Summary

Product identification

Lewatit® S 6368 A SO4 is a food grade, macroporous, monodisperse, strongly basic (type I) anion exchange resin based on a styrene-divinylbenzene copolymer.

It is specially applicable for:

  • Removal of acid and simultaneous decolorisation of solutions of organic substances (e.g., sugar, gelatine, glycerine, grape must, whey, fruit concentrates) in its hydroxide (OH⁻) form.
  • Decolorisation of sugar syrup (beet or cane), glycerine, grape must, and fruit juices in its chloride (Cl⁻) form.

The macroporous structure allows for good adsorption of organic substances (e.g., colorants) and partial adsorption of organic and mineral acids. Desorption is achieved by regeneration with caustic soda solution (OH⁻ form) or alkalized brine solution (Cl⁻ form).

Special care should be given to the initial cycles when treating potable water or the listed aqueous solutions. Recommended start-up conditions are available on request.

Product Information

  • Common Description:
    • Delivery form: SO₄²⁻
    • Functional group: Quaternary ammonium, Type 1
    • Matrix: Styrenic
    • Structure: Macroporous
    • Appearance: Beige, opaque
  • Specified Data:
    • Uniformity coefficient: max. 1.1
    • Mean bead size (d₅₀): 0.58-0.68 mm
    • Total capacity (delivery form): min. 1.0 eq/L

Typical Physical and Chemical Properties

  • Bulk density for shipment (+/- 5%): 680 g/L
  • Density: approx. 1.1 g/mL
  • Water retention (delivery form): approx. 60-65 % by weight
  • Volume change (Cl⁻ - OH⁻): max. approx. 22 %
  • Stability pH range: 0-14
  • Stability temperature range: 1-85 °C (Cl⁻); 0-14 (not specified for OH⁻)
  • Storage time (after delivery): max. 2 years
  • Storage temperature range: -20 - +40 °C

Operation

  • Operating temperature: max. 85 °C (Cl⁻); 70 °C (OH⁻)
  • Operating pH range during exhaustion: 0-12
  • Bed depth for single column: min. 800 mm
  • Bed depth per component in mixed bed: min. 500 mm
  • Backwash bed expansion per m/h (20°C): 12 %
  • Specific pressure loss (15°C): 0.8 kPa*h/m²
  • Max. pressure loss during operation: 300 kPa
  • Specific flow rate: max. 5 BV/h
  • Freeboard during backwash: min. 80-100 vol. %

Regeneration

  • NaCl Regeneration:
    • Concentration: approx. 10 wt. %
    • Quantity (co-current): min. 200 g/L resin
    • Quantity (counter-current): min. 200 g/L resin
  • NaOH Regeneration:
    • Concentration: approx. 2-6 wt. %
    • Quantity (co-current): min. 90 g/L resin
    • Quantity (counter-current): min. 50 g/L resin
  • NaCl/NaOH Regeneration:
    • Concentration: 10 wt. % NaCl / 1-2 wt. % NaOH
    • Quantity (co-current): 200 g/L resin / 20 g/L resin
    • Quantity (counter-current): 200 g/L resin / 20 g/L resin
  • Regeneration contact time: min. 20 minutes
  • Slow rinse at regeneration flow rate: min. 2 BV
  • Fast rinse at service flow rate: min. 4 BV

Additional Information & Regulations

  • Safety Precautions: Strong oxidants (e.g., nitric acid) can cause violent reactions. Observe the safety data sheet.
  • Disposal: Dispose of ion exchange resins according to European waste nomenclature.
  • Storage: Store under roof in dry conditions, above freezing point, without direct sunlight. If frozen, allow to thaw gradually at ambient temperature before handling or use. Do not accelerate thawing.
  • Packaging: Packaging stability is limited to 24 months under recommended storage conditions. Use product within this timeframe or check packaging condition regularly.