Datasheet summary
FR-D700
Engineering summary from PDF text extraction for FR-D700. Verify every value with the OEM datasheet.
Summary
Product Identification
- Product Line: FR-D700 Series Inverter
- Manufacturer: Mitsubishi
Features
The FR-D700 series inverters are designed for reliability, ease of use, and enhanced functionality. Key features include:
- Safety Stop Function: Compliant with EU Machinery Directive, providing immediate output shutoff to the motor upon activation of an external Emergency Stop device. Conforms to EN ISO 13849-1 Category 3 / PLd and EN62061 / IEC61508 SIL2 standards.
- High Starting Torque: Achieves 150%/1Hz high starting torque using General-purpose magnetic flux vector control. (Note: 200%/3Hz for 3.7K or less with slip compensation).
- Auto Tuning: Includes Mitsubishi's "non-rotation" auto tuning function for optimal control of various motors.
- Long-Life Design:
- Cooling fan designed for a 10-year life.
- Capacitors designed for a 10-year life (rated for 5000 hours at 105°C ambient).
- Life Check Function: Monitors the deterioration of main circuit capacitors, control circuit capacitors, and inrush current limit circuits, providing a self-diagnostic alarm when nearing the end of their lifespan.
- Spring Clamp Terminals: For control circuit terminals, offering easier and more secure wiring. Main circuit terminals are screw terminals.
- Brake Resistor Connection: Built-in brake transistor for 0.4K or higher models. Optional brake resistors can be connected to increase regeneration capability, useful for reducing deceleration time on high-inertia loads.
- Password Function: Allows parameter read/write restriction with a 4-digit password.
- Regeneration Avoidance Function: Automatically increases frequency during regeneration to prevent trips.
- Optimum Excitation Control: Optimizes motor efficiency for energy saving, particularly with variable load torque applications like fans and pumps.
- Power Failure-Time Deceleration-to-Stop Function: Decelerates the motor to a stop upon power failure or undervoltage.
- Dancer Control: Enables tension control using PID control based on dancer roll position signals.
- Traverse Function: Prevents unevenness and deformation in winding applications.
- Compact and Space Saving: Installation size comparable to the FR-S500 series, allowing for side-by-side installation with no clearance.
- Easy Maintenance: Cooling fans are easily replaceable without disconnecting main circuit wires.
- RoHS Directive Compliant: Environmentally friendly design.
- Global Standards Compliance: Complies with UL, cUL, and EC Directives (CE marking). Noise filter options are available for EMC Directive compliance.
- Communication Capabilities: Supports Mitsubishi inverter protocol and Modbus-RTU at speeds up to 38.4kbps.
- PC Software: FR Configurator software available for easy PC-based setup via RS-485 communication, including a conversion function from FR-S500 series parameters.
Standard Specifications
Three-phase 200V Power Supply
| Model | Applicable Motor Capacity (kW) | Rated Capacity (kVA) | Rated Current (A) | Overload Current Rating | Voltage (V) | Regenerative Braking Torque (%) | Power Supply Capacity (kVA) | Protective Structure (JEM1030) | Cooling System | Approx. Mass (kg) |
|---|---|---|---|---|---|---|---|---|---|---|
| FR-D720-...K | 0.1 to 15 | 0.3 to 23.1 | 0.8 to 58.0 | 150% 60s, 200% 0.5s (inverse-time) | 200 to 240 | 150%, 100%, 50%, 20% | 0.4 to 27.0 | Enclosed type (IP20) | Self-cooling / Forced air cooling | 0.5 to 6.5 |
| FR-D740-...K | 0.4 to 15 | 0.9 to 22.5 | 1.2 to 29.5 | 150% 60s, 200% 0.5s (inverse-time) | 380 to 480 | 100%, 50%, 20% | 1.5 to 28.0 | Enclosed type (IP20) | Self-cooling / Forced air cooling | 1.3 to 6.0 |
Single-phase 200V Power Supply
| Model | Applicable Motor Capacity (kW) | Rated Capacity (kVA) | Rated Current (A) | Overload Current Rating | Voltage (V) | Regenerative Braking Torque (%) | Power Supply Capacity (kVA) | Protective Structure (JEM1030) | Cooling System | Approx. Mass (kg) |
|---|---|---|---|---|---|---|---|---|---|---|
| FR-D720S-...K | 0.1 to 2.2 | 0.3 to 4.0 | 0.8 to 10.0 | 150% 60s, 200% 0.5s (inverse-time) | 200 to 240 | 150%, 100%, 50%, 20% | 0.5 to 5.2 | Enclosed type (IP20) | Self-cooling / Forced air cooling | 0.5 to 2.0 |
Single-phase 100V Power Supply
| Model | Applicable Motor Capacity (kW) | Rated Capacity (kVA) | Rated Current (A) | Overload Current Rating | Voltage (V) | Regenerative Braking Torque (%) | Power Supply Capacity (kVA) | Protective Structure (JEM1030) | Cooling System | Approx. Mass (kg) |
|---|---|---|---|---|---|---|---|---|---|---|
| FR-D710W-...K | 0.1 to 0.75 | 0.3 to 1.7 | 0.8 to 4.2 | 150% 60s, 200% 0.5s (inverse-time) | 200 to 230*7,*8 | 150%, 100% | 0.5 to 2.5 | Enclosed type (IP20) | Self-cooling | 0.6 to 1.4 |
Common Specifications
- Control Method: Soft-PWM control / high carrier frequency PWM control (V/F control, General-purpose magnetic flux vector control, and Optimum excitation control available).
