PDF datasheet mirror for DP-Level control (Duijvelaar DP Pumps). Verify with OEM before design.
Summary
Product Identification
The DP-Levelcontrol is a series of control units manufactured by DP-Pumps. It serves as a pump control and monitoring unit.
Example identification from a nameplate:
- Type control panel: DKVO 610
- Control unit type: DPLCII (DP-Levelcontrol)
- Article number: 9041111120
- Pump control: DOL (Direct on line)
- Control: 3 VL (3 Floaters)
- Run-Dry Protection (RDP): Yes
- Rated voltage (U): 3x400V(N)
- Panel: BIW (Inside wall)
- Rated current (Ipump): 1.40/2.00A
- Alarm: SPL (Volt free / dry contact)
- Week/Year of construction (Prod.): 46/2015 - 01
- Firmware version: DP-Levelcontrol V 1.2.4. (01/2016)
Operating Limits
- Temperature during operation: -10 to +40 °C
- Relative humidity: non condensing <85%
- Altitude above MSL (max.): 1000 m
Electrical
- Voltage:
- 1 x 230 (+10% -15%) V
- 3 x 400 (+10% -15%) V
- Frequency: 50/60 (±2%) Hz
- Enclosure:
- 230 V IP54
- 400 V IP54
- Rated insulation voltage: 500 V AC
- Rated current per motor (standard models): 1.0 / 1.6 / 2.5 / 3.2 / 4 / 5 / 6.3 / 10 A
- Main protective electric fuse max:
- 16 A by 1 pump
- 25 A by 2 pumps
- Signalling output: 12.6 V to 13.2 V DC, max. 200 mA (for external alarm equipment)
- Volt-free signalling output: 1 change over contact (250 V, 1A, NO/NC contact)
Features and Functionality
The DP-Levelcontrol is a level-dependent pump control and monitoring unit designed for either one or two pumps.
- General:
- Compact plastic housing
- Includes a display
- DOL (Direct On Line) starting
- Level Detection:
- Float switch/digital level switch
- Analog sensor (4...20 mA)
- Operating Principles:
- Float switch control: Measures level with float switches; pump switches on/off at defined levels; high water alarm activates second pump (if present).
- Hydrostatic pressure sensor: Measures level and converts to a 4-20 mA signal; pump switches on/off at defined levels; high water alarm activates second pump (if present).
- Programming:
- Limited parameters available via the Human Machine Interface (HMI) operating panel.
- Full access to parameters via the service port using a special service port cable.
- Motor Protection:
- Connects to a thermal circuit breaker (bimetal element) to trip the pump in case of excessive heat build-up. Alerts can be auto-acknowledged or require manual acknowledgement depending on the circuit.
- Control Panel:
- 7-segment, 5-character display
- Traffic light LEDs (Red: Alert, Yellow: Warning, Green: Readiness for operation)
- LEDs for pump operating status (Red: blocked, Flashing yellow: manual mode, Yellow: OFF, Flashing green: running, Green: ready)
- "High water" LED (red)
- Navigation keys (Arrow keys, ESC, OK)
- Manual-0-Automatic switch for each pump (Manual: short period, 0: off, Automatic: controlled by unit)
- Service Interface:
- Accessible when the control unit is open.
- Requires an RS 232 cable and "DP-Pumps Service Tool" software (available from DP-Pumps website or Service CD-Rom).
- Measured Value Parameters (Examples):
- Level (Analog): Fill level in millimetres (if analog sensors are used)
- Level (Digital): Switching levels if float switches or digital level switches are used
- Line Voltage: Line voltage in volts
- Operating Hours Pump 1/2
- Start Count Pump 1/2
- Pending Messages: List of acknowledged alerts
- Digital Level Indicator: Provides digital display of current level with associated actions (e.g., Very low: Pump OFF, High: Base load pump ON, High water: High water alert and both pumps ON).
