Datasheet summary
iTemp TMT84
Engineering summary from PDF text extraction for iTemp TMT84. Verify every value with the OEM datasheet.
Summary
Product Identification
- Product Name: iTEMP TMT84
- Type: Dual-input temperature transmitter with PROFIBUS® PA protocol
- Document: TI00138R/09/EN/07.21-00
Application
- Converts various input signals (resistance thermometers, thermocouples, resistance, voltage) into digital output signals via PROFIBUS® PA.
- Designed for reliability, long-term stability, and high precision with advanced diagnostic functions.
- Suitable for critical processes and hazardous areas, with FISCO/FNICO conformity (IEC 60079-27) for explosive atmospheres.
- Can be installed in terminal head form B (DIN EN 50446) or in a field housing for Ex d applications.
Input
Measured Variables
- Temperature (temperature-linear transmission)
- Resistance (Ω)
- Voltage (mV)
Input Types and Ranges
Resistance Thermometers (RTD) as per standard:
- IEC 60751:2008:
- Pt100: –200 to +850 °C
- Pt200: –200 to +850 °C
- Pt500: –200 to +250 °C
- Pt1000: –200 to +250 °C
- JIS C1604:1984:
- Pt100: –200 to +649 °C
- DIN 43760 IPTS-68:
- Ni100: –60 to +250 °C
- Ni1000: –60 to +150 °C
- Edison Copper Winding No. 15:
- Cu10: –100 to +260 °C
- GOST 6651-94:
- Pt50: –200 to +1 100 °C
- Pt100: –200 to +850 °C
- OIML R84:2003 / GOST 6651-2009:
- Cu50: –200 to +200 °C
- Cu100: –200 to +200 °C
Resistance Transmitter:
- 10 to 400 Ω
- 10 to 2 000 Ω
Thermocouples (TC) as per standard:
- IEC 60584, Part 1:
- Type A (W5Re-W20Re): 0 to +2 500 °C
- Type B (PtRh30-PtRh6): +40 to +1 820 °C
- Type E (NiCr-CuNi): –270 to +1 000 °C
- Type J (Fe-CuNi): –210 to +1 200 °C
- Type K (NiCr-Ni): –270 to +1 372 °C
- Type N (NiCrSi-NiSi): –270 to +1 300 °C
- Type R (PtRh13-Pt): –50 to +1 768 °C
- Type S (PtRh10-Pt): –50 to +1 768 °C
- Type T (Cu-CuNi): –260 to +400 °C
- IEC 60584, Part 1; ASTM E988-96:
- Type C (W5Re-W26Re): 0 to +2 315 °C
- Type D (W3Re-W25Re): 0 to +2 315 °C
- DIN 43710:
- Type L (Fe-CuNi): –200 to +900 °C
- Type U (Cu-CuNi): –200 to +600 °C
- GOST R8.585-2001:
- Type L (NiCr-CuNi): –200 to +800 °C
Voltage Transmitter (mV):
- –20 to 100 mV
- –5 to 30 mV
Connection Types
- Supports 2-wire, 3-wire, or 4-wire connection for RTD and resistance transmitters.
- Sensor current: ≤ 0.3 mA.
- With 2-wire circuit, compensation of wire resistance is possible (0 to 30 Ω).
- With 3-wire and 4-wire connection, sensor wire resistance up to max. 50 Ω per wire.
- Maximum sensor wire resistance for thermocouples and mV transmitters: 10 kΩ.
- Internal reference junction (Pt100) or external preset value (-40 to +85 °C).
- The two sensor inputs are not galvanically isolated from each other.
Output
- Protocol: PROFIBUS® PA (in accordance with EN 50170 Volume 2, IEC 61158-2, Manchester II encoding).
- Baudrate: 31.25 kBit/s.
- Failure current (FDE): 0 mA.
- Output Data (via AI blocks): Temperature (PV), temperature sensor 1 & 2, terminal temperature.
- Galvanic Isolation: U = 2 kV AC (input/output).
- Current Consumption: ≤ 11 mA.
- Switch-on Delay: 8 s.
Performance Characteristics
Measured Errors
- Accuracy is specified in accordance with DIN EN 60770.
- Digital values are transmitted via FIELDBUS®.
