Summary

Product Identification

The unit type is ES2030CV, a controller for softeners.

Description

The ES2030CV is designed for automatic monitoring and control of softener plants, suitable for single and double column installations in alternating, parallel, or serial circuits. It is universally implementable for a wide range of control and pilot valves. User-specific requirements can be adapted through built-in programmable options, and the programmed configuration is stored in non-volatile memory.

Features

User Interface

  • Monochrome LCD display (16x2 characters)
  • Control via seven keys
  • Eight LEDs for process and alarm indication
  • Acoustic alarm signal
  • Supported languages: English, French, German, Dutch, Spanish, and Italian

Inputs

  • 1x Input for potential-free switch (standard)
  • Optional (with circuit board IF2030): 1x Additional input for potential-free switch

Outputs

  • 5x Relay output (powered) (standard)
  • Optional (with circuit board IF2030): 2x Relay output (dry contact)

Memory

  • Programming stored in non-volatile memory, unaffected by power loss.
  • Real-time clock with battery backup.

SD Card

  • Supported for software updates.

Enclosure

  • Suitable for wall mounting.
  • IP65 rated.

Power Supply

The unit accepts various input voltages and provides a corresponding output voltage:

  • 24 VAC input / 24 VAC output
  • 115 VAC input / 115 VAC output
  • 230 VAC input / 230 VAC output
  • 115 VAC input / 24 VAC output
  • 230 VAC input / 24 VAC output

Function Table

Relay outputs and digital inputs are associated with the following functions:

Relay OutputsDigital Inputs
Control valves (2x)Water meter
Additional programRegeneration wait
Flow pulseLevel switch storage
Flush valveLevel switch chemicals
RegenerationRegeneration start
Alarm

Ordering Information

Wall Mounted Units

  • ES2030CV: With 5 powered relay outputs and 1 digital input.
  • ES2030CI: With 5 powered relay outputs, 2 relay outputs with dry contact, and 2 digital inputs.

Power Supply Options (Add to base unit codes)

  • 24V: 24 VAC / 24 VAC
  • 115V: 115 VAC / 115 VAC
  • 230V: 230 VAC / 230 VAC
  • 115/24V: 115 VAC / 24 VAC
  • 230/24V: 230 VAC / 24 VAC