- Additional Connections (J601):
- Auxiliary voltage for lifting unit: Terminals 18 and 19 (not for present device variant).
- Signalling output: Terminals 30 and 31 (12.6-13.2 V DC, max. 200 mA) for external alarm equipment.
- External alarm: Terminals 40 and 41 (e.g., for dry-running protection via NC float switch or sensor). Pumps stop when contact closes (factory setting, configurable via Service Tool). High water alert has priority.
- Remote acknowledgement: Terminals 50 and 51 to acknowledge alerts remotely.
- Additional Connections (J403): Inputs for thermal circuit breakers for Pump 1 (Alert P1: A03, A01) and Pump 2 (Alert P2: A04, A02). Contacts must be bridged if not available at the pump.
- Enable Input: Terminals 001 and 002. If not bridged, pump control is disabled. Fitted with a wire jumper at the factory. For cables longer than 15 metres, a coupling relay is required.
Parameters and Alerts
The control unit allows setting various parameters and provides alerts/warnings. Parameters displayed depend on the operating mode and measurement method.
- Setting Parameters (Examples):
- 3-3-2 Stand-by Pump: 0 = dual-pump station with peak-load operation (factory setting), 1 = stand-by pump (one pump ON at high water), 2 = stand-by pump (two pumps ON at high water).
- 3-3-3 Draining/Filling: 0 = draining (factory setting), 1 = filling.
- 3-3-4-1 Level Pumps OFF: 250 mm (factory setting) for pneumatic, bubbler, 4-20 mA.
- 3-3-4-2 Level Base Load ON: 400 mm (factory setting) for pneumatic, bubbler, 4-20 mA.
- 3-3-4-3 Level Peak Load ON: 500 mm (factory setting) for pneumatic, bubbler, 4-20 mA.
- 3-3-4-4 Level High Water: 600 mm (factory setting) for pneumatic, bubbler, 4-20 mA.
- 3-3-5-3 Stop Delay: 0 s (factory setting).
- 3-4-2 Measurement Method: 0 = float switch (with hysteresis; factory setting), 1 = digital level switch (without hysteresis), 2 = 4-20 mA sensor.
- 3-4-3-1 Level at 4 mA: 200 mm (factory setting).
- 3-4-3-2 Level at 20 mA: 1000 mm (factory setting).
- 3-7-1 Check Run ON/OFF: 0 = functional check OFF (factory setting), 1 = functional check performed after idle period of one week.
- 3-8-1 Factory Reset: 1 = load factory settings.
- 4-1-1 Firmware Version: (Read-only).
- Alerts and Warnings (Examples):
- A1, A2: Motor protection pump 1/2 (Manual mode acknowledgement).
- A3, A4: Motor 1/2 temperature too high (Auto acknowledgement).
- A5: Power supply failure (Auto acknowledgement).
- A6: Phase error (phase failure) (Auto acknowledgement).
- A7, A8: Leakage motor 1/2 (Manual mode acknowledgement).
- A9: High water alert (Auto acknowledgement).
- A10: External alarm (Auto acknowledgement).
- A11: Sensor fault (Auto acknowledgement).
- A12: Incorrect rotary field of mains supply (phase sequence) (Auto acknowledgement).
- A13: Under voltage (-15% of rated voltage 230 V or 400 V) (Auto acknowledgement).
- A14: Over voltage (+15% of rated voltage 230 V or 400 V) (Auto acknowledgement).
- A15: Flat battery (Auto acknowledgement).
- A16: Service interval system (deactivated by default) (Auto acknowledgement).
Mechanical / Hydraulic
The document refers to an "annex 'Built-in diagram'" for correct overall dimensions, but no specific mechanical or hydraulic parameters are provided in the extracted text.
Disclaimer: This summary is based solely on the provided text extract. It may not include all figures, footnotes, or the latest revisions present in the official OEM PDF datasheet. Contractual data must always match the specific OEM PDF revision used on the project.