Datasheet summary
DEOX 2000 Analyzer for SO2 Dechlorination
Engineering summary from PDF text extraction for DEOX 2000 Analyzer for SO2 Dechlorination. Verify every value with the OEM datasheet.
Summary
Product identification
The DEOX/2000® is a dechlorination measurement module for on-line analysis of sulfite and total chlorine residuals. It is designed for use with either the SFC or MFC electronic packages.
Applications
- Municipal wastewater chlorination / dechlorination processes
- Cooling water
- Industrial process water and wastewater
Standard Features
- Continuous, on-line measurement of both sulfite and chlorine residuals
- Five operating ranges available:
- 0.5mg/L SO₂ - 0.5mg/L Cl₂
- 1.0mg/L SO₂ - 1.0mg/L Cl₂
- 2.5mg/L SO₂ - 2.5mg/L Cl₂
- 5.0mg/L SO₂ - 5.0mg/L Cl₂
- 10.0mg/L SO₂ - 10.0mg/L Cl₂
- Proven, amperometric, three-electrode measuring cell
- Unaffected by varying water quality, turbidity, temperature, or conductivity
- Stable chloramine-T reagent for iodine bias generation
Optional Features
- Choice of peristaltic pump speed (1 rpm for monitoring, 2 rpm for control)
- Sample line dosing with a biocide metering pump to prevent biofouling
- Circular chart recorders with "zero-centered" chart ranges
Technical Data
Type of Measurement
Amperometric. Continuously measures and indicates Sulfite or Chlorine residuals.
Accuracy
+/- 5% of full scale (over the range from SO₂ to Cl₂ residual).
Sensitivity
2% of full scale.
Repeatability
0.001 mg/L or 1% of full scale, whichever is greater.
Stability
+/- 5% of full-scale for 1 month under favorable conditions. Recalibration may be required upon replenishment of the Iodate reagent.
Speed of Response
- 90 seconds with 2 rpm pump motor.
- 180 seconds with 1 rpm pump motor.
Output Signal
Isolated 4-20mA DC analog output proportional to residual, zero centered. Maximum impedance 600 ohms.
Sample Requirements
- Approximately 10 to 20 l/m (2 - 5 US gpm).
- Recommended fluid velocity: 1.5 m/sec (5 ft/sec).
- Maximum pressure: 8 bar (125 psi), throttled to less than 0.3 bar (5 psi) at the Y-strainer inlet.
- Measuring cell sample requirement: 0.5 l/m.
Reagents
- pH 4 buffer solution.
- Potassium Iodate solution.
- Detergent (added to pH 4 buffer).
Salinity
Fresh to sea water.
Piping Connections
- Sample line: 13 mm (1/2”) female NPT.
- Drain hose: 1 mm (3/8”) and 32 mm (1-1/4”).
Temperature
- Ambient: 2°C (35°F) to 52°C (125°F).
- Sample: -3° C (26°F) to 52° C (125°F).
Mounting
Wall or control panel mounting.
Dimensions (W x H x D)
331 x 329 x 251 mm (13-1/16” x 12-15/16” x 9-13/16”).
Shipping Weight
9 kgs (20 lbs).
SFC Electronics
Output Contacts
4 configurable alarm contacts / general fault messages, inc/dec control outputs. Max. 5A, 250 VAC, 1250 VA; Max. 5A, 220 VDC, 150 W.
Analog Outputs
1 available 0/4 to 20 mA, configurable. Load <500 Ohm, accuracy < 0.5% FS. Galvanically isolated up to 50V.
Interfaces
RS 232; RS 485.
Power Supply
- 100 - 240 VAC ±10%, 50-60 Hz, 30VA
- 24 VDC ±20%, 30 W
Protection Category
IP 66 / NEMA 4X.
Dimensions (W x H x D)
270 x 147 x 185 mm (10-5/8” x 5-13/16” x 7-1/4”).
Shipping Weight
2 kg (4.4 lbs).
MFC Electronics
Output Contacts
8 configurable alarm contacts / general fault messages, inc/dec control outputs. Max. 5A, 250 VAC, 1250 VA; Max. 5A, 220 VDC, 150 W.
Analog Outputs
4 available 0/4 to 20 mA, configurable. Load <1000 Ohm, accuracy < 0.5% FS. Galvanically isolated up to 50V.
Interfaces
RS 232; RS 485.
Power Supply
- 200 - 240 VAC ±10%, 50-60 Hz, 30VA
- 100 - 120 VAC ±10%, 50-60 Hz, 30VA
- 24 VDC ±20%, 30 W
Protection Category
IP 66 / NEMA 4X.
Dimensions (W x H x D)
320 x 270 x 175 mm (12-5/8” x 10-5/8” x 6-7/8”).
Shipping Weight
5.5 kg (12.1 lbs).
Accessories Furnished
Y-strainer, shut-off valve, two manual throttling valves for sample waterline, 3 ft. tubing for analyzer drains, 2 empty 1-gallon reagent bottles, pH 4 buffer (15 liters / 4 US gallons), Potassium Iodate (4.8 oz bottle and 1 lb granular), detergent (6 oz), tube of grit, instruction book, 3-way valve for calibration with de-ionized water.
Optional Accessories
Recorders, metering pump for sample line dosing system, amperometric titrator for calibration, sample pump, spare reference junction, door lock for analyzer enclosure.
Disclaimer
This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.