The RGS3000 is a universal controller for automatic monitoring and control of reverse osmosis plants. It supports several operational stages: "Stand by", "Production", "Rinse after production", "Rinse during production", "Rinse during standby", "Maintenance", and "Regeneration".
Ordering Information
- RGS3x00: 4 digital inputs, 3 relay outputs, 1 conductivity meter, 1 temperature meter, and SD Card functions.
- RGS3x01: 5 digital inputs, 5 relay outputs, 1 conductivity meter, 1 temperature meter, and SD Card functions.
- RGS3x12: 5 digital inputs, 5 relay outputs, 1 conductivity meter, 1 temperature meter, SD Card functions, Ethernet (internet/email), and RS485.
The 'x' in the model number denotes the power supply configuration:
- 0: 24 VAC input / 24 VAC output
- 1: 115 VAC input / 115 VAC output
- 2: 230 VAC input / 230 VAC output
- 3: 115 VAC input / 24 VAC output
- 4: 230 VAC input / 24 VAC output
- 5: 240 VAC input / 24 VAC output
An example configuration is RGS3212, indicating a 230 VAC input/output, with SD Card, 5 digital inputs, 5 relay outputs, conductivity and temperature meters, Ethernet, and RS485.
User Interface
- Monochrome graphic LCD display (128x64 pixels)
- Control via four keys
- Five LEDs for process and alarm indication
- Supports English, French, German, and Dutch languages
Inputs
- RGS3x00: 4x inputs for potential-free switches
- RGS3x01 / RGS3x12: 5x inputs for potential-free switches
- 1x Conductivity meter input
- 1x Temperature meter input
Conductivity Meter
- Automatic range switching
- Cell constants from 0.01 - 10.00 cm⁻¹
- Measurement range: 0.5 - 100,000 µS/cm (depending on the cell used)
- Manual or automatic temperature compensation
- Capacitive cell type
Temperature Meter
- Measurement range: 0 - 94°C (32 - 201 °F)
- Sensor type: PT1000
Outputs
- RGS3x00: 1x powered relay output, 2x custom configurable relay outputs (powered or dry contact)
- RGS3x01: 2x custom configurable relay outputs (powered or dry contact)
- RGS3x12: 4x custom configurable relay outputs (powered or dry contact)
Memory
- Stores the last twenty alarm messages.
- Real-time clock with battery backup.
- Configuration is stored in non-volatile memory, unaffected by power loss.
SD Card Functionality
- Software updates
- Programming (Save and Load)
- Data logging
Communication (Available in RGS3x12)
- RS485: Supports data logging in XML or CSV formats.
- Webserver:
- Schematic visualization
- Configuration management
- Download log files from SD Card
- Email messages: For alarms.
Electrical
- Multiple input/output voltage options are available:
- 24 VAC input / 24 VAC output
- 115 VAC input / 115 VAC output
- 230 VAC input / 230 VAC output
- 115 VAC input / 24 VAC output
- 230 VAC input / 24 VAC output
- 240 VAC input / 24 VAC output
Mechanical / Hydraulic
- Enclosure suitable for wall mounting, panel mounting, and plate mounting.
- IP65 rated.
Function Table
Relay outputs and digital inputs are freely programmable for functions including:
Relay Outputs:
- Inlet valve
- High pressure pump
- Concentrate valve
- Permeate valve
- Dosing pump
- Booster pump
- Alarm
- Additional program
Digital Inputs:
- Stop
- High level switch
- Low level switch
- Exceeded water pressure
- Low water pressure
- Concentrate flow switch
- Motor security switch
- Remote alarm reset
- Regeneration input
- Pressure for membrane
- Pressure after membrane
- Pressure permeate
- Level switch dosing tank