Datasheet summary
Deltabar M PMD75B
Engineering summary from PDF text extraction for Deltabar M PMD75B. Verify every value with the OEM datasheet.
Summary
Product identification
- Product Name: Deltabar PMD75B
- Product Type: Digital differential pressure transmitter with metal process membrane
Applications
- Pressure measuring ranges: up to 250 bar (gauge and absolute), and 40 bar (differential pressure)
- Static pressure: up to 420 bar
- Accuracy: up to ±0.035%
Input
Measured variable
- Differential pressure
- Absolute pressure
- Gauge pressure
Measuring range
The following tables detail measuring ranges for different measuring cells and pressure ratings (PN).
Standard PN 160 / 16 MPa / 2400 psi:
- Measuring cells: 10 mbar (0.15 psi) to 40000 mbar (600 psi)
- Maximum Working Pressure (MWP): Ranges from 100 bar (1500 psi) to 160 bar (2400 psi) depending on the cell.
- Overpressure Limit (OPL): Ranges from 150 bar (2250 psi) to 160 bar (2400 psi).
- Burst Pressure: Ranges from 690 bar (10005 psi) to 1320 bar (19140 psi).
Standard PN 250 / 25 MPa / 3626 psi:
- Measuring cells: 100 mbar (1.5 psi) to 40000 mbar (600 psi)
- Maximum Working Pressure (MWP): Typically 250 bar (3626 psi).
- Overpressure Limit (OPL): Typically 250 bar (3626 psi).
- Burst Pressure: Ranges from 1320 bar (19140 psi).
Option PN 320 / 32 MPa / 4641 psi:
- Measuring cells: 100 mbar (1.5 psi) to 40000 mbar (600 psi)
- Maximum Working Pressure (MWP): Typically 320 bar (4641 psi).
- Overpressure Limit (OPL): Typically 320 bar (4641 psi).
- Burst Pressure: Ranges from 1320 bar (19140 psi).
Option PN 420 / 42 MPa / 6092 psi:
- Measuring cells: 100 mbar (1.5 psi) to 40000 mbar (600 psi)
- Maximum Working Pressure (MWP): Typically 420 bar (6092 psi).
- Overpressure Limit (OPL): Typically 420 bar (6092 psi).
- Burst Pressure: Ranges from 1320 bar (19140 psi).
Gauge or Absolute Pressure Measuring Cells:
- Measuring Cells: 160 bar (2400 psi) and 250 bar (3750 psi).
- Maximum measuring range: Up to 160 bar (2400 psi) or 250 bar (3750 psi).
- Smallest calibratable span: 40 bar (600 psi) for 160 bar cell, 40 bar (600 psi) for 250 bar cell.
- Maximum Working Pressure (MWP): 160 bar (2400 psi) or 250 bar (3750 psi).
- Overpressure Limit (OPL): 240 bar (3600 psi) or 375 bar (5625 psi).
- Burst Pressure: 1320 bar (19140 psi).
Minimum static pressure
- For silicone oil at reference operating conditions: 25 mbar (0.0375 psi) abs.
- For silicone oil at 85 °C (185 °F): up to 250 mbar (4 psi) abs.
- For gauge or absolute sensors with silicone oil at reference conditions: 10 mbar (0.15 psi) abs.
- For gauge or absolute sensors with silicone oil at 85 °C (185 °F): up to 10 mbar (0.15 psi) abs.
Output
Output signal
- Current Output: 4 to 20 mA with HART communication protocol (2-wire).
- Operating modes: 4.0 to 20.5 mA, NAMUR NE 43 (3.8 to 20.5 mA - factory setting), US mode (3.9 to 20.8 mA).
- PROFINET with Ethernet-APL: 10BASE-T1L, 2-wire, 10 Mbit.
Signal on alarm
- 4 to 20 mA HART: Configurable max alarm (21.5 to 23 mA) or min alarm (< 3.6 mA - factory setting).
- PROFINET with Ethernet-APL: According to "Application layer protocol for decentralized periphery", Version 2.4, and diagnostics according to PROFINET PA Profile 4.02.
Load
- 4 to 20 mA HART: Maximum load resistance calculated as (Supply voltage - 1.5 V) / 0.023 A.
Damping
- Adjustable from 0 to 999 seconds.
- Factory setting: 1 s.
Linearization
- User-defined linearization tables of up to 32 value pairs can be entered.
Protocol-specific data
- HART:
- Manufacturer ID: 17 (0x11 hex)
- Device type ID: 0x1131
- Device revision: 1
- HART specification: 7
- DD revision: 1
- Minimum load: 250 Ohm
- PROFINET with Ethernet-APL:
- Protocol: Application layer protocol for decentral device periphery and distributed automation, Version 2.4
- Communication type: Ethernet Advanced Physical Layer 10BASE-T1L
- Conformance Class: Conformance Class B
- Netload Class: Netload Class II
- Baud rates: Automatic 10 Mbit/s
- Cycle times: From 32 ms
- Media Redundancy Protocol (MRP): Yes
- System redundancy support: System redundancy S2 (2 AR with 1 NAP)
- Device profile: Application interface identifier 0xB310
- Generic device: Manufacturer ID 0x11, Device type ID A231
Power supply
- Analog/HART:
- Ex d, Ex e, non-Ex: 10.5 to 35 VDC
- Ex i: 10.5 to 30 VDC
- PROFINET over Ethernet-APL: 9.6 to 15 VDC, 540 mW.
