Datasheet summary
CSM RE8040-BLR
Engineering summary from PDF text extraction for CSM RE8040-BLR. Verify every value with the OEM datasheet.
Summary
Product Identification
The RE8040-BLR is a low pressure grade RO element designed for low brackish water applications.
- Model Name: RE8040-BLR
- General Features: Low-Energy Consumption, High Permeate Flow and High Rejection
- Membrane Type: Thin-Film Composite
- Membrane Material: Polyamide (PA)
- Element Configuration: Spiral-Wound, FRP Wrapping
- Certifications: Certified to NSF/ANSI/CAN 61
Operating Limits
- Max. Pressure Drop / Element: 15 psi (0.10 MPa)
- Max. Pressure Drop / 240” Vessel: 60 psi (0.41 MPa)
- Max. Operating Pressure: 600 psi (4.14 MPa)
- Max. Feed Flow Rate: 75 gpm (17.0 m³/hr)
- Min. Concentrate Flow Rate: 16 gpm (3.6 m³/hr)
- Max. Operating Temperature: 113°F (45°C)
- Operating pH Range: 2.0 – 11.0
- CIP pH Range: 1.0 – 13.0
- Max. Turbidity: 1.0 NTU
- Max. SDI (15 min): 5.0
- Max. Chlorine Concentration: < 0.1 mg/L
Feed Water
Test conditions for performance specifications:
- 1,500 mg/L NaCl solution
- 15% recovery
- 77°F (25°C)
- pH 6.5–7.0
- 150 psig (1.03 MPa) applied pressure
Product Water
- Permeate Flow Rate: 10,000 GPD (37.9 m³/day)
- Nominal Salt Rejection: 99.6% (Minimum 99.5%)
- Permeate flow rate for each element may vary but will be no more than -5%.
- Permeate from the first hour of operation should be discarded.
- Stabilized salt rejection is generally achieved within 1~48 hours of continuous use.
Mechanical / Hydraulic
- Effective Membrane Area: 400ft² (37.2 m²)
- Dimensions:
- A: 40.0 inch (1,016 mm)
- B: 7.9 inch (200 mm)
- C: 1.12 inch (28.5 mm)
- Weight: 15kg
- Accessories Part Numbers:
- Inter-Connector: SWA01049
- Brine Seal: SWA01043
- Each membrane element is supplied with one interconnector (coupler) and four O-rings.
- All RE8040 elements fit nominal 8.0 inch (203.2 mm) I.D. pressure vessels.
- The element shell is FRP (Fiber Reinforced Plastic).
General Handling Procedures
- Elements in boxes must be kept dry at room temperature (7–32°C; 40–95°F) and should not be stored in direct sunlight.
- For WET-TYPE, a preservative solution (1% sodium metabisulfite solution) is added to prohibit the growth of micro-organisms.
- Keep elements moist at all times after initial wetting.
- Avoid excessive pressure and flow spikes.
- Only use chemicals compatible with the membrane elements and components. Use of such chemicals may void the element limited warranty.
- Permeate pressure must always be equal or less than the feed/concentrate pressure. Damage caused by permeate back pressure voids the element limited warranty.
- Be aware of glass fiber strands and use safety equipment.
Disclaimer: This summary is based on the provided text extract. The full OEM PDF datasheet may contain additional figures, footnotes, or revisions not captured here. Contractual data must always match the specific OEM PDF revision used on the project.
Official datasheet (PDF)