Engineering summary from PDF text extraction for iTemp TMT142B. Verify every value with the OEM datasheet.
Summary
Product identification
The Endress+Hauser iTEMP TMT142B is a temperature field transmitter with HART® protocol and Bluetooth® capabilities.
Application
- Converts various input signals (RTD, TC, resistance, voltage) into a scalable, analog 4 to 20 mA output signal.
- Features reliability, long-term stability, high precision, and advanced diagnostic functions.
- Suitable for demanding environmental conditions with an optional stainless steel housing.
- Can be installed as an intrinsically safe apparatus in hazardous areas.
Input
Measured variable
- Temperature (temperature-linear transmission behavior)
- Resistance
- Voltage
Measuring range
The device supports a variety of resistance thermometers (RTD), thermocouples (TC), resistance transmitters (Ω), and voltage transmitters (mV) with specified measuring range limits and minimum spans. See the official PDF for exact tabulated values.
- Resistance thermometer (RTD): Supports various standards including IEC 60751, JIS C1604, DIN 43760, GOST 6651, and OIML R84. Ranges vary by type (e.g., Pt100, Pt1000, Ni100, Cu50) from –200 °C to +1100 °C (–328 to +2012 °F).
- Connection types: 2-wire, 3-wire, or 4-wire.
- Sensor current: ≤ 0.3 mA.
- Wire resistance compensation: possible for 2-wire (0 to 30 Ω), up to max. 50 Ω per wire for 3-wire and 4-wire.
- Resistance transmitter:
- 10 to 400 Ω (min. span 10 Ω)
- 10 to 2000 Ω (min. span 10 Ω)
- Thermocouples (TC): Supports types A, B, C, D, E, J, K, L, N, R, S, T, U as per various standards (IEC 60584, ASTM E230, DIN 43710, GOST R8.585). Ranges vary from –270 °C to +2500 °C (–454 to +4532 °F). Minimum span typically 50 K (90 °F).
- Voltage transmitter (mV): –20 to 100 mV (min. span 5 mV).
Output
Output signal
- Analog output: 4 to 20 mA, 20 to 4 mA (invertible).
- Signal encoding: FSK ±0.5 mA via current signal.
- Data transmission rate: 1200 baud.
- Galvanic isolation: U = 2 kV AC for 1 minute (input/output).
Failure information
Failure information as per NAMUR NE43:
- Underranging: Linear decrease from 4.0 to 3.8 mA.
- Overranging: Linear increase from 20.0 to 20.5 mA.
- Failure (e.g., sensor failure, short-circuit): ≤ 3.6 mA ("low") or ≥ 21 mA ("high"), selectable. "High" alarm can be set between 21.5 mA and 23 mA.
Load
Maximum load Rb max. = (Ub max. - 11 V) / 0.023 A.
Linearization/transmission behavior
- Temperature-linear
- Resistance-linear
- Voltage-linear
Network frequency filter
- 50/60 Hz
Filter
- 1st order digital filter: 0 to 120 s.
Protocol-specific data
- HART® specification: 7
- Device address in multi-drop mode: 0 to 63.
- HART® load: min. 250 Ω.
Write protection for device parameters
- Hardware: via DIP switch.
- Software: user role-based concept with password assignment.
Switch-on delay
- ≤ 2 s until HART® communication starts.
- ≤ 7 s until the first valid measured value is present at the current output.
- During switch-on delay: Ia ≤ 3.8 mA.
Power supply
- Non-hazardous areas: 11 to 36 VDC (standard), protected against polarity reversal.
- Hazardous areas: See Ex documentation.
- The device must be powered by a unit operating with a limited energy circuit according to UL/EN/IEC 61010-1.
Current consumption
- 3.6 to 23 mA.
- Minimum current consumption: ≤ 3.5 mA.
- Multidrop mode: 4 mA.
- Current limit: ≤ 23 mA.
Terminals
- Max. wire cross-section: 2.5 mm² (12 AWG) plus ferrule.
Overvoltage protection
- Optional surge arrester available.
- Connection data: Maximum continuous voltage (rated voltage) UC = 36 VDC.
- Surge current resistance: Lightning surge current D1 (10/350 µs) Iimp = 1 kA (per wire); Nominal discharge current C1/C2 (8/20 µs) In = 5 kA (per wire) or 10 kA (total).
- Series resistance per wire: 1.8 Ω, tolerance ±5 %.
Performance characteristics
Response time
- RTD and resistance transmitter (Ω measurement): ≤ 1 s.
- Thermocouples (TC) and voltage transmitters (mV): ≤ 1 s.
- Reference temperature: ≤ 1 s.
Reference operating conditions
- Calibration temperature: +25 °C ±3 K (+77 °F ±5.4 °F).
- Supply voltage: 24 V DC.
- 4-wire circuit for resistance adjustment.
