Datasheet summary
iTemp TMT80
Engineering summary from PDF text extraction for iTemp TMT80. Verify every value with the OEM datasheet.
Summary
Product identification
iTEMP TMT80 Universal temperature head transmitter
Application
PC programmable (PCP) temperature head transmitter for converting input signals into a scalable 4 to 20 mA analog output. Suitable for resistance thermometers (RTD) and thermocouples (TC). Device configuration is done via PC with a configuration kit and PC software.
Operating limits
- Fault signal (sensor break/short circuit): Adjustable as per NAMUR NE43.
- EMC requirements: Meets NAMUR NE21.
- Galvanic isolation: 500 V (input/output).
Feed water (Input)
- Measured variable: Temperature (temperature-linear transmission behavior).
- Resistance thermometer (RTD) measuring ranges:
- Pt100 (IEC 60751, α = 0.00385): –200 to +850 °C (–328 to +1 562 °F), Min. span 10 K (18 °F).
- Pt1000 (IEC 60751, α = 0.00385): –200 to +250 °C (–328 to +482 °F), Min. span 10 K (18 °F).
- RTD connection type: 2-, 3-, or 4-wire connection.
- RTD wire resistance compensation: Possible for 2-wire circuit (0 to 20 Ω).
- RTD cable resistance: Up to max. 11 Ω per wire.
- RTD sensor current: ≤ 0.6 mA.
- Thermocouples (TC) measuring ranges:
- Type B (PtRh30-PtRh6): +40 to +1 820 °C (+104 to +3 308 °F), Min. span 500 K.
- Type K (NiCr-Ni): –200 to +1 372 °C (–328 to +2 501 °F), Min. span 50 K.
- Type N (NiCrSi-NiSi): –270 to +1 300 °C (–454 to +2 372 °F), Min. span 50 K.
- Type R (PtRh13-Pt): –50 to +1 768 °C (–58 to +3 214 °F), Min. span 500 K.
- Type S (PtRh10-Pt): –50 to +1 768 °C (–58 to +3 214 °F), Min. span 500 K.
- TC internal reference junction: Pt100.
- TC reference junction accuracy: ± 1 K.
Product water (Output)
- Output signal: Analog, 4 to 20 mA.
- Signal on alarm (underranging): Linear drop to 3.8 mA.
- Signal on alarm (overranging): Linear rise to 20.5 mA.
- Signal on alarm (sensor breakage/short-circuit): ≤ 3.6 mA or ≥ 21.0 mA (if setting ≥ 21.0 mA, an output current ≥ 21.5 mA is guaranteed). Note: Not for thermocouples.
- Load: Max. (Vpower supply - 8 V) / 0.025 A.
- Transmission behavior: Temperature linear.
- Galvanic isolation: U = 500 VAC (input/output).
- Input current required: ≤ 3.5 mA.
- Current limit: ≤ 25 mA.
- Switch-on delay: 4 s.
Electrical
- Supply voltage: Ub = 8 to 35 V, reverse polarity protection.
- Residual ripple: Permitted residual ripple Uss ≤ 3 V at Ub ≥ 15 V, f max. = 1 kHz.
Performance characteristics
- Response time: 1 s.
- Maximum measured error:
- RTD (Pt100, Pt1000): 0.5 K or 0.15%.
- TC (K, N): typ. 1.0 K or 0.15%.
- TC (S, B, R): typ. 2.0 K or 0.15%.
- Influence of the supply voltage: ≤ ±0.01%/V deviation from 24 V.
- Long-term drift: ≤ 0.1 K/Year or ≤ 0.05%/Year.
- Influence of ambient temperature:
- RTD: Td = ± [(15 ppm/K * (Upper range value - Lower range value)) + (50 ppm/K * Set measuring range)] * Δ T.
- TC: Td = ± [(50 ppm/K * (Upper range value - Lower range value)) + (50 ppm/K * Set measuring range)] * Δ T.
- Influence of load: ≤ ±0.02%/100 Ω.
- Comparison point: Pt100, as per DIN IEC 60751 Class B (internal cold junction for thermocouples TC).
Mechanical / hydraulic
- Mounting: Terminal head in accordance with DIN EN 43 729 flat face, separate in field housing, or with clip on DIN rail as per IEC 60715.
- Orientation: No restrictions.
- Ambient temperature range: –40 to +85 °C (–40 to +185 °F).
- Storage temperature: –40 to +100 °C (–40 to +212 °F).
- Humidity: Max. rel. humidity: 95% as per IEC 60068-2-30.
- Climate class: As per IEC 60 654-1, Class C.
- Degree of protection: IP 00 (depends on installed terminal head or field housing).
- Shock and vibration resistance: 4 g / 2 to 150 Hz as per IEC 60 068-2-6.
- Electromagnetic compatibility (EMC): CE compliance. Interference immunity as per IEC/EN 61326 series, industrial requirements. Interference emission as per IEC/EN 61326 series, Class B equipment.
- Dimensions: 22.8 mm (0.9 in) height, 33 mm (1.3 in) width, Ø44 mm (1.73 in) diameter.
- Weight: Approx. 40 g (1.41 oz).
- Materials: Housing: Polycarbonate (PC). Terminals: nickel-plated brass. Potting: WEVO PU 403 FP/FL.
- Terminals: Screw terminals, wires up to max. 1.75 mm² (15 AWG) or 1.5 mm² (16 AWG) with wire end ferrules.
Operability
- Remote operation: Configuration using PC operating program ReadWin 2000.
- Configurable parameters: Sensor type, connection type (2-, 3-, or 4-wire), measuring unit (°C, °F), measuring range limits, wire resistance compensation (0 to 20 Ω for RTD 2-wire), failsafe mode, zero point offset (–9.9 to +9.9 K).
Accessories
- Device-specific: Mounting kit (order code: 51001112), DIN rail adapter clip (order code: 71528231), Field housing TAF10 (order code: TAF10).
- Communication-specific: FXA291 Commubox (order code: 51516983), TXU10-AA (order code: TXU10-...). ReadWin 2000 software is available for free download.
- Service-specific: Applicator software (web or CD-ROM).
Disclaimer
This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.
Official datasheet (PDF)
Curated from selected public technical reference material for discovery and preliminary comparison. This summary is not a substitute for a current certified manufacturer datasheet. Verify revisions and design limits before use.