Datasheet summary

iTemp TMT162

Engineering summary from PDF text extraction for iTemp TMT162. Verify every value with the OEM datasheet.

Summary

Product identification

iTEMP TMT162 Temperature field transmitter with two sensor inputs and illuminated display.

  • Protocol: FOUNDATION Fieldbus™ (ITK 6.1.2) or PROFIBUS® PA (Profile 3.02).
  • Inputs: Universal input for RTD, TC, resistance (Ω), or voltage (mV) transmitters.

Application

  • Universal input for resistance thermometer (RTD), thermocouple (TC), resistance transmitter (Ω), voltage transmitter (mV).
  • Output via FOUNDATION Fieldbus™ or PROFIBUS® PA.
  • Dual-compartment housing for harsh industrial environments.
  • Backlit display with measured value, bar graph, and status indication.
  • Two sensor inputs.
  • Diagnostics information according to NAMUR NE107.
  • Sensor monitoring capabilities: failure information, sensor backup, drift alarm, and corrosion detection.
  • International approvals including FM, CSA, and ATEX.
  • Galvanic isolation of 2 kV between sensor input and output.

Input

Resistance Thermometer (RTD)

  • Standards supported: IEC 60751, JIS C1604, SAMA, DIN 43760, GOST 6651, OIML R84.
  • Types: Pt, Ni, Cu.
  • Connection: 2-wire, 3-wire, or 4-wire.
  • Sensor current: ≤ 0.3 mA.
  • Wire resistance compensation: Possible for 2-wire (0 to 30 Ω).
  • Maximum sensor wire resistance: 50 Ω per wire (3-wire and 4-wire).
  • Measuring ranges (examples):
    • Pt100 (IEC 60751): –200 to +850 °C (–328 to +1 562 °F)
    • Ni100 (DIN 43760): –60 to +250 °C (–76 to +482 °F)
    • Cu50 (OIML R84): –50 to +200 °C (–58 to +392 °F)
  • Minimum span: 10 K (18 °F) for most RTD types.

Resistance Transmitter (Ω)

  • Measuring ranges:
    • 10 to 400 Ω
    • 10 to 2,000 Ω
  • Minimum span: 10 Ω.

Thermocouples (TC)

  • Standards supported: IEC 60584, ASTM E988, DIN 43710.
  • Types: A, B, C, D, E, J, K, L, N, R, S, T, U.
  • Measuring ranges (examples):
    • Type K: –270 to +1,372 °C (–454 to +2,501 °F)
    • Type S: –50 to +1,768 °C (–58 to +3,214 °F)
    • Type T: –270 to +400 °C (–454 to +752 °F)
  • Minimum span: 50 K (90 °F).
  • Internal cold junction compensation: Pt100.
  • External cold junction compensation: Configurable value –40 to +85 °C (–40 to +185 °F).
  • Maximum sensor wire resistance: 10 kΩ.

Voltage Transmitter (mV)

  • Measuring ranges:
    • –5 to 30 mV
    • –20 to 100 mV
  • Minimum span: 5 mV.

Input Configuration

  • Possible connection combinations for dual inputs:
    • RTD/resistance transmitter (2-wire) with RTD/resistance transmitter (2-wire or 3-wire) or Thermocouple/voltage transmitter.
    • RTD/resistance transmitter (3-wire) with RTD/resistance transmitter (2-wire or 3-wire) or Thermocouple/voltage transmitter.
    • Thermocouple/voltage transmitter with RTD/resistance transmitter (2-wire, 3-wire) or Thermocouple/voltage transmitter.

Output

  • FOUNDATION Fieldbus™: H1, IEC 61158-2, Manchester Bus Powered (MBP). Data transmission rate: 31.25 kBit/s.
  • PROFIBUS® PA: In accordance with EN 50170 Volume 2, IEC 61158-2, Manchester Bus Powered (MBP). Data transmission rate: 31.25 kBit/s.
  • Galvanic isolation: U = 2 kV AC (input/output).
  • Failure information: Status messages according to FOUNDATION Fieldbus™ or PROFIBUS® PA specifications.
  • Linearization/transmission behavior: Temperature-linear, resistance-linear, voltage-linear.
  • Filter: 1st order digital filter: 0 to 60 s.

