Datasheet summary
FC 102
Engineering summary from PDF text extraction for FC 102. Verify every value with the OEM datasheet.
Summary
Product Identification
The VLT® HVAC Drive series is a dedicated drive for HVAC applications, built with advanced intelligence and features designed for pumps, fans, and compressors.
Product Range
- Power Ratings:
- 3 x 200 – 240 V: 1.1 – 45 kW
- 3 x 380 – 480 V: 1.1 – 1000 kW
- 3 x 525 – 600 V: 1.1 – 90 kW
- 3 x 525 – 690 V: 45 – 1400 kW (All with 110% overload torque)
- Enclosure Ratings:
- IP 00: 45 – 630 kW
- IP 20: 1.1 – 400 kW
- IP 21 (NEMA 1): 1.1 – 1400 kW
- IP 54 (NEMA 12): 55 – 1400 kW
- IP 55 (NEMA 12): 1.1 – 90 kW
- IP 66 (NEMA 4X indoor): 1.1 – 90 kW
- Optional coating available for aggressive environments.
Operating Limits
- Maximum ambient temperature: 50°C without derating (D-frame: 45°C).
Feed Water
- Supply Voltage:
- 200 – 240 V ±10%
- 380 – 480 V ±10%
- 525 – 600 V ±10%
- 525 – 690 V ±10%
- Supply frequency: 50/60 Hz
- Displacement Power Factor (cos φ): Near unity (> 0.98)
- Switching on input supply L1, L2, L3: 1–2 times/min.
Product Water
- Output voltage: 0–100% of supply voltage
- Output frequency: 0–590 Hz
- Ramp times: 1–3600 sec.
- Switching on output: Unlimited
Electrical
- Digital Inputs:
- Programmable digital inputs: 6*
- Logic: PNP or NPN
- Voltage level: 0–24 VDC (* 2 can be used as digital outputs)
- Pulse Inputs:
- Programmable pulse inputs: 2*
- Voltage level: 0–24 VDC (PNP positive logic)
- Pulse input accuracy: (0.1–110 kHz) (* Utilize some of the digital inputs)
- Analogue Input:
- Analogue inputs: 2
- Modes: Voltage or current
- Voltage level: 0 V to +10 V (scaleable)
- Current level: 0/4 to 20 mA (scaleable)
- Analogue Output:
- Programmable analogue outputs: 1
- Current range at analogue output: 0/4–20 mA
- Relay Outputs:
- Programmable relay outputs: 2 (240 VAC, 2 A and 400 VAC, 2 A)
Mechanical / Hydraulic
- Back-channel cooling: For frame D, E, and F.
- Cooling Concept: Unique cooling concept with no ambient air flow over electronics.
Features & Benefits
- HVAC Functionality: Dedicated HVAC I/O, integrated fan, pump, and compressor functionality, Auto tuned PID's, Smart Logic Controller, Real Time Clock, Fire Override Mode, Dry run Detection, Constant Torque.
- Energy Saving: Automatic Energy Optimizer function (saves 5 – 15% energy), advanced energy monitoring, flow compensation, sleep mode.
- Robustness: Robust single enclosure, maintenance-free, problem-free operation in harsh environments, max ambient temp. 50°C without derating.
- User-Friendly: Awarded graphical display (27 languages), USB plug and play, PC software tools (VLT® Motion Control Tool MCT 10, VLT® Energy Box, VLT® Motion Control Tool MCT 31).
- EMC Compliance: Built-in DC coils and RFI filters, Integrated DC link harmonic filters (meets EN 61000-3-12), Integrated EMC filters (meets EN 55011 Class B, A1 or A2).
Application Options
- Integrated Options:
- VLT® General Purpose I/O MCB 101
- VLT® Relay Card MCB 105
- VLT® Analog I/O MCB 109
- VLT® 24 V External Supply MCB 107
- VLT® Sensor Input MCB 114 (for motor protection)
- Brake chopper (IGBT) option
- External Power Options: Advanced harmonic filters, dU/dt filters, Sine wave filters.
- High Power Options: IEC Emergency stop, Safety Stop, RFI filter, NAMUR terminals, RCD, IRM, Mains shielding, Regen terminals.
Communication
- Standard Built-in: FC Protocol, N2 Metasys, FLN Apogee, Modbus RTU, BACnet embedded.
- Optional: LonWorks (MCA 108), BACnet (MCA 109), DeviceNet (MCA 104), Profibus (MCA 101).