Datasheet summary
iTemp TMT86
Engineering summary from PDF text extraction for iTemp TMT86. Verify every value with the OEM datasheet.
Summary
Product identification
- Product name: iTEMP TMT86
- Type: Dual-input temperature transmitter
- Communication: PROFINET with Ethernet-APL
Applications
- Temperature measurement with two independent universal inputs (RTD, Ω, TC, mV).
- System integration with PROFINET®.
- Installation in terminal head form B (flat face) as per DIN EN 50446.
- Optional: installation in field housing for Ex d applications.
- Digital communication down to the field level, even in explosive atmospheres.
- Reliability, long-term stability, high precision, and advanced diagnostic functions in critical processes.
Input
- Measured variable: Temperature (temperature-linear transmission behavior), resistance, and voltage.
- Inputs: Two independent universal inputs.
- Input types supported:
- Resistance thermometer (RTD):
- IEC 60751: Pt100, Pt200, Pt500, Pt1000
- JIS C1604: Pt100
- GOST 6651-94: Pt50, Pt100
- OIML R84: 2003, GOST 6651-2009: Cu50, Cu100
- OIML R84: 2003, GOST 6651-94: Cu50
- Resistance transmitter: 10 to 400 Ω, 10 to 2850 Ω
- Thermocouples (TC):
- IEC 60584, Part 1: Type A (W5Re-W20Re), Type B (PtRh30-PtRh6), Type E (NiCr-CuNi), Type J (Fe-CuNi), Type K (NiCr-Ni), Type N (NiCrSi-NiSi), Type R (PtRh13-Pt), Type S (PtRh10-Pt), Type T (Cu-CuNi)
- IEC 60584, Part 1; ASTM E988-96: Type C (W5Re-W26Re), Type D (W3Re-W25Re)
- DIN 43710: Type L (Fe-CuNi), Type U (Cu-CuNi)
- GOST R8.585-2001: Type L (NiCr-CuNi)
- Voltage transmitter (mV): –20 to 100 mV
- Resistance thermometer (RTD):
- Connection types for RTD: 2-wire, 3-wire, or 4-wire.
- Cold junction: Internal or external (requires Pt1000 sensor).
- Input isolation: Measuring inputs are not galvanically isolated from each other.
Output
- Output signal: PROFINET® according to IEEE 802.3cg 10BASE-T1L, 2-wire 10 Mbps.
- Signal on alarm: According to "Application Layer protocol for decentralized periphery", Version 2.4.
- Linearization: Temperature-linear, resistance-linear, voltage-linear.
- Galvanic isolation: 2 kV AC for 1 minute (input/output).
Protocol-specific data (PROFINET)
- Application layer: Version 2.4
- Communication type: 10 Mbps
- Conformance Class: B
- Netload Class: 10BASE-T1L
- Baud rates: Automatic 10 Mbps with full-duplex detection
- Cycle times: 128 ms
- Polarity: Auto-polarity
- Real Time Class: Class 1
- System redundancy support: System redundancy S2 (4 AR with 1 NAP)
- Neighborhood detection (LLDP): Yes
- Device profile: Profile DeviceID 0xB300
- Manufacturer ID: 0x11
- Device type ID: 0xA3FF
- Supported connections: 2 x AR (IO Controller AR), 2 x AR (device access, acyclic communication)
Power supply
- Supply voltage: APL port classifications SLAA or SLAC (hazardous areas), SLAX (non-hazardous areas).
- Connection values (APL field switch):
- Maximum input voltage: 15 VDC
- Minimum output values: 0.54 W
- Connection values (SPE switch, non-hazardous areas):
- Maximum input voltage: 30 VDC
- Minimum output values: 1.85 W
Performance characteristics
- Response time:
- ≤ 0.5 s per channel (RTD)
- ≤ 0.5 s per channel (TC)
- ≤ 1.6 s per channel (CJ)
- Response times double in two-channel mode.
- Reference operating conditions:
- Calibration temperature: +25 °C ±3 K
- Supply voltage: 15 V DC
- 4-wire circuit for resistance adjustment.
- Maximum measured error: See the official PDF for exact tabulated values.
- Operating influences: See the official PDF for exact tabulated values.
- Long-term drift: See the official PDF for exact tabulated values.
Mechanical construction
- Design: Head transmitter or field housing.
- Dimensions (Head transmitter):
- Housing height (screw terminals): 44 mm (1.73 in)
- Housing height (push-in terminals): Varies slightly from screw terminal version.
- Field housing options: TA30A, TA30H, TA30D with various specifications for degree of protection, material, and weight.
- Weight:
- Head transmitter: approx. 40 to 50 g (1.4 to 1.8 oz)
- Field housings: see specific housing specifications.
- Materials: Housing (Polycarbonate), Terminals (Nickel-plated brass, gold-plated or tin-plated contacts), Potting (QSIL 553). All materials are RoHS-compliant.
Environment
- Ambient temperature range:
- –40 to +85 °C (–40 to +185 °F) (standard)
- Extended ranges available for hazardous areas with specific order codes.
- Storage temperature: –52 to +100 °C (–62 to +212 °F).
- Operating altitude: Up to 4000 m (4374.5 yards) above mean sea level.
- Relative humidity: Condensation permitted; Max. 95% RH.
- Degree of protection:
- Head transmitter: IP 20 (depending on installed terminal head/housing).
- In field housing TA30A, TA30D, TA30H: IP 66/67 or IP 66/68 (NEMA Type 4x).
- Shock and vibration resistance: As per DIN EN 60068-2-27 and DNVGL-CG-0339 / DIN EN 60068-2-6.
- Electromagnetic compatibility (EMC): CE conformity; Interference immunity as per IEC/EN 61326 series (industrial); Interference emission as per IEC/EN 61326 series (Class B).
- Overvoltage category: Measuring category II as per IEC 61010-1.
- Pollution degree: Pollution degree 2 as per IEC 61010-1.
- Insulation class: Class III.
Operability
- Operating concept: Operator-oriented menu structure with guided operation and commissioning wizards.
- Local operation: Attachable measured value display TID10 (optional).
- Remote operation: PROFINET with Ethernet-APL, Web server, Service interface.
- System integration: PROFINET® Profile 4.0.
- Supported operating tools: Endress+Hauser FieldCare, DeviceCare, Field Xpert; SIMATIC PDM; Field Information Manager / FIM; Honeywell Field Device Manager.
Certificates and approvals
- PROFINET®-APL Certification: Certified and registered by PNO; supports PROFINET® S2 system redundancy.
- MTTF: 95 years.
Accessories
- Device-specific accessories: TID10 display unit, service cable, field housings (TA30x), DIN rail mounting adapter, wall/pipe mounting brackets.
- Communication-specific accessories: Commubox FXA291, Field Xpert SMT70/SMT77.
- Service-specific accessories: Device Viewer online tool.
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.
Official datasheet (PDF)