Back to EWS
EWS logo

Datasheet summary

OS3050

Engineering summary from PDF text extraction for OS3050. Verify every value with the OEM datasheet.

Summary

Product identification

The unit type OS3050 (OS3051) is designed for automatic monitoring and control of reverse osmosis plants. It supports five operational stages: "Stand by", "Production", "Rinse after production", "Rinse during standby", and "Maintenance".

Features

User Interface

  • Monochrome LCD display (16x2 characters)
  • Control via six keys
  • Ten LEDs for process and alarm indication
  • Supported languages: English, French, German, Dutch, Spanish, and Italian

Inputs

  • 7x Inputs for potential-free switches
  • 1x Conductivity meter input

Optional circuit board provides:

  • 2nd Conductivity meter input
  • 1x Temperature meter input

Conductivity Meter

  • Automatic range switching
  • Cell constants: 0.01 - 10.00 cm⁻¹
  • Measurement range: 0.5 - 100,000 µS/cm (dependent on the cell used)
  • Manual or automatic temperature compensation
  • Capacitive cell type

Temperature Meter (Optional)

  • Range: 0 - 94°C (32 - 201 °F)
  • Sensor type: PT1000

Outputs

  • 4x Relay outputs (powered)
  • 3x Relay output (dry contact)

Optional circuit board provides:

  • 2x Analogue outputs (0-20mA) for recorders

Memory

  • Programming configuration is stored in non-volatile memory, unaffected by power loss.

Enclosure

  • OS3050: Suitable for wall mounting, IP65
  • OS3051: Suitable for panel mounting, IP42

Power Supply

  • 24 VAC input / 24 VAC output
  • 115 VAC input / 115 VAC output
  • 230 VAC input / 230 VAC output

Function Table

Relay Outputs

  • Inlet valve
  • High pressure pump
  • Concentrate valve
  • Permeate valve
  • Dosing pump
  • Alarm
  • Malfunction

Digital Inputs

  • Stop
  • High level switch
  • Low level switch
  • Exceeded water pressure
  • Low water pressure
  • Concentrate flow switch
  • Motor security switch
  • Remote alarm reset

Ordering Information

Wall mounted (OS3050):

  • OS3050/1: With 1 conductivity meter
  • OS3050/2: With 2 conductivity meters and 1 temperature input
  • OS3050/1/I: With 1 conductivity meter and 2 recorder outputs
  • OS3050/2/I: With 2 conductivity meters, 1 temperature input, and 2 recorder outputs

Panel mounted (OS3051):

  • OS3051/1: With 1 conductivity meter
  • OS3051/2: With 2 conductivity meters and 1 temperature input
  • OS3051/1/I: With 1 conductivity meter and 2 recorder outputs
  • OS3051/2/I: With 2 conductivity meters, 1 temperature input, and 2 recorder outputs

Add power supply option to the above codes:

  • 24V: 24 VAC / 24 VAC
  • 115V: 115 VAC / 115 VAC
  • 230V: 230 VAC / 230 VAC