Datasheet summary
AS3050
Engineering summary from PDF text extraction for AS3050. Verify every value with the OEM datasheet.
Summary
Product identification
- Product type: AS3050 or AS3051 controller for cooling tower plants.
Description
This controller is designed for automatic monitoring and control of cooling tower plants. It features a conductivity meter, with an optional second conductivity meter and a temperature meter. An optional circuit board provides two recorder outputs (0(4)-20 mA). The unit offers six programmable stages: "Service", "Flush", "Low level", "Flush blocked", and "Shot dosing". Configuration settings are stored in non-volatile memory.
Features
User Interface
- Monochrome LCD display (16x2 characters)
- Control via six keys
- Ten LEDs for process and alarm indication
- Available languages: English, French, German, Dutch, Spanish, and Italian
Inputs
- 7x Input for potential-free switch
- 1x Conductivity meter
- Optional circuit board for:
- 2nd Conductivity meter
- 1x Temperature meter
Conductivity meter
- Automatic range switching
- Cell constants from 0.01 to 10.00 cm⁻¹
- Range from 0.5 to 100,000 µS/cm (depending on cell used)
- Manual or automatic temperature compensation
- Capacitive cell
Temperature meter
- Range from 0 to 94°C (32 to 201 °F)
- PT1000 sensor
Outputs
- 4x Relay output (powered)
- 3x Relay output (dry contact)
- Optional circuit board for:
- 2x Analogue output (0-20mA) for recorder
Memory
- Programming is stored and unaffected by power loss.
Enclosure
- AS3050: Suitable for wall mounting, IP65
- AS3051: Suitable for panel mounting, IP42
Power supply
- 24 VAC input / 24 VAC output
- 115 VAC input / 115 VAC output
- 230 VAC input / 230 VAC output
Function Table
Relay Outputs
- Flush valve
- Inlet valve
- Proportional dosing
- Biocide dosing
- Alarm
Digital Inputs
- Water meter
- High level switch
- Low level switch
- Flush Blocking 1
- Flush Blocking 2
- Low level 1 circulation tank
- Low level 2 circulation tank
Ordering Information
Wall mounted (AS3050)
- AS3050/1: with 1 conductivity meter
- AS3050/2: with 2 conductivity meters and 1 temperature input
- AS3050/1/I: with 1 conductivity meter and 2 recorder outputs
- AS3050/2/I: with 2 conductivity meters, 1 temperature input, and 2 recorder outputs
Panel mounted (AS3051)
- AS3051/1: with 1 conductivity meter
- AS3051/2: with 2 conductivity meters and 1 temperature input
- AS3051/1/I: with 1 conductivity meter and 2 recorder outputs
- AS3051/2/I: with 2 conductivity meters, 1 temperature input, and 2 recorder outputs
Power Supply Options (add to codes above)
- 24V: 24 VAC / 24 VAC
- 115V: 115 VAC / 115 VAC
- 230V: 230 VAC / 230 VAC
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.
Official datasheet (PDF)
Curated from selected public technical reference material for discovery and preliminary comparison. This summary is not a substitute for a current certified manufacturer datasheet. Verify revisions and design limits before use.