Datasheet summary
CPA5-max-8040
Engineering summary from PDF text extraction for CPA5-max-8040. Verify every value with the OEM datasheet.
Summary
Product identification
- Model: CPA5 MAX-8040
- Configuration: Spiral Wound
- Membrane Polymer: Composite Polyamide
- Nominal Membrane Area: 440 ft² (40.9 m²)
Performance
Stated initial performance (data taken after 30 minutes of operation) is based on the following test conditions:
- 1,500 ppm NaCl
- 225 psi (1.55 MPa) Applied Pressure
- 77 °F (25 °C) Operating Temperature
- 15% Permeate Recovery
- 6.5 - 7.0 pH Range
Performance metrics:
- Permeate Flow: 12,000 gpd (45.5 m³/d)
- Salt Rejection: 99.7 % (99.6% minimum)
Operating limits
- Maximum Applied Pressure: 600 psig (4.14 MPa)
- Maximum Chlorine Concentration: < 0.1 PPM
- Maximum Operating Temperature: 113 °F (45 °C)
- pH Range, Continuous (Cleaning): 2-11 (1-13)
- Maximum Feedwater Turbidity: 1.0 NTU
- Maximum Feedwater SDI (15 mins): 5.0
- Maximum Feed Flow: 75 GPM (17.0 m³/h)
- Minimum Ratio of Concentrate to Permeate Flow for any Element: 5:1
- Maximum Pressure Drop for Each Element: 10 psi
Mechanical / hydraulic
- Dimensions:
- A: 40.0 inches (1016 mm)
- B: 7.89 inches (200 mm)
- C: 1.125 inches (28.6 mm)
- Weight: 36 lbs (16.4 kg)
- All membrane elements are supplied with a brine seal, interconnector, and o-rings.
- Elements are vacuum sealed in a polyethylene bag containing less than 1.0% sodium meta-bisulfite solution, and then packaged in a cardboard box.
- Permeate flow for individual elements may vary +/- 15 percent.
Disclaimer: This summary is based on the provided text extract. It may not include all figures, footnotes, or the latest revisions present in the official PDF datasheet. For contractual data, always refer to the specific OEM PDF revision used on your project.