Back to EWS
EWS logo

Datasheet summary

AS3050

Engineering summary from PDF text extraction for AS3050. Verify every value with the OEM datasheet.

Summary

Product identification

  • Product type: AS3050 or AS3051 controller for cooling tower plants.

Description

This controller is designed for automatic monitoring and control of cooling tower plants. It features a conductivity meter, with an optional second conductivity meter and a temperature meter. An optional circuit board provides two recorder outputs (0(4)-20 mA). The unit offers six programmable stages: "Service", "Flush", "Low level", "Flush blocked", and "Shot dosing". Configuration settings are stored in non-volatile memory.

Features

User Interface

  • Monochrome LCD display (16x2 characters)
  • Control via six keys
  • Ten LEDs for process and alarm indication
  • Available languages: English, French, German, Dutch, Spanish, and Italian

Inputs

  • 7x Input for potential-free switch
  • 1x Conductivity meter
  • Optional circuit board for:
    • 2nd Conductivity meter
    • 1x Temperature meter

Conductivity meter

  • Automatic range switching
  • Cell constants from 0.01 to 10.00 cm⁻¹
  • Range from 0.5 to 100,000 µS/cm (depending on cell used)
  • Manual or automatic temperature compensation
  • Capacitive cell

Temperature meter

  • Range from 0 to 94°C (32 to 201 °F)
  • PT1000 sensor

Outputs

  • 4x Relay output (powered)
  • 3x Relay output (dry contact)
  • Optional circuit board for:
    • 2x Analogue output (0-20mA) for recorder

Memory

  • Programming is stored and unaffected by power loss.

Enclosure

  • AS3050: Suitable for wall mounting, IP65
  • AS3051: Suitable for panel mounting, IP42

Power supply

  • 24 VAC input / 24 VAC output
  • 115 VAC input / 115 VAC output
  • 230 VAC input / 230 VAC output

Function Table

Relay Outputs

  • Flush valve
  • Inlet valve
  • Proportional dosing
  • Biocide dosing
  • Alarm

Digital Inputs

  • Water meter
  • High level switch
  • Low level switch
  • Flush Blocking 1
  • Flush Blocking 2
  • Low level 1 circulation tank
  • Low level 2 circulation tank

Ordering Information

Wall mounted (AS3050)

  • AS3050/1: with 1 conductivity meter
  • AS3050/2: with 2 conductivity meters and 1 temperature input
  • AS3050/1/I: with 1 conductivity meter and 2 recorder outputs
  • AS3050/2/I: with 2 conductivity meters, 1 temperature input, and 2 recorder outputs

Panel mounted (AS3051)

  • AS3051/1: with 1 conductivity meter
  • AS3051/2: with 2 conductivity meters and 1 temperature input
  • AS3051/1/I: with 1 conductivity meter and 2 recorder outputs
  • AS3051/2/I: with 2 conductivity meters, 1 temperature input, and 2 recorder outputs

Power Supply Options (add to codes above)

  • 24V: 24 VAC / 24 VAC
  • 115V: 115 VAC / 115 VAC
  • 230V: 230 VAC / 230 VAC

Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.