The Hydro-Unit Premium Line is a pressure booster system available in several configurations:

  • DOL CC: Fixed speed pressure booster system with Megacontrol pump control.
  • VFD CM CC: Variable speed pressure booster system with Megacontrol pump control, frequency inverter in the control cabinet.
  • VFD MM CC: Variable speed pressure booster system with Megacontrol pump control, frequency inverter mounted on the (IE5) motor.

These systems are designed for building services water supply applications.

Operating limits

  • Flow rate (Q): ≤ 65.4 m³/h (≤ 18.2 l/s) (for a system with three pumps, without stand-by pump)
  • Head (H): ≤ 134 m
  • Fluid temperature (T): ≥ 0 °C to ≤ +60 °C
  • Operating pressure (p): ≤ 16 bar
  • Inlet pressure (pᵢₙₗ): ≤ 5 bar (for higher inlet pressures, contact the manufacturer)

Feed water

The system is suitable for handling:

  • Drinking water
  • Service water
  • Cooling water
  • Fluids not chemically or mechanically aggressive to the materials of construction.

Electrical

  • Voltage: 3 × 400 V ± 10 %
  • Frequency: 50 Hz
  • Motor efficiency class:
    • Hydro-Unit Premium Line DOL CC, VFD CM CC: IE3 to IEC 60034-30 (some models may be "IE -", indicating unspecified or lower efficiency)
    • Hydro-Unit Premium Line VFD MM CC: IE5 to IEC 60034-30 (magnetless synchronous reluctance motor)
  • Control cabinet: IP54, sheet steel housing (RAL 7035)
  • Enclosure (System): IP55
  • Sound pressure level: Ranges from 55 dB(A) to 71 dB(A) depending on the specific model.
  • Dry running protection: Sensor

Mechanical / hydraulic

  • Design: Compact system mounted on a common base frame, featuring one or more vertical high-pressure pumps.
  • Pump Control:
    • DOL CC: Power contactor per pump.
    • VFD CM CC, VFD MM CC: One frequency inverter per pump.
  • Multiple pump system features:
    • Check valve per pump
    • Discharge-side gate valve per pump
    • Suction-side gate valve per pump
  • Installation: Stationary dry installation.
  • Automation: Megacontrol micro-processor control unit with a graphical display, operating panel, three LEDs (Green: system ready, Yellow: warning, Red: alert), lockable master switch (repair switch), motor protection switch per pump, and a service interface for Servicetool. Two volt-free contacts are provided for reporting warnings and alerts.
  • Materials:
    • Pump casing: 1.4308
    • Pump shroud: 1.4301
    • Hydraulic system: 1.4301
    • Mechanical seal: To EN 12756
    • Elastomer: EPDM
    • Baseplate: Steel, powder-coated
    • Shut-off valve: Brass, nickel-coated
    • Swing check valve: POM
    • Accumulator, connection: 1.4401
    • Membrane: Approved for drinking water
  • Connections: DN1 and DN2 connections are G 1 1/2, G 2, or PN 16, depending on the model.
  • Dimensions: Detailed dimensions (L1, L2, Lt, H1, H2, Ht, W1, W2, W3, Wt in mm) are tabulated for 2-pump and 3-pump systems across various sizes and stages. See the official PDF for exact tabulated values.

Certifications

  • France: Approved in accordance with the French drinking water regulation.
  • United Kingdom: Approved in accordance with the UK drinking water regulation.
  • Germany: Approved in accordance with German drinking water regulation (specifically for globe valves and swing check valve).