Datasheet summary
Hydro-Unit Eco
PDF datasheet mirror for Hydro-Unit Eco (Duijvelaar Pumps). Verify with OEM before design.
Summary
Product Identification
This document describes the Hydro-Unit Break-Unit DPVCI ECO-Control series, manufactured by Duijvelaar Pompen. The control unit is specifically identified as ECO-Control.
The identification sticker on the product provides details such as:
- Installation type (e.g., HUV1 DPVCI 2/5(12) B)
- Controller type and startup method (ECO CONTROL)
- Article number (ID)
- Material of appendages and connection size (App.)
- Material of piping and connection size (Con.)
- Dry-running protection type (RDP)
- Order number (PO)
- Installation supply voltage (U)
- Installation frequency (F)
- Maximum current consumption of the installation (Imax)
- Pressure class and construction type (PN)
- Production week/year and number (Prod.)
This version of the manual is valid for ECO-Control software version 3.9/4.1 (from 08/2013).
Operating Limits
The break-unit ECO is designed for pressure boosting in (process) water installations and for pumping liquids with a viscosity identical to water. It is intended for indoor installation only.
- Environment temperature: +4 to 30 °C
- Fluid temperature: +4 to 30 °C
- Maximum working pressure: 600 kPa
- Minimum supply pressure: Minimum such that the supply capacity is in balance with the demand.
- Maximum supply pressure: 250 kPa (on float valve)¹
- ¹A pressure reducing device may be required.
- Pressure class: PN10
- Maximum height: 1000 m above NAP (Dutch sea level reference)
Feed Water
The system is designed to prevent water from flowing back into the public water supply network. It is mandatory when the water consumer works with substances dangerous to public health, complying with water work sheets WB 3.8 class AB and EN 13077. A filter in the supply line is recommended in case of contamination.
Electrical
The ECO-Control unit is designed for a single pump.
- Power supply: 1x230 V 50 Hz
- Maximum fuse protection: 16 A slow
- Pump motor maximum: 1.1 kW – 1x230 V
- Control current protection: Electronic fuse
- Pump short-circuit protection: 2x 10 A slow glass fuses (20x5 mm)
- Earthing: Permanent earthing required.
- Safety: Use of an earth leakage circuit breaker is recommended.
- Hazardous areas: Not developed for and must NOT be installed in hazardous areas.
Inputs (analog and digital):
- 1x analog input 4-20 mA (16 Vdc for pressure sensor in pressure control mode (Par.0=1) / 1.2 Vdc for control in flow control (Par.0=2))
- 1x digital input for RDP (dry-running protection)
- 1x digital input for klixon connection (thermal protection)
- 1x digital input for fire alarm switching
Outputs (digital):
- 1x digital output for pump control (1x230 V – 7.20 A)
- 1x digital output for external potential-free alarm signaling (max. 50 Vac – 1.00 A)
Mechanical / Hydraulic
The installation is identified as HUV1 DPVCI AB ECO-Control.
Installation requirements:
- Clean, dry, dust-free, frost-free, and well-lit space.
- Sufficient space for accessibility.
- Adequate height for the installation space.
- Provision for draining any released water without nuisance.
- System must be free from walls.
- Space designated for technical equipment and secured against unauthorized access.
- Supply and discharge lines must be connected tension-free, preferably with a pipe compensator.
- An optional leak water collection tray can be connected to a drain line.
- Optional wall mounting set available.
Dimensions:
- For the HUV1 DPVCI 40 L HDPE AB installation and the ECO-Control unit, see the official PDF for exact dimensions and drawings.
Parameter Settings
The ECO-Control unit is pre-programmed with factory default settings. The following parameters can be adjusted:
- 0 Pompregeling (Pump control): Default 4 (Break-unit)
- 1 Reset droogloop- en temperatuuralarm (Reset dry-running and temperature alarm): Default 0 (Automatic reset)
- 2 Type droogloopcontact (Type dry-running contact): Default 1 (Closing gives alarm - NO)
- 3 Type drukopnemer (Type pressure sensor): Default 0 (0-10 bar)
- 4 Actie bij drukopnemerfout (Action on pressure sensor fault): Default 1 (Pump off)
- 5 Wenswaarde systeemdruk (Desired system pressure value): Default 2.8 bar
- 6 Bandbreedte drukregeling (Pressure control bandwidth): Default 0.3 bar
- 7 Grenswaarde hogedrukalarm (High pressure alarm limit): Default 9.9 bar
- 8 Reset hogedrukalarm (Reset high pressure alarm): Default 0 (Auto-reset alarm)
- 9 Grenswaarde lagedrukalarm (Low pressure alarm limit): Default 1.0 bar
- 10 Reset lagedrukalarm (Reset low pressure alarm): Default 1 (Manual reset alarm)
- 11 Max aantal starts (Max number of starts): Default 20 n/uur (starts/hour)
- 12 Minimale draaitijd (Minimum running time): Default 60 sec
- 13 Minimale draaitijd-correctie (Minimum running time correction): Default 10 sec
- 14 Vertraging droogloopalarm (Dry-running alarm delay): Default 1 sec
- 15 Vertraging hoge/lagedrukalarm (High/low pressure alarm delay): Default 2 sec
- 16 Proefdraai-interval (Test run interval): Default 1 dagen (days)
- 17 Proefdraaitijd (Test run time): Default 30 sec
- 18 Nominale motorstroom (Nominal motor current): Default Inom Amp (from motor type plate)
- 19 Vertraging overschrijding Inom (Delay for exceeding Inom): Default 5 sec
- 20 Grenswaarde lage motorstroom (Low motor current limit): Default 20 % (% of Inom)
- 23 Type brandalarmcontact (Type fire alarm contact): Default 0 (Opening gives alarm - NC)
- 24 Alarmcontact (uitgang) (Alarm contact (output)): Default 0 (Closed during alarm - NO)
- 25 Vertraging herstel droogloop (Dry-running recovery delay): Default 5 sec
- 26 Reset alle instellingen (Reset all settings): Default 0 (No action)
Alarm Codes
The system provides various alarm codes for conditions such as high/low motor current, activated fire alarm, dry-running protection, temperature input, pressure sensor fault, and high/low system pressure. The lowest alarm code always has priority. See the official PDF for exact tabulated values, auto-reset/manual reset behavior, and pump/alarm relay states.
Disclaimer: This summary is based on extracted text and may not include all figures, footnotes, or the latest revisions from the original OEM PDF. Contractual data must always match the specific OEM PDF revision used for the project.