Datasheet summary
Depolox Pool E 700 P Pool Managemet System
Engineering summary from PDF text extraction for Depolox Pool E 700 P Pool Managemet System. Verify every value with the OEM datasheet.
Summary
Product identification
The DEPOLOX® Pool E 700 P is a pool management system designed for measurement and control functions in pool water treatment applications. It is part of the WALLACE & TIERNAN® ANALYZERS/CONTROLLERS product line.
Design and Function
The system consists of a DEPOLOX Pool E flow cell module and a 700 P electronic module. The intelligent measurement module, housed in a non-corrosive enclosure, can be fitted with up to five sensors and features a clear flow cell with optional illumination. The flow cell is available in both pressureless and pressurized versions.
Measurement Module
- Processes sensor data and transmits it via a single CAN bus cable to the 700 P electronics.
- Ensures stable measurements through:
- pH compensated free chlorine measurement with a 3-electrode chlorine sensor.
- Temperature compensation.
- Constant sample water flow controlled by a flow valve.
- Quartz grit hydromechanical cleaning of chlorine sensor electrodes.
- Optimized sample water flow to each sensor.
- Integrated multi-sensor for temperature, flow switch, and earthing.
- Optional LED indicators (red, yellow, white) for sensor status.
Electronic Module
- Features a 7” colour touch panel for intuitive operation.
- Incorporates communication interfaces: RS 485, USB, and Ethernet.
- Supports various chemical feed applications including dosing pumps, relay control feeders, chlorine gas feed control, on-site electrochlorination, and control signals to UV systems and flocculation/activated carbon slurry feed systems.
- Can measure and control free chlorine, pH, ORP, combined and total chlorine, and conductivity.
- Provides control outputs for chemical feed devices.
- Includes 8 alarm/relay outputs, expandable to 12, which are freely configurable.
Operating Limits and Conditions
Flow Cell Module
- Controlled sample water flow: 33 l/h
- Flow control valve:
- Control range: 0.2 – 3.0 bar at valve inlet (3 – 43 psig)
- Maximum back pressure: Up to 1.5 bar at valve outlet (0 to 22 psig)
- Maximum sample water temperature: 50 °C
- Multi-sensor switching point: 18 l/h ± 3 l/h with a hysteresis of 2 l/h.
- Sample water connections: PVC hose 6 x 3 mm or PE hose 6 x 1 mm; hose connectors on 1/2 ” union.
- Voltage supply (flow cell): 24 V DC from the electronic module via CAN connection.
- Weight (incl. packing): approx. 2.5 kg (5.5 lbs)
- Dimensions: 253 x 375 x 163 mm (8.5 x 15 x 6 inches)
Electronic Module
- Power supply: 100 – 240 V ± 10% 50/60 Hz, 48 W; 24 V DC, 30 W.
- Ambient temperature: 0 – 50 °C (32 – 122 °F).
- Enclosure: IP 66.
- Dimensions: 320 x 311 x 153 mm (12.5” x 12” x 12.9”).
- Weight with packaging: approx. 4.5 kg (10 lbs).
Sensors and Measurements
Sensor Inputs (Supported)
- 1 x Free chlorine
- 1 x pH
- 1 x ORP (oxidation reduction potential)
- 1 x Temperature (Pt 1000)
- 1 x Flow switch
- 1 x Total chlorine/combined chlorine
- 1 x Conductivity
Specific Sensor Details
- Free chlorine:
- Measuring range: 0 to max 20 mg/l (scale freely selectable).
- Resolution: Up to 10 mg/l: 0.01 mg/l; up to 20 mg/l: 0.1 mg/l.
- Temperature compensation: 0 – 50 °C.
- Total chlorine:
- Measuring range: 0 to max 20 mg/l (scale freely selectable).
- Resolution: Up to 10 mg/l: 0.01 mg/l; up to 20 mg/l: 0.1 mg/l.
- Temperature compensation: 0 – 45 °C.
- Applicable for salt water pools with up to 4 % salt concentration.
- Combined chlorine:
- Calculated and displayed as the difference between total and free chlorine.
- Displayed range: 0 to max 20 mg/l (scale freely selectable).
- Resolution: Up to 10 mg/l: 0.01 mg/l; up to 20 mg/l: 0.1 mg/l.
- pH value:
- Measuring range: 0 to 14 pH (scale freely selectable in 1 pH steps).
- Resolution: 0.01 pH.
- Temperature compensation: 0 – 50 °C.
- ORP:
- Measuring range: 0 to 400 mV or 500 to 1000 mV (scale freely selectable in 100 mV steps).
- Resolution: 1 mV.
- Conductivity:
- Measuring range: 500, 2500 µS/cm, 10, 20, 50, 100, 200, 300 mS/cm.
- Resolution: 0.1 mS/cm.
- Can be switched to NaCl display in mg/l and %.
- Temperature compensation: 0 – 50 °C.
- Temperature:
- Measured by integral Pt 1000 sensor.
- Measuring range: 0 to 50 °C.
- Resolution: 0.1 °C.
Electronic Module Interfaces and Outputs
Touchpanel Display
- 7-inch graphic display with backlight.
- Resistive touch screen.
- Resolution: 800 x 480 pixels.
Inputs
- Analog inputs: 1 x feed rate display; 2 x free selectable for circulation recording.
- Digital inputs: 3 x freely selectable (e.g., controller stop, mode changeover, second set point).
Output Contacts
- Alarm/Relay outputs: Max. 8 freely selectable alarm contacts/general alarm signal, controller outputs for free chlorine, combined chlorine, pH, and conductivity.
- Extendable with internal contact module.
- Maximum rating: 6 A / 250 V AC, 0.2 A / 220 V DC.
Analog Outputs (Optional)
- 4 x 0/4 – 20 mA, freely configurable.
- Load protected ≤ 500 Ohm.
- Accuracy: < 0.5 % FS.
- Galvanically isolated up to 50 V relative to earth.
Communication Interfaces
- SD card slot: For storage of process and archived data.
- USB interface: For firmware uploads/downloads and parameter adjustment via USB stick.
- Ethernet interface: For remote access (VNC Server) and Modbus® TCP protocol.
- RS 485: Two-wire bus connectivity.
- CAN Bus interface: For universal digital machine communication with sensors and measuring modules.
- Fieldbus connectivity: Optional field bus converter for Profibus® DP.
Integrated Functions and Controls
- DIN Contact: Transmits water parameter status according to DIN 19643.
- Economic Mode: Allows for reduced circulation volume based on internal clock, flow limit, or digital input.
- CEDOX Control Algorithm: Optimized chlorine residual control for economical use.
- Additional Integrated Pool Controls:
- Start-stop control of UV or activated carbon slurry feed systems.
- Control of salt concentration in salt water pools (with optional conductivity sensor).
- Flocculation control, proportional to circulation amount.
- Peak Chlorination: Freely adjustable for optimizing water quality.
- Chemical Feed Rate Indication: Real-time display and optional stop at maximum thresholds.
Integral Safety Functions
- Safety shutdown for circulating pump failure, supply-tank-empty, sample water failure, and low circulation amount.
- Feed time monitoring and delay.
- Controller stop at sensor failure.
Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.