Electrical connection
Terminals
- Supply voltage and internal ground terminal: 0.5 to 2.5 mm² (20 to 14 AWG)
- External ground terminal: 0.5 to 4 mm² (20 to 12 AWG)
Cable specification
- Plastic cable entry: Ø5 to 10 mm (0.2 to 0.38 in)
- Nickel-plated brass cable entry: Ø7 to 10.5 mm (0.28 to 0.41 in)
- Stainless steel cable entry: Ø7 to 12 mm (0.28 to 0.47 in)
- PROFINET with Ethernet-APL:
- Cable type A
- Cable capacitance: 45 to 200 nF/km
- Loop resistance: 15 to 150 Ω/km
- Cable inductance: 0.4 to 1 mH/km
Performance characteristics
Response time
- HART: Acyclic: min. 330 ms, typically 590 ms. Cyclic (burst): min. 160 ms, typically 350 ms.
- PROFINET with Ethernet-APL: Cyclic: min. 32 ms.
Reference operating conditions
- As per IEC 62828-2.
- Ambient temperature: +22 to +28 °C (+72 to +82 °F).
- Humidity: 5 to 80 % rF ± 5 %.
- Ambient pressure: 860 to 1060 mbar (12.47 to 15.37 psi).
Total performance
Calculated as ± √ ((E1)² + (E2)² + (E3)²), where E1 is reference accuracy, E2 is ambient temperature effect, and E3 is static pressure effect.
Resolution
- Current output: <1 μA
Long-term stability
- 10 mbar (0.15 psi) and 30 mbar (0.45 psi) measuring cell:
- 1 year: ±0.20 %
- 5 years: ±0.28 %
- 10 years: ±0.31 %
- 15 years: ±0.34 %
- 100 mbar (1.5 psi) measuring cell:
- 1 year: ±0.08 %
- 5 years: ±0.12 %
- 10 years: ±0.20 %
- 15 years: ±0.28 %
- 500 mbar (7.5 psi) to 40 bar (600 psi) measuring cells:
- 1 year: ±0.025 %
- 5 years: ±0.05 %
- 10 years: ±0.10 %
- 15 years: ±0.15 %
- 160 bar (2 400 psi) and 250 bar (3 750 psi) gauge/absolute measuring cells:
- 1 year: ±0.05 %
- 5 years: ±0.07 %
- 10 years: ±0.10 %
- 15 years: ±0.15 %
Response time T63 and T90
- 10 mbar (0.15 psi) and 30 mbar (0.45 psi) sensor:
- Dead time (t1): maximum 50 ms
- Time constant T63 (t2): maximum 450 ms
- Time constant T90 (t3): maximum 1100 ms
- 100 mbar (1.5 psi) sensor:
- Dead time (t1): maximum 50 ms
- Time constant T63 (t2): maximum 120 ms
- Time constant T90 (t3): maximum 200 ms
- All other sensors:
- Dead time (t1): maximum 50 ms
- Time constant T63 (t2): maximum 85 ms
- Time constant T90 (t3): maximum 200 ms
Warm-up time (according to IEC62828-4)
- ≤ 5 s
Mounting
Orientation
The installation orientation depends on the piping connection options. See the document for detailed diagrams.
Environment
Ambient temperature range
- See the official PDF for exact tabulated values.
Storage temperature
- See the official PDF for exact tabulated values.
Operating altitude
- See the official PDF for exact tabulated values.
Climate class
- See the official PDF for exact tabulated values.
Atmosphere
- See the official PDF for exact tabulated values.
Degree of protection
- See the official PDF for exact tabulated values.
Vibration resistance
- See the official PDF for exact tabulated values.
Electromagnetic compatibility (EMC)
- Devices fulfill the requirements of IEC / DIN EN 61326-1 (Table 2 Industrial Environment).
- Test levels for transient overvoltages (Surge) are 1000 V line to earth on DC power and input/output ports.
- Optional overvoltage protection: Spark-over voltage min. 400 V DC, nominal discharge current 10 kA.
- Overvoltage category II.
Process
Process temperature range
- See the official PDF for exact tabulated values.
Process temperature range (temperature at transmitter)
- See the official PDF for exact tabulated values.
Process pressure range
- See the official PDF for exact tabulated values.
Mechanical construction
Materials in contact with process
- See the official PDF for exact tabulated values.
Materials not in contact with process
- See the official PDF for exact tabulated values.
Display and user interface
- Features a large display with backlight for readability.
- Intuitive wizard navigation for commissioning and verification.
- Bluetooth connectivity for remote operation.
Certificates and approvals
- CE mark
- RCM-Tick marking
- Ex approvals (see separate Safety Instructions)
- Corrosion test
- EAC conformity
- Drinking water approval
- Functional safety SIL/ IEC 61508 Declaration of Conformity (optional)
- Marine approval
- Radio approval
- CRN approval
- Pressure Equipment Directive 2014/68/EU (PED)
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.