Datasheet summary

iTherm Moduline TM412

Engineering summary from PDF text extraction for iTherm Moduline TM412. Verify every value with the OEM datasheet.

Summary

Product identification

The Endress+Hauser iTHERM ModuLine TM412 is a modular resistance thermometer designed for hygienic and aseptic applications in the Food & Beverages and Life Sciences industries. It utilizes a spring-loaded insert and is compatible with Pt100 temperature sensors according to IEC 60751.

Applications

  • Hygienic and aseptic applications in the Food & Beverages and Life Sciences industries.
  • Measuring range: –200 to +600 °C (–328 to +1 112 °F).
  • Pressure range: up to 40 bar (580 psi).
  • Protection class: up to IP69K.

Input

Measured variable

  • Temperature (temperature-linear transmission behavior).

Measuring range

The measuring range depends on the type of sensor used:

  • Pt100 thin-film: –50 to +200 °C (–58 to +392 °F)
  • Pt100 thin-film, iTHERM StrongSens (vibration-resistant > 60g): –50 to +500 °C (–58 to +932 °F)
  • Pt100 thin-film, iTHERM QuickSens (fast-response): –50 to +200 °C (–58 to +392 °F)
  • Pt100 wire wound (extended measuring range): –200 to +600 °C (–328 to +1 112 °F)

Output

Output signal

The measured value can be transmitted directly-wired or via Endress+Hauser iTEMP temperature transmitters using various protocols:

  • Analog output 4 to 20 mA, HART®
  • PROFIBUS® PA
  • FOUNDATION Fieldbus™
  • Bluetooth® connectivity (optional)
  • IO-Link®
  • PROFINET® with Ethernet-APL

Transmitters offer enhanced accuracy and reliability compared to directly wired sensors, with options for displays, bargraphs, and fault indication.

Performance characteristics

Maximum measured error

RTD resistance thermometer as per IEC 60751:

  • Class B: ± (0.3 + 0.005 · |t|) °C
  • Class A: ± (0.15 + 0.002 · |t|) °C
  • Class AA (former 1/3): ± (0.1 + 0.0017 · |t|) °C
Sensor typeOperating temperature rangeClass BClass AClass AA
Pt100 (TF) Basic–50 to +200 °C–50 to +200 °C–30 to +200 °C-
Pt100 (TF) Standard–50 to +400 °C–50 to +400 °C–30 to +250 °C0 to +150 °C
Pt100 (TF) iTHERM QuickSens–50 to +200 °C–50 to +200 °C–30 to +200 °C0 to +150 °C
Pt100 (TF) iTHERM StrongSens–50 to +500 °C–50 to +500 °C–30 to +300 °C0 to +150 °C
Pt100 (WW)–200 to +600 °C–200 to +600 °C–100 to +450 °C–50 to +250 °C

Response time

Tests in water at 0.4 m/s (1.3 ft/s), according to IEC 60751; 10 K temperature step change (response time without heat transfer paste, with thermowell). See the official PDF for exact tabulated values.

Installation

Orientation

No restrictions, but self-draining in the process must be guaranteed.

Installation instructions

  • Recommended immersion depth depends on sensor type and insert design to minimize heat dissipation errors.
  • For pipes, immersion depth should ideally be half the pipe diameter.
  • Observe installation instructions in Ex documentation for ATEX certification.
  • Minimum immersion lengths are recommended for calibration and to ensure transmitter functionality.

Environment

Ambient temperature range

  • Terminal head (without transmitter): Depends on terminal head, cable gland, or fieldbus connector.
  • Terminal head (with head transmitter): –40 to 85 °C (–40 to 185 °F). SIL mode: –40 to 70 °C (–40 to 158 °F).
  • Terminal head (with head transmitter and display): –20 to 70 °C (–4 to 158 °F).
  • Field transmitter (without display): –40 to 85 °C (–40 to 185 °F).
  • Field transmitter (with display): –40 to +80 °C (–40 to +176 °F). SIL mode: –40 to +75 °C (–40 to +167 °F).
  • Extension neck (iTHERM QuickNeck): –50 to +140 °C (–58 to +284 °F).

Humidity

  • Condensation permitted as per IEC 60 068-2-33.
  • Maximum relative humidity: 95% as per IEC 60068-2-30.

Degree of protection

  • Max. IP69K, depending on the design.

Shock and vibration resistance

  • Standard inserts (Pt100 WW or TF): 30 m/s² (3g) 1)
  • iTHERM StrongSens Pt100 (TF): > 600 m/s² (60g)
  • iTHERM QuickSens Pt100 (TF), version: ⌀6 mm (0.24 in): > 600 m/s² (60g)
  1. Vibration resistance also applies for the iTHERM QuickNeck.

Process

Process temperature range

  • Maximum –200 to +600 °C (–328 to +1 112 °F), depends on sensor type.

Thermal shock

  • Resistance in CIP/SIP process with a temperature increase from +5 to +130 °C (+41 to +266 °F) within 2 seconds.

Process pressure range

  • Maximum pressure depends on design, process connection, and process temperature. Refer to the 'Process connection' section in the official PDF for specific values.

Mechanical construction

Material

  • Materials in contact with product (FCM) comply with relevant standards. Specific materials not detailed in extract.

Surface roughness

  • For weld-in connections, Ra ≤ 0.76 µm (30 µin) is required.

Certificates and approvals

  • International certifications: explosion protection (e.g., ATEX/IECEx/FM/CSA).
  • Compliance with hygiene standards: 3-A®, EHEDG, ASME BPE, FDA, TSE Certificate of Suitability.

Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.