Datasheet summary
SM 60
Engineering summary from PDF text extraction for SM 60. Verify every value with the OEM datasheet.
Summary
Product identification
Product: SM60 Ozone Controller | Switch Family: AQL Ozone family
Features
- Accurate control of ozone in air
- Ideal controller for ozone generators
- Low sensor drift via active sampling
- Large LED status indicators
- Adjustable relay set point
- Relay switch outputs
- Analog 0-5V output
- RS 232 | RS 485 outputs
- Robust and reliable
Specifications
- Sensor type: Analytic GSS Technology ® Gas Sensitive Semiconductor
- Sampling method: Active sampling via fan
- Operational mode: Continuous control
- Warm up time: 10 minutes (max. accuracy)
- LED status indicators: Green = sensor ON/OFF | Amber = relay energized (i.e. O₃ generator ON/OFF)
- Relay set point: Adjustable via dipswitch (OZL default = 0.1 ppm)
- Control band: 10% hysteresis (avoids O₃ generator “hunting”)
- Digital outputs: RS 232 | RS 485
- Analog output: 0-5 VDC (8 bit)
- Relay outputs: Normally Open | Normally Closed | Common
- Primary relay rating: 24V | 2A (use with secondary relay for switching high voltage loads)
- Power supply: 12 VDC | 800 mA | Plug-in AC power adaptor supplied
- Enclosure rating: IP20 & NEMA 1 equivalent
- Enclosure dimensions: 130 W x 94 H x 57 D (mm) | 5 ⅛ W x 3 ¾ H x 2 ¼ D (in)
- Enclosure casing: Flame resistant thermoplastic PS
- Enclosure mounting: Screw fix
- Weight: 225 g | 8 oz (excludes AC power adaptor)
- Approvals: Part 15 of FCC Rules, EN 61000-6-3: 2001, EN 61000-6-1: 2001
Ozone Sensors
| Sensor | Calibrated Range | Maximum Exposure | 0-5V Output Scale | Accuracy | Output Resolution | Response Time T90 | Operating Conditions |
|---|---|---|---|---|---|---|---|
| OZL | 0-0.5 ppm | 1 ppm | 0-0.500 | <± 15% | 0.002 ppm | < 60 s | -5°C to 40°C |
| OZH | 0.5-20 ppm | 25 ppm | 0-50 | <± 15% | 0.2 ppm | < 60 s | 5 to 95% RH* |
* Non-condensing
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.
Official datasheet (PDF)
Curated from selected public technical reference material for discovery and preliminary comparison. This summary is not a substitute for a current certified manufacturer datasheet. Verify revisions and design limits before use.