Product identification

  • Unit Type: ES2070 CA
  • Description: Controller for Demineralisation

Description

The ES2070 CA is a universal controller for automatic monitoring and control of demineralisation plants. It can monitor conductivity, temperature, and several inputs, such as level switches, wait signals, and external regeneration start. Programmable options allow adaptation to user-specific requirements. The programmed configuration is stored in non-volatile memory, unaffected by power loss.

Features

User Interface

  • Monochrome character LCD display: 2x16
  • Six keys
  • Languages: English, French, German, Dutch, Italian

Inputs

  • 6x Input for potential-free switch
  • 1x Conductivity meter
  • 1x Temperature meter

Conductivity meter

  • Automatic range switching
  • Cell constants: 0.01 - 10.00 cm⁻¹
  • Range: 0.5 - 100,000 µS/cm (depending on used cell)
  • Manual or automatic temperature compensation
  • Capacitive cell

Temperature meter

  • Range: 0 - 94°C (32 - 201 °F)
  • Sensor type: PT1000

Outputs

  • 9x Relay output (powered) - For single valve or control valve
  • 6x Relay output (dry contact) - Programmable for valve or special function

Memory

  • Real-time clock with "lifetime" battery
  • Programming stored in non-volatile memory, unaffected by power loss

Enclosure

  • Suitable for wall mounting
  • IP65

Power supply

The unit supports various input and output voltage combinations:

  • 24 VAC input / 24 VAC output
  • 115 VAC input / 115 VAC output
  • 230 VAC input / 230 VAC output
  • 115 VAC input / 24 VAC output
  • 230 VAC input / 24 VAC output
  • 240 VAC input / 24 VAC output

Ordering Information

The model is specified as "ES2070 CA + voltage", indicating the input and output voltages.

  • Example: ES2070 CA 230/24V signifies 230 VAC input and 24 VAC output for relays.