Maximum measured error
Errors are specified according to DIN EN 60770 under reference conditions and represent ±2 s (Gaussian distribution). See the official PDF for exact tabulated values for various sensor types and ranges.
- Resistance thermometers (RTD) and resistance transmitters: Errors are detailed for digital values (via HART®) and analog output (D/A conversion), including sensor-specific formulas.
- Thermocouples (TC) and voltage transmitters: Errors are detailed for digital values (via HART®) and analog output (D/A conversion), including sensor-specific formulas.
Sensor adjustment
Sensor-transmitter-matching
- Callendar-Van Dusen coefficients: For Pt100 resistance thermometers, using coefficients A, B, and C to match the sensor and transmitter for improved accuracy.
- Linearization for copper/nickel resistance thermometers: Using polynomial equations with coefficients A and B specific to the sensor's calibration data.
- 1-point adjustment: Shifts the sensor value (offset).
Current output adjustment
- Correction of the 4 and/or 20 mA current output value.
Operating influences
Influences of ambient temperature and supply voltage on measured error are detailed for both RTD/resistance transmitters and TC/voltage transmitters. See the official PDF for exact tabulated values.
Installation
Mounting location
- Directly to sensor or remote mounting using brackets.
- Display can be mounted in four positions.
Environment
Ambient temperature
- –40 to +85 °C (–40 to +185 °F) (for hazardous areas, see Ex documentation).
- Without display: –40 to +85 °C (–40 to +185 °F).
- With display: –40 to +80 °C (–40 to +176 °F).
- With overvoltage protection module: –40 to +85 °C (–40 to +185 °F).
- Display legibility may be affected at temperatures below –30 °C (–22 °F).
Storage temperature
- Without display: –50 to +100 °C (–58 to +212 °F).
- With display: –40 to +80 °C (–40 to +176 °F).
- With overvoltage protection module: –50 to +100 °C (–58 to +212 °F).
Humidity
- Permitted: 0 to 95 %.
Climate class
- As per IEC 60654-1, Class Dx.
Degree of protection
- Die-cast aluminum or stainless steel housing: IP66/67, Type 4X.
Shock and vibration resistance
- Caution: Vibrations must not exceed specifications. Resonance may occur with L-shaped mounting brackets.
Electromagnetic compatibility (EMC)
- CE compliance: Meets IEC/EN 61326 series and NAMUR Recommendation EMC (NE21).
- Maximum measured error: <1% of measuring range.
- Interference immunity: As per IEC/EN 61326 series, industrial requirements.
- Interference emission: As per IEC/EN 61326 series, Class B equipment.
- Shielded sensor cables are recommended for lengths ≥ 30 m (98.4 ft).
Overvoltage category
- II
Degree of contamination
- 2
Mechanical construction
Design, dimensions
- Die-cast aluminum or optional stainless steel (316L) housing.
- Electronics module and connection compartment.
- Display attachable in 90° stages.
Weight
- Aluminum housing (with display): approx. 1.4 kg (3 lb).
- Stainless steel housing (with display): approx. 4.2 kg (9.3 lb).
Materials
- Housing: Die-cast aluminum (AlSi10Mg/AlSi12 with powder coating) or 316L stainless steel (1.4404).
- Sensor terminals: Nickel-plated brass (gold flashed).
- Nameplate: Aluminum (anodized).
Cable entries
- Available in 3x thread ½" NPT, 3x thread M20, or 3x thread G½".
Operability
Operating concept
- Configuration programs via HART® protocol.
- Miniature switch (DIP switch) for hardware settings.
Local operation
- LC display (backlit, attachable in 90° stages).
- Displays measured value, units (°C, °F, K, %), status, and symbols.
- No operating elements directly on the display; located on the electronics module.
Remote operation
- Configuration via HART® communication using specialized software.
Bluetooth® wireless technology
- Optional interface for operation and configuration using the SmartBlue app.
- Range: 25 m (82 ft) (with display window), 10 m (33 ft) (without display window) under reference conditions.
- Communication is encrypted with password protection.
- Can be deactivated.
Certificates and approvals
- CE mark: Confirms compliance with EC directives.
- EAC mark: Confirms compliance with EEU guidelines.
- Ex approvals: Information available from sales center; separate Ex documentation required for explosion protection data.
- CSA C/US: Complies with relevant CSA standards.
- HART® certification: Registered by FieldComm Group, meets HART® Communication Protocol Specifications, Revision 7.
MTTF
- Without Bluetooth®: 152 years.
- With Bluetooth®: 114 years. (According to Siemens SN-29500 at 40 °C (104 °F)).
Ordering information
Detailed ordering information and product configuration available via the Endress+Hauser website and Product Configurator.
Accessories
Various device-specific and communication-specific accessories are available. These include dummy plugs, cable glands, pipe mounting brackets, overvoltage protection modules, Commuboxes, and the Field Xpert SMT70 tablet PC.
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.