- Example for Pt100 (IEC 60751:2008), 0 to +200 °C:
- Typical measured error (digital value): 0.08 °C
- Maximum measured error (digital value): ≤ 0.12 °C
- Non-repeatability (digital value): 0.06 °C + 0.006% * (MV - LRV)
- Example for Type K (IEC 60584-1), 0 to +800 °C:
- Typical measured error (digital value): 0.31 °C
- Example for Resistance Transmitter, 10 to 400 Ω:
- Measured error (digital value): 32 mΩ
- Non-repeatability (digital value): 15 mΩ
Operating Influences
- Ambient Temperature and Supply Voltage: Influence values are specified per 1 °C change in ambient temperature and per 1 V change in supply voltage for various sensor types.
- Example for Pt100 (IEC 60751:2008):
- Ambient temperature influence (digital, maximum): ≤ 0.12 °C
- Supply voltage influence (digital, maximum): ≤ 0.12 °C
- Example for Type K (IEC 60584-1):
- Ambient temperature influence (digital, maximum): ≤ 0.04 °C
- Supply voltage influence (digital, maximum): ≤ 0.04 °C
- Example for Pt100 (IEC 60751:2008):
Long-Term Drift
- Resistance Thermometers (RTD):
- Example for Pt100 (IEC 60751:2008):
- After 1 year: ≤ 0.03 °C + 0.024% * measuring span
- After 3 years: ≤ 0.042 °C + 0.035% * measuring span
- After 5 years: ≤ 0.051 °C + 0.037% * measuring span
- Example for Pt100 (IEC 60751:2008):
- Thermocouples (TC):
- Example for Type K (IEC 60584-1):
- After 1 year: ≤ 0.09 °C + 0.017% * (MV + 150 °C)
- After 3 years: ≤ 0.14 °C + 0.023% * measuring span
- After 5 years: ≤ 0.19 °C + 0.024% * measuring span
- Example for Type K (IEC 60584-1):
Mechanical / Hydraulic
Installation
- Terminal head: Form B (flat face) as per DIN EN 50446.
- Field housing: Available for Ex d applications.
- Mounting: Wall or pipe mounting, or clip-on DIN rail (IEC 60715).
- Dimensions (Head Transmitter): 24.1 mm (width), 33 mm (height), 44 mm (depth).
- Cable Glands: M20x1.5, NPT ½" (depending on housing type).
Materials
- Housing (Head Transmitter): Polycarbonate (PC).
- Terminals: Screw terminals (nickel-plated brass), Push-in terminals (tin-plated brass).
- Field Housings: Aluminum (polyester powder coated) or Stainless Steel 316L.
Environmental Conditions
- Ambient Temperature Range: –40 to +85 °C (for hazardous areas, refer to Ex documentation).
- Storage Temperature: –40 to +100 °C.
- Humidity: Max. 95% relative humidity (condensation permitted).
- Climate Class: C as per EN 60654-1.
- Degree of Protection:
- Head transmitter (installed): Depends on terminal head or field housing.
- With field housing TA30A, TA30D, TA30H: IP 66/67 (NEMA Type 4x).
- Vibration Resistance: As per IEC 60068-2-6 (10 to 2000 Hz at 5g).
- Electromagnetic Compatibility (EMC): CE compliant, meets IEC/EN 61326 series and NAMUR Recommendation EMC (NE21). Interference emission Class B.
Electrical
Power Supply
- Supply Voltage: 9 to 32 V DC (polarity-independent), max. voltage Ub = 35 V.
- Power Source: Powered via PROFIBUS® PA bus.
Operability
- Local Operation: Head transmitter has no display. Optional attachable measured value display TID10 available. DIP switches on TID10 for hardware settings (e.g., write protection).
- Remote Operation: Configuration via PROFIBUS® PA communication using configuration software (e.g., Endress+Hauser FieldCare, SIMATIC PDM).
- Bus Address: Set via configuration software or DIP switches on optional display.
Standard Diagnostic Functions
- Sensor cable diagnostics (cable break, short-circuit, corrosion).
- Incorrect wiring detection.
- Internal device errors.
- Overrange/underrange detection.
- Ambient temperature out-of-range detection.
- Corrosion detection as per NAMUR NE89.
- Low voltage detection.
2-Channel Functions
- Sensor backup (switches to second sensor upon primary failure).
- Drift warning or alarm based on deviation between sensors.
- Temperature-dependent switching between sensors.
- Mean value or differential measurement from two sensors.
Certifications and Approvals
- PROFIBUS® PA certification by PNO (PROFIBUS® User Organization).
- Certified in accordance with PROFIBUS® PA Profile 3.02.
- Interoperable with certified devices from other manufacturers.
- Intrinsically safe apparatus for Zone 1 hazardous areas.
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.