Datasheet summary
OS3050
Engineering summary from PDF text extraction for OS3050. Verify every value with the OEM datasheet.
Summary
Product identification
The unit type OS3050 (OS3051) is designed for automatic monitoring and control of reverse osmosis plants. It supports five operational stages: "Stand by", "Production", "Rinse after production", "Rinse during standby", and "Maintenance".
Features
User Interface
- Monochrome LCD display (16x2 characters)
- Control via six keys
- Ten LEDs for process and alarm indication
- Supported languages: English, French, German, Dutch, Spanish, and Italian
Inputs
- 7x Inputs for potential-free switches
- 1x Conductivity meter input
Optional circuit board provides:
- 2nd Conductivity meter input
- 1x Temperature meter input
Conductivity Meter
- Automatic range switching
- Cell constants: 0.01 - 10.00 cm⁻¹
- Measurement range: 0.5 - 100,000 µS/cm (dependent on the cell used)
- Manual or automatic temperature compensation
- Capacitive cell type
Temperature Meter (Optional)
- Range: 0 - 94°C (32 - 201 °F)
- Sensor type: PT1000
Outputs
- 4x Relay outputs (powered)
- 3x Relay output (dry contact)
Optional circuit board provides:
- 2x Analogue outputs (0-20mA) for recorders
Memory
- Programming configuration is stored in non-volatile memory, unaffected by power loss.
Enclosure
- OS3050: Suitable for wall mounting, IP65
- OS3051: Suitable for panel mounting, IP42
Power Supply
- 24 VAC input / 24 VAC output
- 115 VAC input / 115 VAC output
- 230 VAC input / 230 VAC output
Function Table
Relay Outputs
- Inlet valve
- High pressure pump
- Concentrate valve
- Permeate valve
- Dosing pump
- Alarm
- Malfunction
Digital Inputs
- Stop
- High level switch
- Low level switch
- Exceeded water pressure
- Low water pressure
- Concentrate flow switch
- Motor security switch
- Remote alarm reset
Ordering Information
Wall mounted (OS3050):
- OS3050/1: With 1 conductivity meter
- OS3050/2: With 2 conductivity meters and 1 temperature input
- OS3050/1/I: With 1 conductivity meter and 2 recorder outputs
- OS3050/2/I: With 2 conductivity meters, 1 temperature input, and 2 recorder outputs
Panel mounted (OS3051):
- OS3051/1: With 1 conductivity meter
- OS3051/2: With 2 conductivity meters and 1 temperature input
- OS3051/1/I: With 1 conductivity meter and 2 recorder outputs
- OS3051/2/I: With 2 conductivity meters, 1 temperature input, and 2 recorder outputs
Add power supply option to the above codes:
- 24V: 24 VAC / 24 VAC
- 115V: 115 VAC / 115 VAC
- 230V: 230 VAC / 230 VAC
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.
Official datasheet (PDF)
Curated from selected public technical reference material for discovery and preliminary comparison. This summary is not a substitute for a current certified manufacturer datasheet. Verify revisions and design limits before use.