Back to Testomat
Testomat logo

Datasheet summary

Testomat 2000 V

Engineering summary from PDF text extraction for Testomat 2000 V. Verify every value with the OEM datasheet.

Summary

Product identification

Testomat 2000® V is a control system for measuring water hardness and carbonate hardness/alkalinity in blending water. It is designed for use with a proportional 3/2-way motor valve with a 0/4-20mA interface.

Application

  • Regulation of water blending systems (cooling circuits, process water).

Measuring range

  • Water hardness: 1.0–25.0 °dH
  • Carbonate hardness: 1.0–20.0 °dH (depending on indicator choice)

Technical Data

Electrical

  • Power supply: 230–240 VAC, 115 VAC, 24 VAC (all 50–60 Hz)
  • Power consumption: max. 30 VA
  • Protection class: I
  • Degree of protection: IP 65

Mechanical / hydraulic

  • Dimensions (W x H x D): 380 x 480 x 280 mm
  • Weight: approx. 9.5 kg
  • Water inlet: Opaque hose with 6 mm external diameter / 4 mm internal diameter
  • Water outlet: Hose with 6 mm external diameter / 4 mm internal diameter
  • Mains water supply operating pressure:
    • 1 to 8 bar (15 to 116 psi)
    • 0.3 to 1 bar (5 to 15 psi) (after removing the valve body from the regulator/filter housing)
  • Water temperature: 10 to 40 °C (50 to 104 °F)
  • Ambient temperature: 10–45 °C (50 - 104 °F)
  • Option: booster pump (see accessories)

Other

  • Menu languages: German, English, French, Italian (others upon request)

Disclaimer: This extraction may miss figures, footnotes, or revisions. Contractual data must match the OEM PDF revision used on the project.