CAB3-8040
Engineering summary from PDF text extraction for CAB3-8040. Verify every value with the OEM datasheet.
Summary
Product Identification
- Membrane Element: CAB3-8040
- Type: Spiral Wound
- Membrane Polymer: Blend Cellulose Acetate
Performance
- Permeate Flow: 4,500 gpd (17.0 m³/d)
- Salt Rejection:
- Nominal: 99.0 %
- Minimum: 98.5 %
- Nominal Membrane Area: 340 ft²
Operating Limits
- Maximum Applied Pressure: 600 psig (4.14 MPa)
- Maximum Operating Temperature: 104 °F (40 °C)
- Maximum Feed Flow: 75 GPM (17.0 m³/h)
- Minimum Ratio of Concentrate to Permeate Flow for any Element: 5:1
- Maximum Pressure Drop for Each Element: 10 psi
Feed Water Parameters
- Feedwater Chlorine Concentration: 0.3 - 0.5 PPM (1.0 PPM maximum)
- Feedwater pH Range: 4.0 - 6.0
- Maximum Feedwater Turbidity: 1.0 NTU
- Maximum Feedwater SDI (15 mins): 5.0
Test Conditions
The stated performance is initial (data taken after 30 minutes of operation), based on the following conditions:
- 2000 PPM NaCl solution
- 420 psi (2.89 MPa) Applied Pressure
- 77 °F (25 °C) Operating Temperature
- 10% Permeate Recovery
- 5.0 - 6.0 pH Range
Mechanical / Hydraulic
- Core tube ID: 1.125" (28.6 mm)
- Dimensions:
- A: 40.0" (1016 mm)
- B: 7.95" (201.9 mm)
- C: 1.50" (38.1 mm)
- Weight: 36 lbs (16.4 kg)
- All membrane elements are supplied with a brine seal, interconnector, and o-rings.
- Elements are vacuum sealed in a preservative solution containing copper sulfate and glycerine, and then packaged in a cardboard box.
Notes
- Permeate flow for individual elements may vary + or - 15 percent.
Disclaimer: This summary is based on extracted text and may not include all figures, footnotes, or the latest revisions. Contractual data must match the OEM PDF revision used on the project.