Datasheet summary
FR-E700
Engineering summary from PDF text extraction for FR-E700. Verify every value with the OEM datasheet.
Summary
Product Identification
The FR-E700 series is a line of inverters.
Key Features
- Advanced Magnetic Flux Vector Control: Achieves high torque performance, with 200%/0.5Hz for models 3.7K or less, and 150%/0.5Hz for 5.5K to 15K models.
- Compact Design: Installation size is compatible with the previous FR-E500 series. Side-by-side installation is possible without clearance.
- Usability Enhancements:
- Setting Dial: Allows for quick parameter setting.
- Easy Setting Mode: Facilitates setup through interactive wizards.
- USB Connector: Standard mini-B connector for easy PC connection using FR Configurator software.
- Optional Operation Panels: Compatibility with FR-PA07 and FR-E500 series panels.
- Optional Parameter Units: FR-PU07 and FR-PU07BB(-L) offer advanced parameter setting, including parameter copying without powering on the inverter (battery pack type).
- Advanced Auto Tuning: Optimizes control for various three-phase induction motors.
- Short Time Overload Capacity: Increased to 200% for 3 seconds.
- Torque Limit/Current Limit Function: Provides machine protection and load limiting.
- Improved Regeneration Capability: Built-in brake transistor for models 0.4K to 15K; optional brake resistors enhance regeneration.
- Enhanced Expandability: Supports various plug-in options for digital input, analog output, and communication protocols (RS-485, Modbus RTU standard; CC-Link, PROFIBUS-DP, DeviceNet®, LONWORKS® optional).
- Long-Life Design: Extended design life for cooling fans (10 years) and capacitors (10 years at 105°C).
- Environment-Friendly: RoHS Directive compliant.
- Safety Stop Function (FR-E700-SC models): Compliant with EN ISO 13849-1 Category 3 / PLd and EN62061 / IEC61508 SIL2 standards, allowing for immediate shutoff of motor output upon activation of an external Emergency Stop device.
- Filter Options: Available for harmonic suppression and EMC compliance.
Standard Specifications
Three-phase 200V Power Supply (Model FR-E720-…K(SC))
| Rating | Applicable Motor Capacity (kW) | Rated Capacity (kVA) | Rated Current (A) | Overload Current Rating | Output Voltage | Regenerative Braking Torque |
|---|---|---|---|---|---|---|
| 0.1K to 15K | 0.1 to 15 | 0.3 to 23.9 | 0.8 to 60 | 150%/60s, 200%/3s | 200 to 240V | 150% to 20% |
Three-phase 400V Power Supply (Model FR-E740-…K(SC))
| Rating | Applicable Motor Capacity (kW) | Rated Capacity (kVA) | Rated Current (A) | Overload Current Rating | Output Voltage | Regenerative Braking Torque |
|---|---|---|---|---|---|---|
| 0.4K to 15K | 0.4 to 15 | 1.2 to 23.0 | 1.6 to 30 | 150%/60s, 200%/3s | 380 to 480V | 100% to 20% |
Single-phase 200V Power Supply (Model FR-E720S-…K(SC))
| Rating | Applicable Motor Capacity (kW) | Rated Capacity (kVA) | Rated Current (A) | Overload Current Rating | Output Voltage | Regenerative Braking Torque |
|---|---|---|---|---|---|---|
| 0.1K to 2.2K | 0.1 to 2.2 | 0.3 to 4.4 | 0.8 to 11.0 | 150%/60s, 200%/3s | 200 to 240V | 150% to 20% |
Single-phase 100V Power Supply (Model FR-E710W-…K)
| Rating | Applicable Motor Capacity (kW) | Rated Capacity (kVA) | Rated Current (A) | Overload Current Rating | Output Voltage | Regenerative Braking Torque |
|---|---|---|---|---|---|---|
| 0.1K to 0.75K | 0.1 to 0.75 | 0.3 to 2.0 | 0.8 to 5.0 | 150%/60s, 200%/3s | 200 to 230V | 150% to 100% |
Common Specifications
- Control Method: Soft-PWM control/high carrier frequency PWM control (V/F control, Advanced magnetic flux vector control, General-purpose magnetic flux vector control, Optimum excitation control available).
- Output Frequency Range: 0.2 to 400Hz.
- Frequency Setting Resolution: Analog input (0.06Hz/60Hz or 0.12Hz/60Hz), Digital input (0.01Hz).
- Frequency Accuracy: Analog input (±0.5% of max. output frequency), Digital input (0.01% of set output frequency).
- Starting Torque: 200% or more at 0.5Hz (with Advanced magnetic flux vector control, 3.7K or less).
- Acceleration/Deceleration Time: 0.01 to 360s or 0.1 to 3600s (individual settings for acceleration and deceleration), linear or S-pattern modes.
- DC Injection Brake: Operation frequency (0 to 120Hz), time (0 to 10s), voltage (0 to 30%).
- Stall Prevention: Operation current level adjustable (0 to 200%).
- Input Signal Terminals: Seven terminals for standard models, six for safety stop function models.
- Output Signal Terminals: Open collector output (two terminals), Relay output (one terminal).
- FM Terminal (Pulse Train Output): Max. 2.4kHz.
- Operational Functions: Includes frequency jump, automatic restart, forward/reverse prevention, multi-speed operation, stop-on-contact, PID control, and computer link.
- Safety Stop Function: Compliant with EN ISO 13849-1 Category 3 / PLd, EN62061 / IEC61508 SIL2.
Environmental Specifications
- Surrounding Air Temperature: -10°C to +50°C (non-freezing); -10°C to +40°C for totally-enclosed structure models.
- Ambient Humidity: 90%RH or less (non-condensing).
- Storage Temperature: -20°C to +65°C.
- Atmosphere: Indoors (without corrosive gas, flammable gas, oil mist, dust, and dirt).
- Altitude/Vibration: Maximum 1000m above sea level, 5.9m/s² or less at 10 to 55Hz.
Outline Dimension Drawings
Dimension drawings are provided for various series and capacity ranges (FR-E720, FR-E720S, FR-E710W, FR-E740) and optional units (FR-PU07, FR-PU07BB, FR-PA07). Exact dimensions are listed in millimeters (mm) within these drawings.
Terminal Connection Diagrams
Diagrams illustrate the terminal connections for standard control circuit models and safety stop function models, including main circuit, control circuit, analog input, and digital I/O connections.
Disclaimer: Extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.
Official datasheet (PDF)
Curated from selected public technical reference material for discovery and preliminary comparison. This summary is not a substitute for a current certified manufacturer datasheet. Verify revisions and design limits before use.