
- Easy guided commissioning with intuitive user interface
- Use of proven software and measuring cell components
- Flexible write protection via hardware and/or software
- Pre-assembled values (pressure and leakage-tested) for faster installation
Technical Specifications
Input
- Measured Variable: Absolute pressure, Gauge pressure
- Measuring Ranges (Absolute Pressure):
- Measuring cell: 1 bar (15 psi) to 400 bar (6,000 psi)
- Maximum measuring range (URL): +1 barabs to +400 barabs
- Smallest calibratable span: 0.05 bar to 20 bar
- Measuring Ranges (Gauge Pressure):
- Measuring cell: 1 bar (15 psi) to 400 bar (6,000 psi)
- Maximum measuring range (URL): +1 bar to +400 bar
- Smallest calibratable span: 0.05 bar to 20 bar
- Maximum Working Pressure (MWP): Varies by measuring cell, up to 400 bar (6,000 psi) at +20 °C (+68 °F).
- Overpressure Limit (OPL): Varies by measuring cell and process connection, up to 2000 bar (29000 psi) for 400 bar measuring cell.
Output
- Output Signal: 4 to 20 mA with HART communication protocol, 2-wire
- Operating Modes:
- 4.0 to 20.5 mA
- NAMUR NE 43: 3.8 to 20.5 mA (factory setting)
- US mode: 3.9 to 20.8 mA
- Signal on Alarm: In accordance with NAMUR recommendation NE 43 (Max alarm: 21.5 to 23 mA, Min. alarm: < 3.6 mA).
- Load: Up to 1065 Ω (VDC) or 848 Ω (VAC) depending on supply voltage.
- Damping: Continuously adjustable from 0 to 999 s (factory setting: 1 s).
- Linearization: User-defined tables of up to 32 value pairs can be entered.
Energy Supply
- Supply Voltage:
- Ex d, Ex e, non Ex: 10.5 to 35 VDC
- Ex i: 10.5 to 30 VDC
- Power Consumption: Maximum supply current limited to 500 mA.
Performance Characteristics
- Response Time (HART):
- Acyclic: min. 330 ms, typically 590 ms
- Cyclic (burst): min. 160 ms, typically 350 ms
- Reference Operating Conditions: As per IEC 62828-2 (Ambient temperature TA = +22 to +28 °C, Humidity = 5 to 80% RH, Ambient pressure = 860 to 1,060 mbar).
- Total Performance: Comprises reference accuracy and ambient temperature effect.
- Reference Accuracy [E1]:
- Standard device: Up to ±0.055% (Platinum) or ±0.065% (Standard) depending on measuring cell and TD.
- Devices with diaphragm seal: Up to ±0.15% for TD 1:1 to 5:1.
- Temperature Effect [E2]: Varies by measuring cell size and TD.
- Resolution (Current output): < 1 μA.
- Long-term Stability:
- 1 year: ± 0.1 %
- 5 years: ± 0.2 %
- 10 years: ± 0.25 %
Environment
- Ambient Temperature Range: –40 to +85 °C (–40 to +185 °F). With color display, limitations apply above +60 °C (+140 °F).
- Storage Temperature: –40 to +85 °C (–40 to +185 °F).
- Operating Altitude: Up to 5,000 m (16,404 ft) above sea level.
- Climate Class: Class 4K4H (–20 to +55 °C, 4 to 100% RH).
- Degree of Protection: IP66/68, TYPE 4X/6P for housing and process connection.
Mechanical Construction
- Materials in Contact with Process: Refer to specific product configuration.
- Weight: Refer to specific product configuration.
Certifications and Approvals
- CE mark
- RCM-Tick marking
- Hazardous area approvals (details in Safety Instructions)
- EAC conformity
- Pressure Equipment Directive 2014/68/EU (PED)
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.