Summary

Product Identification

This document describes Evoqua's WALLACE & TIERNAN® MULTI SENSOR VALIDATION SYSTEMS, specifically the Triple Validation Monitor and Dual Validation Monitor, which can be used with DEPOLOX® analysers for chlorine residual and turbidity measurements.

Key Benefits

  • Improve confidence in water quality
  • Minimise chances of out-of-specification water
  • Improved security and validity of readings
  • High reliability of readings
  • Increased confidence in analysers
  • Reduced response priority to problems
  • Proof of diligence to regulators

Technical Specification

Triple Validation Monitor

Power Supply

  • Voltage Range: 100-240V AC (auto sensing), 24Vdc as a special option
  • Frequency Range: 50-60Hz
  • Power: 30 VA
  • Fuse: 2A internal (Non-replaceable)

Digital Input

  • 7 x volt free: 24V DC @ 4mA nom. (internal supply)
  • Optical Isolation

Digital Output

  • 6 x relay: SPST, volt free
    • 24V @ 30W dc Max
    • 250V @ 200W ac Max
  • Watchdog Output: SP NC relay contact

Analogue Input

  • 3 x Scaled range 4-20mA
  • Resolution: 14 bit Unipolar (5µA)
  • Input impedance: 250 Ω
  • Isolation: All analogue signals isolated using discreet multi-way signal isolators (see Note 1)

Analogue Output

  • 2 x Scaled range 4-20mA
  • Resolution: 14 bit Unipolar (5µA)
  • Max. load impedance: 600 Ω
  • Isolation: All analogue signals isolated using discreet multi-way signal isolators (see Note 1)

Re-transmission Output

  • 3 x Scaled range 4-20mA
  • Error < 0.1% of end value
  • Max. load impedance: 600 Ω
  • Isolation: All analogue signals isolated using discreet multi-way signal isolators (see Note 1)

Enclosure

  • Environmental: IP65 (door closed)
  • Operating temperature: 0 - 40°C (90% non-condensing)
  • Storage temperature: -20 to +70°C
  • Mounting: Wall mounted painted steel enclosure, Landscape

Physical

  • Dimensions: 300 x 400 x 150mm (h x w x d)
  • Weight: 8kg

Dual Validation Monitor

Power Supply

  • Voltage Range: 100-250V AC (auto sensing), 24Vdc as a special option
  • Frequency Range: 50-60Hz
  • Power: 30 VA
  • Fuse: 2A internal (Non-replaceable)

Digital Input

  • 2 x volt free: 24V DC @ 4mA nom. (internal supply)
  • Optical Isolation

Digital Output

  • 4 x relay: SPST, volt free
    • 24V @ 30W dc Max
    • 250V @ 200W ac Max
  • Watchdog Output: SP NC relay contact

Analogue Input

  • 2 x Scaled range 4-20mA
  • Resolution: 14 bit Unipolar (5µA)
  • Input impedance: 250 Ω
  • No Isolation

Analogue Output

  • 1 x Scaled range 4-20mA
  • Resolution: 14 bit Unipolar (5µA)
  • Max. load impedance: 600 Ω
  • No Isolation

Enclosure

  • Environmental: IP65 (door closed)
  • Operating temperature: 0 - 40°C (90% non-condensing)
  • Storage temperature: -20 to +70°C
  • Mounting: Wall mounted plastic enclosure, Landscape

Physical

  • Dimensions: 260 x 350 x 250mm (h x w x d)
  • Weight: 5kg

Note 1 All analogue signals to and from the Validation Monitor are isolated using discreet multi-way signal isolators.

Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.