Acutec 35 Gas Detection System
Engineering summary from PDF text extraction for Acutec 35 Gas Detection System. Verify every value with the OEM datasheet.
Summary
Product identification
The Acutec™ 35 is a self-testing gas detection system designed for ambient air monitoring. It is available in a compact, modular design with sensors for chlorine (Cl₂), ammonia (NH₃), or sulfur dioxide (SO₂).
Key Benefits
- Gas detection for Chlorine, Ammonia or Sulfur Dioxide
- Simple and neat installation of module components
- Easy access to control panel via a hinged cover on the NEMA 4X enclosure
- Audible horn to provide local warning
- Choice of Detector or Monitor version
- Sunlight readable 4 digit LED on the monitor
- Single or multipoint gas detection systems
- Automatic integral gas generator
Installation
The modular system allows for single or multipoint configurations. Each detection point requires one sensor/transmitter and one receiver module. The sensor/transmitter is installed in the area to be monitored, and the receiver module can be located up to 1000 feet away. Receiver modules and a power supply module are housed in NEMA 4X enclosures.
Enclosure
- NEMA 4X Polystyrene enclosures with knockouts for 1/2” (12.7 mm) FNPT conduit hubs.
- Provided with four conduit hubs for single-point enclosures and seven for dual-point enclosures.
- Fitted with a hinged polycarbonate window.
- Includes a piezoelectric horn for audible local warning.
Receiver Module
Two versions are available:
- Detector: Signals gas presence, includes two gas alarm set points, three configurable alarm relays, and a separate sensor alarm relay.
- Monitor: Includes all Detector features plus a 4-digit LED display of gas concentrations (PPM) and an isolated 4-20mA output.
Both versions are switch-programmable for full-scale range and feature front panel switches for alarm acknowledgement, reset, relay inhibition, Auto-Test activation, and LED indicator testing.
Power Supply Module
- Accepts AC input between 85-255 VAC, 50/60 Hz.
- Provides a regulated 12 VDC output for receiver modules.
- Supports up to two receiver modules.
- Includes a power failure alarm relay.
- Powers an integral audible alarm and charges the optional battery back-up.
Sensor/Transmitter
- Combines an electrochemical gas sensor with a transmitter, housed in a NEMA 4X enclosure.
- Digitally converted measurements are sent to the receiver module up to 1000 feet away via two-wire cable.
- Optional auto-test facility with an integral gas generator performs daily sensor tests and alarms on failure or reduced sensitivity.
Optional Battery Back-Up System
- Consists of a sealed lead-acid battery in its own enclosure.
- Maintains receiver functions for a minimum of 12 hours (single point) or 6 hours (dual point) in the event of power failure.
- Features automatic, continuous battery charging via the power supply module.
Technical Data
Gases Detected
- Chlorine (Cl₂)
- Sulfur Dioxide (SO₂)
- Ammonia (NH₃)
Gas Ranges
- Cl₂: Std. 0-10 ppm, Min. 0-5 ppm, Max. 0-50 ppm
- SO₂: Std. 0-20 ppm, Min. 0-10 ppm, Max. 0-100 ppm
- NH₃: Std. 0-100 ppm, Min. 0-50 ppm, Max. 0-500 ppm
Power Requirements
- 85-255 VAC, 50/60 Hz, 1 Amp - Self-regulating
Ambient Conditions
- Temperature: 0° to 105°F (-18° to 40°C) continuous; -10° to 120°F (-23° to 49°C) intermittent
- Humidity: 0-99% non-condensing
Gas Alarm Setpoints
- 2 independent setpoints
- Warning Level: adjustable from 5% to 100% of range
- Alarm Level: adjustable from 5% to 100% of range
Alarm Indicators
- High intensity LED bars
- Warning indicator: non-latching
- Alarm indicator: latching
Alarm Relays
- Three assignable alarm relays (SPDT) for alarm setpoints.
- 10A at 120 VAC, 5A at 250 VAC, resistive.
- Configurable for normal/fail-safe, latching/non-latching, and fast/slow operation.
Sensor Alarm
- Indicates loss of sensor/transmitter input or failure of optional sensor Auto-Test.
- Includes a front panel LED indicator and a relay (10A at 120 VAC, 5A at 250 VAC, resistive SPDT, factory set to fail-safe).
Monitor Features
- Concentration Display: 4-digit LED, sunlight readable.
- Concentration Output Signal: Isolated 4-20 mA DC, 1000 ohms maximum load.
Power Supply Output
- Regulated 13.7 VDC, 1A supplied to 1 or 2 receivers. Also used for battery charging, audible back-up, and integral alarm horn power.
Audible Alarm Horn
- Weatherproof 12 VDC piezoelectric horn with 85-dB output.
Power Failure Alarm Relay
- Indicates loss of AC input power.
- 1 relay (10A at 120 VAC, 5A at 250 VAC, resistive SPDT).
Gas Sensor
- Type: Electrochemical gas diffusion
- Connection Distance: Up to 1000 feet (300 m) to receiver via two-wire cable.
- Dual point units include 50 ft. (15 m) of cable.
- Single point units include 25 ft. (8 m) of cable.
- Operating Life: 2 years
- Storage Life: 5 years
Optional Battery Back-Up
- Battery Type: 12 VDC, 4 Amp HR sealed lead-acid
- Battery Capacity:
- Single point unit: min. 12 hrs. (avg. 24 hrs.)
- Dual point unit: min. 6 hrs. (avg. 12 hrs.)
- Charge Control: Current limited to 0.75A max.
- Charge Time: Typically 10 hours from fully discharged.
- Low Voltage Cutoff: Relay disconnect at 10 VDC.
- Battery Life: Min. 3 yrs. in operation.
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.