AS3020

Engineering summary from PDF text extraction for AS3020. Verify every value with the OEM datasheet.

Summary

Product identification

The unit type AS3020 is a universal controller for automatic monitoring and control of cooling tower plants.

Features

User Interface

  • Monochrome LCD display (16x2 characters)
  • Control through three internal keys
  • Supports English, French, German, and Dutch languages

Inputs

  • 3x Input for potential-free switch
  • 1x Conductivity meter

Conductivity meter

  • Automatic range switching
  • Supports cell constants from 0.01 to 10.00 cm⁻¹
  • Range from 0.5 to 100,000 µS/cm (depending on the cell used)
  • Manual temperature compensation
  • Utilizes a capacitive cell

Outputs

  • 3x Relay output (powered)

Memory

  • Programming is stored in non-volatile memory and is not affected by power loss.

Enclosure

  • Suitable for wall mounting
  • IP65 rated

Power supply

The unit accepts the following power supply inputs and provides a corresponding output:

  • 24 VAC input / 24 VAC output
  • 115 VAC input / 115 VAC output
  • 230 VAC input / 230 VAC output
  • 12 VDC input / 12 VDC output
  • 24 VDC input / 24 VDC output

Function Table

The relay outputs and digital inputs are related to the following functions:

Relay Outputs

  • Inlet valve
  • Flush valve
  • Alarm

Digital Inputs

  • Alarm reset
  • High level switch
  • Low level switch

Ordering Information

The AS3020 controller is ordered with a specified power supply:

  • AS3020 controller with power supply:
    • 24V: 24 VAC / 24 VAC
    • 115V: 115 VAC / 115 VAC
    • 230V: 230 VAC / 230 VAC
    • 12VDC: 12 VDC / 12 VDC
    • 24VDC: 24 VDC / 24 VDC