iTherm Moduline TM131

Engineering summary from PDF text extraction for iTherm Moduline TM131. Verify every value with the OEM datasheet.

Summary

Product identification

The iTHERM ModuLine TM131 is an innovative, highly modular, and robust RTD or TC thermometer designed for a wide range of industrial applications.

Application

  • For universal use.
  • Measuring range: –200 to +1,100 °C (–328 to +2,012 °F).
  • Pressure range up to 100 bar (1,450 psi).
  • Vibration-resistant sensor elements up to 60g.
  • Improved ease of maintenance: sensor replacement without process shutdown and easy, safe recalibration.

Measuring principle

  • Resistance thermometers (RTD): Utilize a Pt100 sensor with a resistance of 100 Ω at 0 °C. Available as wire-wound (WW) or thin-film (TF) sensors. TF sensors offer smaller sizes and better vibration resistance.
  • Thermocouples (TC): Employ the Seebeck effect to measure temperature differences. Standardized types include J, K, and N.

Measuring system components

  • Power supply unit/barrier
  • Display units
  • Surge arrester

Modular design

The thermometer features a modular design with several configurable options:

  • Terminal head: Available in aluminum, polyamide, or stainless steel.
  • Wiring, electrical connection, output signal: Options include ceramic terminal blocks, flying leads, and head transmitters with various output protocols (4 to 20 mA, HART®, Ethernet-APL, PROFIBUS® PA, FOUNDATION™ Fieldbus, IO-Link®).
  • Plug or cable gland: Polyamide or brass cable glands, M12, and 7/8" plugs are available.
  • Removable extension neck: Various options including QuickNeck for tool-free insert removal.
  • Lagging: Provides space between the thermometer and process connection.
  • Process connection: Various threaded, flanged, and compression fittings.
  • Thermowell: Versions with and without thermowells, available in various diameters, materials, and tip types.
  • Insert: Features sensor models like iTHERM QuickSens (fastest response times) and iTHERM StrongSens (high vibration resistance). Available in RTD (wire wound or thin-film) or thermocouple types (K, J, or N).

Input

  • Measured variable: Temperature.
  • Measuring range: Varies by sensor type.
    • Pt100 thin-film (TF), basic: –50 to +200 °C (–58 to +392 °F)
    • Pt100 thin film (TF), standard: –50 to +400 °C (–58 to +752 °F)
    • Pt100 thin film (TF), iTHERM StrongSens: –50 to +500 °C (–58 to +932 °F)
    • Pt100 wire wound (WW), extended: –200 to +600 °C (–328 to +1,112 °F)
    • Thermocouple TC, type J: –40 to +750 °C (–40 to +1,382 °F)
    • Thermocouple TC, type K: –40 to +1,100 °C (–40 to +2,012 °F)
    • Thermocouple TC, type N: (Measuring range not specified in extract)

Output

The measured value can be transmitted directly-wired or via an Endress+Hauser iTEMP transmitter.

  • Output signal:
    • Analog output 4 to 20 mA, HART® (optional SIL transmitter).
    • PROFIBUS® PA, FOUNDATION™ Fieldbus™, PROFINET® with Ethernet-APL, IO-Link®.

Power supply

  • Sensor connection wires are equipped with terminal lugs with a nominal diameter of 1.3 mm (0.05 in).
  • Details on terminal assignment for RTD and thermocouple sensor connections are provided, along with diagrams for various head-mounted and field transmitters.

Performance characteristics

  • Maximum measurement error: Tolerances for RTD resistance thermometers as per IEC 60751 (Class B, A, AA) are specified. Permissible deviation limits for thermocouples as per IEC 60584 and ASTM E230/ANSI MC96.1 are also provided.
  • Response time: Typical values in seconds (s) for t50 and t90 are provided for various thermowell diameters, tip types, and sensor configurations when tested in water.
  • Calibration: Information on calibration methods (fixed-point, reference thermometer), evaluation services, and sensor-transmitter matching is included. Minimum immersion lengths for inserts required for calibration are specified.
  • Insulation resistance: RTD and TC insulation resistance values are provided.

Installation

  • Orientation: No restrictions, but self-draining should be considered.
  • Installation instructions: Guidance on ensuring adequate immersion length for accuracy, especially in pipes, is provided.
  • Ambient conditions:
    • Ambient temperature range:
      • Terminal head without transmitter: Depends on head, gland, or connector.
      • Terminal head with transmitter: –40 to +85 °C (–40 to +185 °F).
      • Terminal head with transmitter and display: –20 to +70 °C (–4 to +158 °F).
      • QuickNeck extension neck: –50 to +140 °C (–58 to +284 °F).
    • Humidity: Condensation permitted as per IEC 60 068-2-33, max. 95% relative humidity as per IEC 60068-2-30 with iTEMP transmitters.
    • Climate class: As per EN 60654-1, Class C.

Degree of protection

  • Max. IP 66 (NEMA Type 4x encl.), depending on design.
  • Partly IP 68, tested in 1.83 m (6 ft) over 24 h.

Shock and vibration resistance

  • Inserts exceed IEC 60751 requirements (3g, 10 to 500 Hz).
  • Specific vibration resistance values for different sensor types are provided, with iTHERM StrongSens and iTHERM QuickSens (certain versions) reaching up to 600 m/s² (60g).

Process

  • Process temperature range: Max. –200 to +1,100 °C (–328 to +2,012 °F), dependent on sensor type and thermowell material.

Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.