Datasheet summary
AHC series
Engineering summary from PDF text extraction for AHC series. Verify every value with the OEM datasheet.
Summary
Product identification
AHC filters are liquid-solid separator filters designed for high efficiency and limited pressure loss. These centrifugal separators are widely used in various industrial applications, particularly cooling towers.
Key features include:
- High efficiency to remove sand and heavy suspended solids.
- No interruption flow.
- No filtration screen or internal moving parts.
- Zero maintenance.
- Very low water loss.
AHC filters can remove 98% of sand and/or suspended solids larger than 50 µm. They can be integrated with an automatic drain valve.
Operating limits
- Max working pressure: 10 bar (145 psi)
- Max working temperature: 60 °C (140 °F)
Mechanical / hydraulic
AHC filters support flow rates up to 2750 m³/h (12100 US gpm).
Materials of construction:
- Filter Body: Painted FeC / AISI 304 / AISI 316
- Cover: Painted FeC / AISI 304 / AISI 316
- Body support: AISI 304 / AISI 316
- Gasket: EPDM
Inlet/outlet connections: Flanged connections according to EN 1092-1.
Drain connections: Threaded connections (thrdF).
Technical data by model:
| Filter model | Inlet/outlet diameter | Max flow rate | Min flow rate | Drain Conn. |
|---|---|---|---|---|
| AHC L1½ | 1"½ flanged | 20 m³/h (88 US gpm) | 10 m³/h (44 US gpm) | 1" thrdF |
| AHC L2 | 2" flanged | 30 m³/h (132 US gpm) | 20 m³/h (88 US gpm) | 1" thrdF |
| AHC L3 | 3" flanged | 70 m³/h (308 US gpm) | 30 m³/h (132 US gpm) | 1" thrdF |
| AHC L4 | 4" flanged | 120 m³/h (528 US gpm) | 60 m³/h (264 US gpm) | 1" thrdF |
| AHC L6 | 6" flanged | 280 m³/h (1232 US gpm) | 120 m³/h (528 US gpm) | 2" thrdF |
| AHC L8 | 8" flanged | 450 m³/h (1980 US gpm) | 250 m³/h (1100 US gpm) | 2" thrdF |
| AHC L10 | 10" flanged | 750 m³/h (3300 US gpm) | 400 m³/h (1760 US gpm) | 2" thrdF |
| AHC L12 | 12" flanged | 1000 m³/h (4400 US gpm) | 600 m³/h (2640 US gpm) | 2" thrdF |
| AHC L16 | 16" flanged | 1600 m³/h (7040 US gpm) | 900 m³/h (3960 US gpm) | 2" thrdF |
| AHC L20 | 20" flanged | 2750 m³/h (12100 US gpm) | 1400 m³/h (6160 US gpm) | 2" thrdF |
Dimensions (Shape L):
| Filter Model | A [mm] | B [mm] | C [mm] | D [mm] | E [mm] | F [mm] | G [mm] | Weight [Kg] |
|---|---|---|---|---|---|---|---|---|
| AHC L1½ | 280 | 140 | 1200 | 950 | 200 | 280 | 45 | 30 |
| AHC L2 | 330 | 168 | 1400 | 1150 | 200 | 300 | 55 | 35 |
| AHC L3 | 380 | 219 | 1750 | 1500 | 250 | 350 | 65 | 55 |
| AHC L4 | 460 | 273 | 2050 | 1800 | 250 | 400 | 80 | 100 |
| AHC L6 | 590 | 406 | 2400 | 2100 | 300 | 710 | 120 | 220 |
| AHC L8 | 700 | 508 | 2600 | 2250 | 150 | 600 | 145 | 290 |
| AHC L10 | 800 | 610 | 3000 | 2650 | 150 | 705 | 165 | 450 |
| AHC L12 | 900 | 711 | 3500 | 3100 | 150 | 810 | 190 | 550 |
| AHC L16 | 1100 | 914 | 4700 | 4250 | 150 | 1020 | 250 | 1100 |
| AHC L20 | 1200 | 1016 | 5600 | 5100 | 150 | 1120 | 250 | 1900 |
Head loss: Information regarding head loss curves or data is indicated but not provided in the extracted text. See the official PDF for exact tabulated values or graphs.
Disclaimer: This summary is based solely on the provided text extract. It may not include all figures, footnotes, or the latest revisions present in the complete OEM PDF datasheet. For contractual data, always refer to the specific OEM PDF revision used on your project.