Datasheet summary
AS3035
Engineering summary from PDF text extraction for AS3035. Verify every value with the OEM datasheet.
Summary
Product Identification
The unit type AS3035 is a controller for cooling tower plants, applicable for automatic monitoring and control.
Features
User Interface
- Monochrome LCD display (16x2 characters)
- Control through six keys
- Five LEDs for process and alarm indication
- Acoustic signal for alarm
- Multiple language support: English, French, German, Dutch, Spanish, Italian, Swedish, and Danish
Inputs
- 4x inputs for potential-free switches
- 1x conductivity meter input
- Optional (with circuit board IF2030): 1x additional input for potential-free switch
Conductivity Meter
- Automatic range switching
- Supports cell constants from 0.01 to 10.00 cm⁻¹
- Measurement range from 0.5 to 100,000 µS/cm (depending on the used cell)
- Manual temperature compensation
- Uses a capacitive cell
Outputs
- 1x powered relay output
- 2x relay outputs (dry contact)
- Optional (with circuit board IF2030): 2x additional relay outputs (dry contact)
Memory
- Programming configuration is stored in non-volatile memory and retained during power loss.
Enclosure
- Suitable for wall mounting
- IP65 rated
Power Supply Options
- 24 VAC input / 24 VAC output
- 115 VAC input / 115 VAC output
- 230 VAC input / 230 VAC output
- 115 VAC input / 24 VAC output
- 230 VAC input / 24 VAC output
Ordering Information
- AS3035: Standard wall-mounted unit with 1 powered relay output and 2 dry contact relay outputs.
- AS3035IF: Unit with 1 powered relay output, 4 dry contact relay outputs, and 1 temperature meter.
Power supply options are appended to the base model code:
- 24V: 24 VAC / 24 VAC
- 115V: 115 VAC / 115 VAC
- 230V: 230 VAC / 230 VAC
- 115/24V: 115 VAC / 24 VAC
- 230/24V: 230 VAC / 24 VAC