Datasheet summary
CTS8000
Engineering summary from PDF text extraction for CTS8000. Verify every value with the OEM datasheet.
Summary
Product Identification
The unit type is CTS8000, designed for automatic monitoring and control of cooling tower plants. It features five operational stages: "Stand by", "Service", "Flushing", "Biociddosing", and "Maintenance".
Features
User Interface
- Color 7" TFT display (800x480)
- Touch panel control
- Available languages: English, French, German, Dutch
Inputs
- 8x Inputs for potential-free switches
- CTS: 1x Capacitive conductivity meter (passive) + 1x Temperature meter
- CTI: 1x Inductive conductivity meter (0-10V)
Expandable Inputs:
- CTS: 3x Capacitive conductivity meters (passive) + 3x Temperature meters
- CTI: 1x Inductive conductivity meter (0-10V)
- Up to 12x 0(4)-20mA inputs (for Flow, pressure, conductivity, pH, tank level) or pulse inputs (e.g., paddle wheel flow meter)
Conductivity Meter
- Automatic range switching
- Cell constants: 0.01 - 10.00 cm⁻¹
- Measurement range: 0.5 - 100,000 µS/cm (depending on cell)
- Manual or automatic temperature compensation
- Capacitive cell type
Temperature Meter
- Range: 0 - 94°C (32 - 201 °F)
- Sensor type: PT1000
Outputs
- 4x Powered relay outputs
- 3x Dry contact relay outputs
Optional Outputs:
- 7x Additional relay outputs (4x powered / 3x dry contact)
- 6x 0(4)-20mA outputs (for recorder, soft starter set point)
Memory
- Storage for the last twenty alarm messages
- Real-time clock with a "lifetime" battery
- Programming configuration stored in non-volatile memory
SD Card
- Supports software updates
- Programming save and load functionality
- Data log, Process log, and Alarm log storage
Communication (Optional)
- RS485 (data log format: CSV)
- RS232 (data log format: CSV)
- Webserver
- Email notifications for alarms
Enclosure
- Suitable for wall mounting, panel mounting, and plate mounting
- IP65 rated
Power Supply Options
- 24 VAC input
- 115 VAC input
- 230 VAC input
- With 24 VAC output: 115 VAC input, 230 VAC input, 240 VAC input
- (Output = input or extern) for 24-240 VAC input
Ordering Information
- Base Unit: CTS8000 (capacitive), CIS8000 (inductive)
- Power Supply: Specific configurations available, including 115/230/240 VAC input with 24 VAC output, or universal 24-240 VAC input.
- Communication: Options for without or with RS232, RS485, and Ethernet.
- Relay Outputs: Configurable number of boards with 7 relay outputs each (1-2 boards).
- Conductivity/Temperature Meters: Configurable number of meters (1-4).
- 0-20mA Inputs: Configurable number of additional boards with 3 inputs each (0-4 boards).
- 0-20mA Outputs: Configurable number of additional boards with 3 outputs each (0-2 boards).