- Output Frequency Range: 0.2 to 400 Hz.
- Frequency Setting Resolution:
- Analog Input: 0.06 Hz/60 Hz (terminals 2, 4: 0 to 10V / 10-bit) or 0.12 Hz/60 Hz (terminal 2, 4: 0 to 5V / 9-bit).
- Analog Input (Terminal 4): 0.06 Hz/60 Hz (terminal 4: 0 to 20mA / 10-bit).
- Digital Input: 0.01 Hz.
- Frequency Accuracy:
- Analog Input: Within ±1% of max. output frequency (at 25°C ±10°C).
- Digital Input: Within 0.01% of set output frequency.
- Starting Torque: 150% or more (at 1Hz) with General-purpose magnetic flux vector control and slip compensation.
- Acceleration/Deceleration Time Setting: 0.1 to 3600s (individual setting for acceleration and deceleration). Linear and S-pattern modes available.
- DC Injection Brake: Operation frequency (0 to 120Hz), time (0 to 10s), and voltage (0 to 30%) adjustable.
- Stall Prevention: Operates based on operation current level (0 to 200%).
- Frequency Setting Signal:
- Analog Input: Terminal 2 (0 to 10V or 0 to 5V), Terminal 4 (0 to 10V, 0 to 5V, or 4 to 20mA).
- Digital Input: From operation panel or parameter unit.
- Input Signals: Five terminals configurable for multi-speed selection, remote setting, JOG operation, PID control, external thermal input, etc.
- Output Signals: Open collector output (2 terminals), Relay output (1 terminal). Configurable for inverter operation, over-frequency, overload alarm, etc.
- Pulse Train Output: Available for meter functions (e.g., output frequency, current, voltage).
- Operating Status Display: Available on the operation panel or optional parameter unit, showing frequency, current, voltage, time, and fault records (last 8 faults).
- Protective Functions: Overcurrent, overvoltage, undervoltage, input phase loss (3-phase input only), output phase loss, earth fault, thermal overload, heatsink overheat, parameter error, PU disconnection, CPU fault, brake transistor alarm, analog input error, stall prevention, and safety circuit faults.
- Warning Functions: Fan alarm (0.75K or less models do not have a cooling fan), overcurrent/overvoltage stall prevention, PU stop, parameter write error, regenerative brake prealarm, electronic thermal relay prealarm, maintenance timer alarm, operation panel lock, password lock.
Environmental Specifications
- Surrounding Air Temperature: -10°C to +50°C (maximum, non-freezing).
- Ambient Humidity: 90%RH or less (non-condensing).
- Storage Temperature: -20°C to +65°C.
- Atmosphere: Indoors (no corrosive gas, flammable gas, oil mist, dust, or dirt).
- Altitude/Vibration: Maximum 1000m above sea level; vibration up to 5.9m/s² (10 to 55Hz).
Outline Dimension Drawings
Dimension drawings are provided for various models, including FR-D720, FR-D720S, FR-D710W, and FR-D740 series, in different capacity ranges. Specific dimensions (W, W1, D, D1) are detailed in millimeters.
Terminal Connection Diagram and Specifications
Detailed diagrams and explanations for main circuit and control circuit terminals are provided. This includes connections for AC power input, motor output, brake resistors/units, DC reactors, control inputs (start, speed selection), frequency setting signals (analog voltage/current), open collector outputs, and safety stop functions.
- Main Circuit Terminals: R/L1, S/L2, T/L3 (AC power); U, V, W (Inverter output); P/+, PR (Brake resistor); P/+, N/- (Brake unit); P/+, P1 (DC reactor); Earth (Ground).
- Control Circuit Terminals: STF, STR (Start); RH, RM, RL (Multi-speed); SD (Contact common); PC (24VDC supply); 10 (Frequency setting power); 2 (Frequency setting voltage); 4 (Frequency setting current); 5 (Frequency setting common); FM (Pulse output); PU connector (RS-485 communication); S1, S2 (Safety stop input); SO (Safety monitor output); SC (Safety stop common).
Operation Panel and Parameter Unit
- Operation Panel: Integrated into the inverter, featuring a 4-digit LED monitor, setting dial, mode switches, and function keys. Supports PU, External, and Network operation modes.
- Parameter Unit (FR-PU07 - Optional): Provides direct input via keypad, operation status indication, help function, and supports up to eight languages. Can store parameter settings for up to three inverters.
- Enclosure Surface Operation Panel (FR-PA07 - Optional): Can be mounted on enclosures.
Parameter List
Parameters cover basic operations such as torque boost, maximum frequency, acceleration/deceleration times, and advanced functions like PID control and communication settings. A "simple mode" displays essential parameters by default, with an "extended mode" available by changing Pr. 160.
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.
Official datasheet (PDF)
Curated from selected public technical reference material for discovery and preliminary comparison. This summary is not a substitute for a current certified manufacturer datasheet. Verify revisions and design limits before use.