System Integration

FOUNDATION Fieldbus™

  • Manufacturer ID: 452B48
  • Device type: 10CC (Hex)
  • ITK Version: 6.1.2
  • Link Master (LAS) capability: Yes
  • Supported functions: Quick Setup, User sensor trim, Factory trim settings, Callendar Van Dusen, Polynomial linearization, Sensor drift detection.

PROFIBUS® PA

  • Profile version: 3.02
  • Manufacturer-specific ID no.: 1549 (hex)
  • Write protection: Activated by hardware setting (DIP switch).
  • GSD files: Available via Endress+Hauser website.

Power Supply

  • Supply voltage: Ub = 9 to 32 V DC, polarity-independent.
  • Maximum voltage: Ub = 35 V DC.
  • FISCO/FNICO compliance: According to IEC 60079-27.

Electrical Characteristics

  • Current consumption (device basic current): ≤11 mA.
  • Switch-on current: ≤11 mA (FOUNDATION Fieldbus™ only).
  • Failure current FDE: 0 mA.

Performance Characteristics

  • Response time: Measured value update < 1 s per channel.
  • Maximum measured error (typical values):
    • RTD: 0.1 °C to 1 °C (0.18 °F to 1.8 °F) depending on type.
    • TC: Typ. 0.25 °C to 1.0 °C (0.45 °F to 1.8 °F) depending on type.
    • Resistance transmitter: ±0.04 Ω or ±0.08 Ω.
    • Voltage transmitter: ±10 µV.
  • Non-repeatability:
    • Resistance: 15 mΩ or 100 ppm of measured value.
    • Voltage: 4 µV or 3 µV.
  • Long-term drift: ≤ 0.1 °C/year (≤ 0.18 °F/year) or ≤ 0.05 %/year.
  • Influence of ambient temperature:
    • Resistance: 15 ppm of measured value, min. 1.5 mΩ or 15 mΩ.
    • Voltage: 30 ppm of measured value, min. 0.3 µV or 0.15 µV.
  • Resolution of A/D converter: 18 bit.

Mechanical / Hydraulic

  • Housing materials: Die-cast aluminum or stainless steel (316L), or T17 stainless steel for hygienic applications.
  • Weight:
    • Aluminum housing: approx. 1.4 kg (3 lb) with display.
    • Stainless steel housing: approx. 4.2 kg (9.3 lb) with display.
    • T17 housing: approx. 1.25 kg (2.76 lb) with display.
  • Cable entries: Available with ½" NPT, M20, or G½" threads.
  • Mounting: Direct sensor mounting or remote mounting using brackets.
  • Display mounting: Attachable in 90° stages.

Environment

  • Ambient temperature:
    • Without display: –40 to +85 °C (–40 to +185 °F).
    • With display: –40 to +80 °C (–40 to +176 °F).
  • Storage temperature:
    • Without display: –40 to +100 °C (–40 to +212 °F).
    • With display: –40 to +80 °C (–40 to +176 °F).
  • Humidity: 0 to 95 %.
  • Altitude: Up to 2,000 m (6,560 ft) above sea level.
  • Climate class: As per IEC 60654-1, Class C.
  • Degree of protection: IP66/67, Type 4X (aluminum/stainless steel housing); IP66 / IP68, NEMA 4X, NEMA 6P (T17 stainless steel housing).
  • Shock and vibration resistance: As per KTA 3505, IEC 60068-2-6 (vibration), DNV GL Guideline.
  • Electromagnetic compatibility (EMC): In accordance with IEC/EN 61326 series and NAMUR Recommendation EMC (NE21). Interference immunity: Industrial requirements. Interference emission: Class B equipment.
  • Overvoltage category: II.
  • Degree of contamination: 2.

Operability

  • Configuration: Via fieldbus interface using configuration programs or via DIP switches for hardware settings.
  • Display: LC display with bar graph, measured value, status, unit, caution symbol, and communication symbol.

Certificates and Approvals

  • CE mark: Complies with EC directives.
  • Ex approvals: Information available on request (ATEX, FM, CSA).
  • MTBF: 126 a (FOUNDATION Fieldbus™ and PROFIBUS® PA).
  • UL recognized component: E225237.
  • CSA: CAN/CSA-C22.2 No. 61010-1.
  • FOUNDATION Fieldbus™ certification: ITK revision 6.1.2.
  • PROFIBUS® PA certification: Profile 3.02.

Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.